SAUDI ARAMCO ID/PID - 6/30/2008 - REV 3 (Standards Cutoff - March 2012) Rev 6 31-Mar-12

SAIC NUMBER DATE APPROVED QR NUMBER


SAUDI ARAMCO INSPECTION CHECKLIST
Emergency Eyewash/Shower System Installation SAIC-B-4002 30-Apr-13 PLUMB
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
B Emergency Eyewash/Shower Accessories
An appropriate sign with words in Arabic and English shall be mounted in a
clearly visible location near each permanent Emergency Shower and
Eyewash. Words shall be as shown below:
Emergency Shower: Emergency Eyewash: SAES-B-069
B1 -Get into shower immediately -Flush Eye Immediately Para 6.4.3
-Remove Contaminated clothing -Hold eyes open rolling them back and forth during flushing
while showering -Flush for at least 15 minutes
-Shower for at least 15 minutes -Summon medical assistance
-Summon medical assistance
All permanently installed eyewashes and showers shall be provided with
SAES-B-069
B2 drainage for periodic testing, such as surface drainage to a catch basin, to a
Para 6.6.1
gravel filled pit or to a suitable area.
Floor drains shall be installed under eyewash or combination eyewash and SAES-B-069
B3
safety showers located within buildings. Para 6.6.2
Permanently installed safety shower and eyewash units shall have a vertical
background area nominally 1 m wide by 2 m high painted with either SAES-B-069
B4
alternating green and white stripes approximately 152 mm wide or a solid Para 6.4.1
green color (refer to SAES-B-067).
If an alarm is provided, the alarm shall be activated when either the SAES-B-069
B5
eyewash or safety shower is activated Para 6.5.2
If an alarm is provided, the alarm shall sound at a location that is attended
SAES-B-069
B6 during all working hours, such as a control room and the vicinity of the
Para 6.5.2
eyewash/shower
If an alarm is provided, the alarm shall be activated by a flow switch or by SAES-B-069
B7
microswitches on the operating valves. Para 6.5.2
If an alarm is provided, the alarm shall show on a visual display board or the
SAES-B-069
B8 plant's DCS display in the attended location to identify the location of the
Para 6.5.2
emergency.
Shower Enclosures, if used, shall provide for a minimum unobstructed area SAES-B-069
B9
of 34 inches in diameter. (ANSI Z358.1 Para 4.4) Section 6.1
Water supply systems shall be certified as suitable for the purpose by Saudi
SAES-B-069
B10 Aramco Environmental Compliance Division/ Environmental Protection
Para 6.7.1
Division.

C Emergency Eyewash/Shower supply and drainage piping connection

No permanent or temporary connections shall be made to the water supply SAES-B-069


C1
for other purposes Para 6.3.2
A strainer shall be provided in the water supply to permanently installed SAES-B-069
C2
eyewash to prevent solid particles from entering the eyes. Para 6.3.3
SAES-B-069
C3 Block valves in the water supply system shall be car-sealed open.
Para 6.3.1
SAES-B-067
C4 Car-sealed valves of any type shall be painted safety orange.
Para 4.2.4 b
Connections between dissimilar metals shall be by means of a dielectric or SAES-S-060
C5
insulating union. Para 604.11.2b
Cross-Connection and Backflow Prevention - The water supply system shall
be designed as a potable water system in accordance with SAES-L-310;
SAES-B-069
C6 SAES-S-040; SAES-S-060 and SAES-S-070 for design requirements
Para 5.5
including cross-connection constraints and backflow preventer requirements
between potable water and other system.
SAES-B-069
C7 Color Coding and Identification
Para 6.4
All newly constructed and existing repaired or modified domestic water
piping shall be protected from contamination during installation and shall be SAES-S-060
C8
disinfected in accordance with the requirements of Section SASC-S-17, of Para 613.0
Saudi Aramco Sanitary Code, GI-0151.006.

Page 1 of 2
SAUDI ARAMCO ID/PID - 6/30/2008 - REV 3 (Standards Cutoff - March 2012) Rev 6 31-Mar-12
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Emergency Eyewash/Shower System Installation SAIC-B-4002 30-Apr-13 PLUMB
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
REMARKS:

REFERENCE DOCUMENTS:
1-SAES-B-069 -- Emergency Eyewash and Showers, 23 January 2012
2-SAES-B-067 -- Safety Identification and Color-Coding, 17 February 2010
3-SAES-S-070 -- Installation of Utility Piping System, 9 February 2011
4-ANSI Z-358.1 -- American National Standard for Emergency Eyewash and Shower Equipment, 2004

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: Name, Organization, T&I Witnessed QC Record Reviewed Work Verified
Name, Sign and Date:
Initials and Date:
*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 2 of 2