PROTECTION FUNCTIONS
ANSI Code Protection Elements PAC-F100 PAC-M100 PAC-T100
OPERATOR INTERFACE
8
2
1 9
2 10
3 11
4 12
5 13
6
14
7
ORDERING OPTION
PAC - -100 - - -
Protection (F :Feeder /
M :Motor / T :Transformer)
Power Control
(P0 :AC 110~220V, DC 80~300V / P1 : DC 19~130V) <Draw-Out type>
OVERVIEW
PAC-x100 is multi-protections and multi-functions management PAC-x100 has 4 setting groups and enables optimal protection
relay. PAC-F100 is Feeder Manager, PAC-M100 is Motor schemes activating a different setting group manually or
Manager, and PAC-T100 is Transformer Manager. automatically according as system operation conditions change.
Also, programmable logic (EasyLogic ) implements trip logic,
PAC-F100 can be used, irrespective of grounding method, for interlock sequence, lock-out, etc. without external logic
distribution line, transmission line, and transformer back-up controller or connections.
protection & monitoring/control, also can be applied to private
power networks with directional protection elements. PAC-x100 s Event & Fault Waveform Recording function
provides oscillographic data for fault analysis and logging
PAC-M100 is for MV/HV Asynchronous Motor or Motor Feeder information of equipment operation. All these data are stored
with protections of Over Current / Earth Fault, Start-up, Start in Non-Volatile memory and can be retrieved by integrated
Inhibit, Thermal, Negative Seq, Phase Unbalance, Under software tool of PACManagerTM through RS232 port on front
Current, and Over & Under Voltage. panel.
PAC-T100 is configurable to apply for 2 or 3 winding PAC-x100 has 8 basic LEDs and 8 user-defined LEDs, supports
transformers with Current Differential, Phase / Earth / Negative convenient menu trees on graphic LCD, and provides
Seq Over Current, Over Excitation, Single Phase Over / Under switchgear control measures by push buttons on front panel.
Voltage protections.
PAC-x100 has 1 RS232 port (DB9) on front panel to connect
PAC-x100 has various diagnosing and checking functions such software tool and 2 RS485 ports on rear side terminal blocks to
as Watch Dog Timer & Self Diagnosis, Current Input Circuit connect to SCADA with ModBus, DNP3.0, and IEC 60870-5-103
Monitoring, Current / Voltage Unbalance Monitoring, PT Fuse communication protocols.
Monitoring, Trip Circuit Supervision (TCS) as well as all kinds of
electric value measurements.
FUNCTIONAL DESCRIPTIONS
Protection & Detection
Each protection element has commonly Enable / Disable /
Event setting item, so it can be incorporated with EasyLogic
to make a protection element operate only in special
conditions.
Instantaneous / Ratio Current Differential between 3-phase currents vector sum (3I0) and current value
from CT on grounding (Ig), maximum current value among 3
Protection (50/87, 87T) phase currents is used for Restraint current, and this element is
This element is primary protection for transformer of 2 or 3 operated as Definite Time by ratio setting of Differential
windings of Wye / Delta connections. It consists of 2 element, 1) current to Restraint current.
Instantaneous / Definite Time element operated by simple
magnitude difference between primary and secondary
currents, and 2) Current Ratio Differential operated as 3I0-Ig Operation Zone
Instantaneous / Definite Time by ratio setting of Differential
current to Restraint current. Winding connection method,
capacity, CT ratio are configured by software tool. Differential
current is a vector sum of phase currents and Restraint current
is a half of scalar sum of phase currents. Ratio characteristics
have 2 stages of Low Current and High Current zones. Ratio
differential protection provides 1) 2 /5 Harmonics restraint
element to prevent mal-operation caused by inrush or over-
excitation of transformer, and 2) a function to compensate 87G
Zero-sequence Current at external ground fault of Wye
Max(Ia, Ib, Ic)
Grounded system. Basically, Wye-connection CT is used, but the
Figure 5. Restricted Earth Fault Protection Scheme
existing Phase Compensation CT can be applied.
Current
Inrush
Figure 6. Direction Detection at A-phase Earth Fault
Pickup Value
Inrush Detection (I2f/I1f)
Normal Current This element is used to detect Inrush Current caused by
energization of long-distance line, transformer, reactor, etc.
Time and to prevent mal-operations by other protection elements,
Figure 4. Cold Load Current and it is operated as Instantaneous / Definite Time by the ratio
of 2nd harmonic component (I2f) to fundamental component
Restricted Earth Fault Protection (87G) (I1f) of current value. Other protection elements can restrain
This REF element is used for sensitive earth fault protection their own operation by setting “BLOCK” property during
near to grounding point of Wye connection Neutral grounding Inrush Detection.
transformer for which normal Ratio Current Differential (87T)
element cannot be applied due to small fault current value.
