The document discusses adjusting the speed control parameters of a motor to address issues with undershooting the leveling speed. It recommends increasing the Speed Control Gain and reducing the Speed Control Integral Time used for Low Speed at Stop. It also notes that the specific parameters to change depend on the C5-05 setting and whether a third set of speed loop settings is used, referring to a section in the manual on page 119 for more details on speed loop adjustments.
The document discusses adjusting the speed control parameters of a motor to address issues with undershooting the leveling speed. It recommends increasing the Speed Control Gain and reducing the Speed Control Integral Time used for Low Speed at Stop. It also notes that the specific parameters to change depend on the C5-05 setting and whether a third set of speed loop settings is used, referring to a section in the manual on page 119 for more details on speed loop adjustments.
The document discusses adjusting the speed control parameters of a motor to address issues with undershooting the leveling speed. It recommends increasing the Speed Control Gain and reducing the Speed Control Integral Time used for Low Speed at Stop. It also notes that the specific parameters to change depend on the C5-05 setting and whether a third set of speed loop settings is used, referring to a section in the manual on page 119 for more details on speed loop adjustments.
Motor stops shortly Speed control Increase the Speed Control Gain and reduce
(undershoot) loop responds the Speed Control Integral Time
when the leveling too slow. used for Low Speed at Stop. The parameters to speed is reached. be changed depend on the setting of C5-05 and whether a third set of speed loop settings is used. Refer to Speed Loop Adjustments (CLV and CLV/PM) on page 119. Motor stops shortly (undershoot) when the leveling speed is reached.
Speed Loop Adjustments (CLV and CLV/PM)
The speed control loop uses four different gain and integral time settings that can be adjusted using C5-parameters. The settings are switched over when the motor speed reaches the level set in parameter C5- 07. • Proportional gain and integral time C5-03/04 are used at start when the speed is lower than the setting of C5-07. • Proportional gain and integral time C5-01/02 are used at speeds above the setting of C5-07. • Proportional gain and integral time C5-13/14 are used at stop when leveling speed is selected as speed reference and the speed is lower than the setting of C5-07. • Proportional gain and integral time C5-19/20 are used During Position Lock at start in CLV/PM. Increase the gain and shorten the integral time to increase speed control responsiveness in each of the sections. Reduce the gain and increase the integral time if vibration or oscillation occurs.