C1103 – 03 (2009)
NOTE 5—The user of this practice is advised that a wetted interior minimum volume of 2.5 ft3.
surface is desirable and will produce more consistent results. Air may pass
through the walls of dry pipe. This can be overcome by wetting the pipe. 8.2 Joint Air Test:
8.2.1 Review procedures in 8.1.
7.3 Review safety precautions in Section 6.
8.2.2 Pressurize the void volume with air to 3.5 psi greater
8. Procedures than the pressure exerted by groundwater above the pipe.
Allow the air pressure and temperature to stabilize before
8.1 The following procedures apply to testing with either air
shutting off the air supply, and start of test timing.
or water.
8.2.3 If pressure holds, or drops less than 1 psi in 5 s, the
8.1.1 Determine groundwater conditions surrounding the
joint is acceptable. Practically, the test is a go/no go test.
sewer line to be tested, and select the type of test to be
8.2.4 If the joint being tested fails, it shall be retested, or
conducted.
repaired if necessary, and retested, in accordance with this
8.1.2 If the groundwater pressure is equal to or greater than
practice.
the test pressure, and the sewer line or joint is not leaking, the
8.2.5 After the joint test is completed, exhaust void volume,
sewer line or joint is acceptable in accordance with Practice
then exhaust end element tubes prior to removal of apparatus.
C969 and no additional testing is required. If one or more joints
8.2.6 Use or failure of the joint air test shall not preclude
are leaking, but the total amount of leakage in the sewer line
acceptance by appropriate water infiltration and exfiltration
being tested is equal to, or less than, the allowable leakage rate
testing (see Practice C969), or other means.
established in accordance with Practice C969, the line is
acceptable and no additional testing is required provided 8.3 Joint Water Test:
visible leaks are repaired. Moisture or beads of water appearing 8.3.1 Review procedures in 8.1.
on the surface of the joint will not be considered as visible 8.3.2 Introduce water into void volume until water flows
leakage. evenly from open petcock. Close the petcock and pressurize
8.1.3 Review proper operation, safety, and maintenance with water to 3.5 psi above the pressure exerted by groundwa-
procedures as provided by the manufacturer of the joint test ter above the pipe. Shut off the water supply.
apparatus. 8.3.3 If the pressure holds, or drops less than 1 psi in 5 s, the
8.1.4 Move the joint test apparatus into the sewer line to the joint is acceptable. Practically, the test is a go/no go test.
joint to be tested and position it over the joint. Make sure the 8.3.4 If the joint being tested fails, it shall be retested, or
end element sealing tubes straddle both sides of the joint and repaired if necessary, and retested, in accordance with this
the hoses are attached. For the water test, the bleed-off petcock practice.
must be located at top dead center. 8.3.5 After the joint test is completed, exhaust end element
8.1.5 Inflate end element sealing tubes with air in accor- tubes which will automatically release the water from the void
dance with equipment and manufacturer’s instructions. volume, prior to removal of apparatus.
8.3.6 Use or failure of this joint water test shall not preclude
NOTE 6—The user of this practice is advised that all test pressures are acceptance by appropriate water infiltration or exfiltration
measured as gage pressure, which is defined as any pressure greater than
testing (see Practice C969), or other means.
atmospheric pressure. Since water produces a pressure of 0.43 psi for
every foot of depth, test pressures must be increased to offset the depth of
groundwater over the sewer line. If the groundwater level is 2 ft or more 9. Precision and Bias
above the top of the pipe at the upstream end or if the pressure required 9.1 No justifiable statement is presently capable of being
for the test is greater than 6-psi gage, the joint test method shall not be made either on precision or bias of these procedures since the
used and the infiltration test may be used (see Practice C969).
NOTE 7—An air or water reservoir shall be included in the joint test
test results merely state whether this is in conformance to the
system. By maintaining a constant supply of air or water in a reservoir, criteria for success specified. Due to the sealing effects of
continuous pumping of air or water is not required, and any variances in groundwater and internal flow on concrete sewer lines, the test
test equipment and joint space will be negated. The reservoir shall have a conditions and results are not reproducible.
ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.
This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.
This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org).