Differential current for this element is the value difference
Waveform Recording
Push Buttons
PAC-x100 manager relay has fault oscillograph function up to 8 4 push buttons for CB control (Local/Remote, Select, Open,
waveforms with 64 sampling rate (32 for PAC-T100 of Close) and 7 push buttons for display / setting (4 Arrows, Menu,
transformer manager relay) in non-volatile memory. Waveform Enter, Reset) are provided. “Reset” button is used to clear and
has maximum 4 second recording time, where current, voltage, reset protection element operation and self-diagnosis.
I/O contacts, protection element status are included. Trigger
condition to start recording can be I/O contact status change, RS232 Communication Port
protection element operation, and combination of internal 1 RS232 serial communication port is provided to connect to
logic configuration by EasyLogicTM. And trigger position can be integrated software tool of PACManagerTM. This software tool
set in 0~99% location of total waveform size. Recorded is used for setting / configuration change, event / waveform
waveforms can be uploaded to PACManagerTM locally or by data retrieval & analysis, logic editing, firmware update, etc.
SCADA remotely. The waveform is of COMTRADE file format so
that it can be used for fault simulation with fault analysis and
relay test equipment.
MANAGEMENT RELAY
Voltage Input AC 110~220V 20%(50/60Hz)
Power Control Power Consumption DC 80~300V, DC 19~130V
30VA
Rated Current 5/1A, 50/60Hz
Input Range 0.1~250A (5A rated value)
0.01~50A (1A rated value)
Current 0.001~0.12A (67Ns Current)
Burden 0.5VA / Phase
Thermal Withstand Capability 1 sec (100 times of rated value)
4 sec (20 times of rated value)
Continuous (3 times of rated value)
Rated Voltage 50.0~240.0V, 50/60Hz
Input Range 1~450V
Voltage
Burden 0.5VA
Thermal Withstand Capability Continuous (~450V)
Number 16
Voltage Range Maximum DC 250V
Contact Input On/Off Voltage Level DC 19~130V On: 19V, Off: 14V
DC 80~300V On: 80V, Off: 60V
Time 10 msec
Trip
Number 6 / NO
Make and Carry 16A, Continuous AC 250V
30A, 0.3 sec DC 125V, Resistance Load
Breaking Capacity 5A, 0.1 Power Factor, AC 250V
5A, L/R 25msec, DC 125V
Contact Output Signal
Number 8 / NO, 2 / NC
Make and Carry 5A, Continuous AC 250V
5A, 0.3 sec DC 125V, Resistance Load
Breaking Capacity 1A, 0.1 Power Factor, AC 250V
1A, L/R 25msec, DC 125V
Construct Draw-out Type
Material Fe
Enclosure Weight 6.5kg
Terminal Block U / Ring Lug
Inside-diameter: 4mm, Outside-diameter: 8mm(Max.)
Standard IEC 60068-2-1/2
Temperature Operation (Ambient): -25~70
Environment Storage: -30~75
Humidity RH 30~95%
Altitude 1000m
Insulation IEC 60255-5, ANSI/IEEE C37.90.0
Insulation Resistance 100 , DC 500V
AC Power Frequency Voltage withstand 2kV, 1 min.
