INSTALL OVAL EYEBOLT 5/8" GALVANIZED

NEUTRAL WIRE SHALL BE WHITE OR NATURAL GRAY

ANY COLOR EXCEPT WHITE

DRIP LOOP AT LEAST 1.5 m


(W/ PHASE MARKINGS

LINESIDE CONDUIT SHALL BE RSC(EXPOSED)

INSTALL CLAMPS ON CONDUIT

INSTALL MERALCO METER BASE

MAIN DISCONNECTING MEANS


(MAIN CIRCUIT BREAKER/FUSIBLE LINK)
1.6 - 1.83 m

INSTALL GROUND TERMINAL FOR TERMINATION OF


NEUTRAL WIRE
INSTALL CONDUIT FOR GROUND WIRE (PVC/RSC)

USE SOLDERLESS CONNECTOR OR GROUND CLAMP

GROUND WELL

INSTALL GROUND ROD (8 FT.)

FOR ST-5 METER BASE (1PH) FOR ST-7 METER BASE (3 PH)

4" X 8" X 12" 5" X 10 " X 18

CONDUIT HUB SIZE IS 2 INCHES CONDUIT HUB SIZE IS 2 1/2 INCHES

CONCENTRIC KNOCKOUT PROVISION CONCENTRIC KNOCKOUT PROVISION


AT THE SIDES AND BACK CAN AT THE SIDES AND BACK CAN
ACCOMODATE ACCOMODATE
UP TO 1 1/2 INCH CONDUIT ONLY UP TO 2 1/2 INCH CONDUIT ONLY

CONCENTRIC KNOCKOUT PROVISION CONCENTRIC KNOCKOUT PROVISION


AT THE BOTTOM CAN ACOMMODATE AT THE BOTTOM CAN ACOMMODATE
UP TO 2-INCH COUNDUIT UP TO 2 1/2 INCH COUNDUIT

LINE AND LOAD WIRE SIZES: LINE AND LOAD WIRE SIZES:
# 6 AWG UP TO 4/0 AWG CU-AL # 6 AWG UP TO 4/0 AWG CU-AL

NEUTRAL OR 3rd WIRE SIZES: NEUTRAL OR 4th WIRE SIZES:


# 8 AWG - 2/0 AWG CU-AL # 8 AWG - 2/0 AWG CU-AL

TYPICAL SERVICE ENTRANCE INSTALLATION


FOR SELF - CONTAINED METERING
(Date Implemented January 2007) NO. DATE DESCRIPTION DATE APPD

MANILA ELECTRIC COMPANY


ORTIGAS AVE, PASIG CITY, METRO MANILA PHILIPPINES