Professional Documents
Culture Documents
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A Handling, Storage and Preservation
Verify that approved procedures for handling, storage and preservation of Schedule"Q"
A1 emergency eyewash / shower lists all the required inspection schedules for Att IV Section
maintaining the quality of the material and /or equipment. 5
All equipment and materials shall meet this Standard and ANSI Z358.1, SAES-B-069
B3
Eyewash and Shower Equipment. Para 4.1.4
Eyewash and showers shall be constructed of a material resistant to SAES-B-069
B4
corrosion in their installed environment Para 4.3.1
Verify that the water supply piping shall be consistent with materials SAES-B-069
B5
provided for the source water system as specified in SAES-L-132 Para 4.3.2
A combination eyewash/shower unit shall be capable of flowing through
SAES-B-069
B6 both units simultaneously with the flow rate, pressure, and temperature
Para 5.2.2
requirements specified herein.
Eyewash nozzles shall be protected with covers, which can be easily SAES-B-069
B7
removed, to prevent nozzle contamination and clogging. Para 5.2.5
Permanently installed emergency eyewashes shall be provided with
pressure controllers or self-regulating orifices to ensure that eyes will not be
injured due to excessive water velocity if the water supply pressure SAES-B-069
B8
exceeds the 207 kPa (30 psig) design flowing pressure in ANSI Z358.1, Para 5.4
unless the system is designed such that this pressure could not be
exceeded.
The water supply system shall be designed as a potable water system in
accordance with SAES-L-310, SAES-S-040, SAES-S-060 and SAES-S-070
SAES-B-069
B9 for design requirements including cross-connection constraints and
Para 5.5
backflow preventer requirements between potable water and other
systems.
Page 1 of 2
SAUDI ARAMCO ID/PID - 6/30/2008 - REV 3 (Standards Cutoff - March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Emergency Eyewash/Shower Receiving, Handling, Storage
SAIC-B-4001 30-Apr-13 PLUMB
and Preservation
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
*Acceptable evidence shall be a label or tag on the equipment marked ANSI Z358.1, or a certified test report from a recognized independent testing
laboratory indicating that the equipment has been tested and conforms to ANSI Z358.1.
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-B-069 -- Emergency Eyewash and Showers, 23 January 2012
2-Schedule "Q" -- Saudi Aramco quality Requirements, February 2008
3-ANSI Z-358.1 -- American National Standard for Emergency Eyewash and Shower Equipment, 1990
Page 2 of 2