Lightening Impulse Voltage withstand 5kV, 1.2/50
EMC
1MHz burst IEC 60255-22-1, ANSI/IEEE C37.90.1
2.5kV, 1MHz
Surge Immunity IEC 60255-22-5 class IV
4.0kV, 1.2 x 50
Type Test Fast Transient IEC 60255-22-4 class IV, ANSI/IEEE C37.90.1
4.0kV, 2.5kHz, 5/50ns
Electrostatic Discharge IEC 60255-22-2 class III
6.0kV (Contact), 8.0kV (Air)
RFI Susceptibility IEC 60255-22-3 class III, ANSI/IEEE C37.90.2
10V/m, 27MHz~500MHz
Line Conducted HF IEC 61000-4-6 class III
10V, 150kHz~80MHz
Vibration IEC 60255-21-1 class
16.7Hz, 0.4mm, 600sec
Front/Back/Left/Right/Top/Bottom
Shock IEC 60255-21-2 class
30g, Front/Back/Left/Right/Top/Bottom
Operating Value 3% of Setting value
Operating Time 40msec ( 800msec Op. Time)
Accuracy 3% ( 800msec Op. Time)
Reset Value 96~98% of Pickup value
Reset Time 40msec
Phase Angle 3
TECHNICAL SPECIFICATIONS
Protection: PHASE / GROUND OVER CURRENT (50/51, 50N/51N) Protection: NEGATIVE PHASE SEQUENCE OVERVOLTAGE (47)
Setting Setting
Pickup Current 0.50~100.00A, 0.01 step Pickup Voltage 5~170V, 1 step
Operating Delay 0.00~60.00sec, 0.01step Operating Delay 0.00~60.00sec, 0.01step
Time Multiplier 0.01~10.00, 0.01 step
Trip Characteristic Curve
IEC 60255-3 Protection: UNDER/OVER FREQUENCY (81U/O)
-Normal Inverse, Very Inverse, Extremely Inverse, Long Inverse Setting
ANSI/IEEE Mode Under, Over
-Inverse, Short Inverse, Long Inverse, Moderately Inverse Pickup Frequency 45.00~65.00Hz, 0.01step
Very Inverse, Extremely Inverse, Definite Inverse Pickup Undervoltage 5~170V, 1 step
KEPCO df/dt -10.00 ~ +10.00, 0.01step
-Normal Inverse, Very Inverse, Definite Normal Inverse Operating Delay 0.00~180.00sec, 0.01step
Protection: SENSITIVE DIRECTIONAL GROUND OVER CURRENT (67NS) Protection: AUTO-RECLOSING (79)
Setting Setting
Direction Disable/Forward/Reverse Shot Number 1~4, 1step
Polarizing Voltage Source -3V0,Vg Prepare Condition EasyLogic
Pickup Current 1~100mA, 1 step Cycle Start Condition EasyLogic
Pickup Voltage 5~170V, 1 step Cycle Stop Condition EasyLogic
Operating Delay 0.00~60.00sec, 0.01step Prepare Time 0.05~200.00sec, 0.01 step
Maximum Torque Angle -90~90º, 1º step Discriminating Time 0.01~5.00sec, 0.01 step
Reclaim Time 0.01~350.00sec, 0.01 step
Protection: THERMAL OVERLOAD (49) 1st ~ 4th Shot Delay 0.01~300.00sec, 0.01 step
Setting
K-Factor for IEC 60255-8 0.10~4.00, 0.01 step Protection: CIRCUIT BREAKER FAILURE (50BF)
Time Constant( ) 1.0~999.9min, 0.1step Setting
Cooling Time Factor(Tcf) 1.0~10.0 , 0.1step Trip Relay T1, T2, T3, T4, T5, T6
Thermal Alarm 50~100% of trip temperature, 1step Pickup Current (CB Closed) 0.50~2.50A, 0.01 step
Operating Delay (Trip Timer) 0.00~60.00sec, 0.01step
Protection: UNDERCURRENT (37)
Setting Protection: START-UP MONITORING/STALL
Pickup Current 0.10~5.00A, 0.01 step PROTECTION FOR MOTOR (48/51L)
Operating Delay 0.00~180.00sec, 0.01step Setting
Start-up Current 5.00~90.00, 0.01 step
Protection: NEGATIVE PHASE SEQUENCE OVER CURRENT (46)
Start-up Time 1.0~180.0sec, 0.1 step
Setting Locked Rotor Time 0.5~180.0sec, 0.1 step
Pickup Current(I2) 0.50~100.00, 0.01 step Speed Switch None, DI1~DI16
Operating Delay 0.00~60.00sec, 0.01step
Time Multiplier 0.01~10.00, 0.01 step Protection: START INHIBIT FOR MOTOR (66/68)
Trip Characteristic Curve
IEC 60255-3 Setting
-Normal Inverse, Very Inverse, Extremely Inverse, Long Inverse Start 1.00~50.00A, 0.01 step
ANSI/IEEE Stop 0.10~1.00A, 0.01 step
-Inverse, Short Inverse, Long Inverse, Moderately Inverse Start Monitoring Time 5~120min, 1 step
Very Inverse, Extremely Inverse, Definite Inverse Cold Start Number 1~5, 1 step
KEPCO Hot Start Number 0~5, 1 step
