EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A2
2. Circular bands shall not be less than 1 inch (25mm) wide nor SAES-K-100
less than equivalent to the gage of the duct material it supports. Section 604.2.2
Horizontal Duct shall have a support within two feet of each elbow and SAES-K-001
A3
within 4 feet of each branch intersection (SMACNA Para 5.1.1) Para 4.8.12.6
Concrete fasteners shall be installed after the concrete has been poured SAES-K-001
A5
and the forms have been removed. (SMACNA Para. 5.2.2) Para 4.8.12.6
The support spacing interval and method of contact with the duct
SAES-K-100
A6 assembly shall be selected to avoid structural failure or closure failure in
Section 1
the duct. (UMC Para. 6.204 A)
When Ducts are supported from wall they shall be located against the
SAES-K-001
A10 wall or maximum of 2" away from wall. Weld, bolt or No. 8 (Min) screw
Para 4.8.12.6
may be used as fasteners. (SMACNA FIG 5-9 Note No. 2)
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Fastener (for supporting ducts from wall) shall be located within 1" of the
duct edge (wall side) and within 2" of the duct outer edge. Minimum of 3 SAES-K-001
A11
on 24" width and up is required in addition along sides nearest anchors. Para 4.8.12.6
(SMACNA FIG 5-9)
Round Ducts riser from floor shall be supported by split band support by
supplemental angle or channel spanning the slab opening or as
recommended by the manufacturer. Minimum of two fasteners in each
half of band is required. (SMACNA FIG. 5-10) SAES-K-001
A13
Note: No. of fasteners and spacing shall be as shown in Construction Para 4.8.12.6
drawings. If Construction drawings do not address the number of the
fasteners and/or spacing of them then the number of the fasteners and
spacing shall be as instructed by Saudi Aramco (SMACNA FIG 5-10)
REFERENCE DOCUMENTS:
1-SAES-K-001 -- Design and Installation of Heating, Ventilating and Air Conditioning Systems, 05 December 2012
2-SAES-K-100 Saudi Aramco Mechanical (HVAC) Code, 20 October 2012
3-SMACNA -- HVAC Duct Construction Standards, Metal & Flexible, Fourth Edition
4-Uniform Mechanical Code (UMC), 2009
ATTACHMENTS:
1-Table 6-7-Duct Supports
The support system shall not penetrate a bearing member in such a manner as to cause excessive loading on
the member
(UMC Para. 6.204 G)