As per ISO-14644-1, the equipment under test CONFIRMS to "ISO Cleanliness class 5"' as the both 95% UCL and the
CONCLUSION individual readings for all the locations for 0.3 and 0.5 micrometre size particles are within the prescribed limits at the
time of validating as on 26.05.2020
NOTE: Given below is the table showing maximum allowable particle concentration per cubic meter of sampled air as stipulated in the standard
Classification Abbreviation
number 0.1 mic 0.2 mic 0.3 mic 0.5 mic 1 mic 5 mic SD Standard Deviation
ISO Class 1 10 2 10 SE Standard Error
ISO Class 2 100 24 102 4 UCI Upper Concentration Limit
ISO Class 3 1000 237 1020 35 8
ISO Class 4 10000 2370 10200 352 83 Formulae :-
ISO Class 5 100000 23700 102000 3520 832 29
ISO Class 6 1000000 237000 1020000 35200 8320 293 SE= SD/SQUARE ROOT ( No of locations)
ISO Class 7 352000 83200 2930 95% UCL= Mean+ [T- Factor x SE]
ISO Class 8 3520000 832000 29300
ISO Class 9 35200000 8320000 293000
SEAL
Authorised Signatory
Date : 26.05.2020
Page 2 of 2
REPORT OF FILTER INTEGRITY TEST USING PAO AEROSOL
TEST REPORT REFERENCE SSEPL/FI/TR/2019-2020 Dt: 26.05.2020
CLIENT M/s. BESTON INDUSTRIES
SITE M/s. EMS MEMORIAL CO–OPERATIVE HOSPITAL & RESEARCH CENTRE LTD.
AREA/ EQUIPMENTUNDER TEST Laboratory / BBC01GI A2 Serial no. 85
DATE OF TESTING 26.05.2020
TESTED BY Mr. Ananthan Of M/s. Shree SulajEnvirotech (p) Ltd.
IN THE PRESENSE OF Mr. Akhil K.P.
DETAILS OF TEST EQUIPMENT USED
"TEC Services, Inc., USA", Model No. PH 5" Aerosol Photometer" having Serial number 1862calibrated on
23.03.2019 and valid up to 23.03.2020 vide Calibration certificate TVSPL/SER/CC/TEC/SSEPL/S/SK/19-
20/017PH SN: 1862 dated 23.03.2019 of M/s. Technovalue Solutions Pvt. Ltd., Mumbai.
LASKIN NOZZLE PAO GENERATOR
FILTER INTEGRITY TEST PROCEDURE
The filter under test is challenged with an aerosol produced by mixing the output of the Laskin nozzle PAO
generator with ambient air resulting in an upstream aerosol PAO concentration of around 20 Mcg/Lit. The
compressed air pressure is maintained at 20 psi. The test is conducted at the operating air flow volume of the
equipment under test. 100% and 0% setting are done on the photometer for the relevant aerosol and the
filter is scanned for leaks. The maximum allowable leak is 0.010%
Test Area HepaFilter
Upstream
Filter Upstream Down Stream
Equipment concentration Test Result
Ref. concentration concentration
micgms / lit
BSC:BBC01GIA2Sr.No.85 F1 23 100% 0.0% Passed
Authorised Signatory
Date : 26.05.2020
REPORT OF AIR VELOCITY TEST
TEST REPORT REFERENCE SSEPL/AV/TR/20192020 Dated: 26.05.2020
CLIENT M/s. BESTON INDUSTRIES
SITE M/s. EMS MEMORIAL CO–OPERATIVE HOSPITAL &
RESEARCH CENTRE LTD.
AREA/ EQUIPMENTUNDER TEST Laboratory / BBC01GI A2 Serial no. 85
DATE OF TESTING 26.05.2020
TESTED BY Mr. Ananthan Of M/s. Shree SulajEnvirotech (p) Ltd.
IN THE PRESENSE OF Mr. Akhil K.P.
Details Of Test Equipment Used
Vane Type Anemometer of make "LUTRON, Model AM4201 bearing serial number Q843429 Calibration on
11/10/2019 and calibration valid up to 11/10/2020 Vide calibration Certificate MTO-2027-01/19-20 Dt:
11.10.2019 of M/s. Macro Calibration Services, Chennai.
Authorised Signatory
Date : 26.05.2020