-Normal Inverse, Very Inverse, Definite Normal Inverse Consecutive Start Interval 1~120min, 1 step
Emergency Start Switch None, DI1~ DI16
Protection: PHASE UNBALANCE PROTECTION (46U)
Protection: INSTANTANEOUS DIFFERENTIAL FOR TRANSFORMER (50/87)
Setting DIFFERENTIAL PROTECTION FOR TRANSFORMER (87T)
Minimum Pickup of I1 0.50~5.00, 0.01 step
Pickup Current of I2/I1 2~80%, 1 step Transformer setting
Operating Delay 0.0~60.00sec, 0.01step Transformer Type Y_Y, Y_D, …, D_D_D
Phase compensation select Internal (software), External
Protection: PHASE OVERVOLTAGE (59) Lagging Angle 0, 30, …, 300 lag
PHASE UNDERVOLTAGE (27) Winding setting
Rated Voltage 0.01~600.00kV, 0.01 step
Setting Rated VA 0.01~600.00MVA, 0.01 step
Pickup Voltage 5~170V, 1 step CT Ratio 5~10000, 5 step
Time Multiplier 0.01~10.00, 0.01step Inzone Grounding Yes, No
Operating Delay (Definite Time) 0.00~60.00sec, 0.01step Instantaneous Differential Setting
Trip Characteristic Curve Pickup 10~150A, 1 step
Refer to 12 page <TC CURVE> Operating Delay 0.00~60.00sec, 0.01step
Differential Protection Setting
Minimum Pickup 0.20~2.50 A, 0.01 step
Protection: RESIDUAL/GROUND OVERVOLTAGE (59G) Operating Delay 0.00~60.00sec, 0.01step
Setting Slope1 5~100 %, 1 step
Source -3V0, Vg Slope2 20~200 %, 1 step
Pickup Voltage 5~170V, 1 step Knee Point 5.0~100.0A, 0.1 step
Time Multiplier 0.01~10.00, 0.01step Harmonic Restraint Mode None, 2nd Harm, 5th Harm,
Operating Delay(Definite Time) 0.00~60.00sec, 0.01step 2nd or 5th Harm
Trip Characteristic Curve 2nd Harmonic Level(I2d/I1d) 5.0~40.0 %, 0.1 step
Refer to 12 page <TC CURVE> 5th Harmonic Level(I5d/I1d) 5.0~40.0 %, 0.1 step
Measurement
Item PAC-F100 PAC-M100 PAC-T100
RMS Current value & phase angle per 3-phase, 0.5~250A
Current
±0.5%(0.5~45A), ±1.0%(>45A) 3-Winding
Voltage RMS Voltage value & phase angle per 3-phase Single phase
Harmonics 1st ~ 31st Harmonic Analysis for each phase of current and voltage
Total Harmonic Distortion (THD)
Demand A, W, Var, VA
TC CURVES
Protection TC Curve K L C
IEC Normal Inverse 0.14 0.02 0.00
IEC Very Inverse 13.50 1.00 0.00
IEC Extremely Inverse 80.00 2.00 0.00
IEC Long Inverse 120.00 1.00 0.00
ANSI Inverse 8.9341 2.0938 0.17966
Phase / Ground
Over current (51/51N) ANSI Short Inverse 0.2663 1.2969 0.03393
ANSI Long Inverse 5.6143 1 2.18592
Negative Phase Sequence ANSI Moderately Inverse 0.0103 0.02 0.0228
Over curren (46)
ANSI Very Inverse 3.922 2 0.0982
ANSI Extremely Inverse 5.64 2 0.02434
ANSI Definite Inverse 0.4797 1.5625 0.21359
KEPCO Normal Inverse 0.11 0.02 0.42
KEPCO Very Inverse 39.85 1.95 1.08
KEPCO Definite Normal Inverse 0.0515 0.02 0.114
Phase Over Voltage (59) Inverse 10.5 1.75 0.00
Phase Under Voltage (27) Inverse 8.0 2.2 0.00
Residual/Ground Trip Inverse 12.5 2 0.35
Overvoltage (59G) Alarm Inverse 24.75 2.23 4.15
-Over Current : Operation time is equal more 2000% and 2000% of setting value.
-Over Voltage : Operation time is equal more 800% and 800% of setting value.
Thermal Overload
With Pre-load Without Pre-load
t : Trip Time
: Time Constant(min.)
I : Current Input Value
IN : Rated Current
Ip: Pre-load Current
k : Overload Ratio
DIMENSIONS
PAC - T100
28
13
16
1
17
2
18
3
19
4
20
5
21
6
22
7
23
8
24
9
25
31 10
46 26
32 11
47 27
33 12
48
34
49 42
35 43
50 44
36 58
51 59
52 60
37
38 89
53 90
39
54 30
40 45
55 74
41 75
56
57
[Seoul Office]
6F, Kwangmyung B/D, 115-3, Bangi-dong, Songpa-gu,
Seoul, 138-050 Korea
Tel : +82-2-2240-8106 Fax : +82-2-2240-8195
URL : http://www.pnctech.co.kr E-mail : ttegur@pnctech.co.kr
Deuy Park, Overseas Sales & Marketing Manager
CA - 2007 - 10
Designed by Korea Yellow Pages Tel.82-2-2279-9607 www.yellowpage-kr.com