A Emergency Eyewash/Shower
Emergency eyewashes and showers shall be permanently installed except in
the following situations where temporary installations are permitted if SAES-B-069
A1
approved by the Chief Fire Prevention Engineer or his representative in Para 4.1.5
consultation with the Environmental Compliance Division
Eye / face wash units shall be positioned with water nozzles 33 inches to 45
SAES-B-069
A5 inches from the floor and 6 inches minimum from the wall or the nearest
Para 6.1
obstruction. (ANSI Z358.1 Para 7.4.1)
Hand-held sprays are permitted in temporary installations in place of safety SAES-B-069
A6
showers Para 4.1.5
In permanent installations, hand-held drench hoses may be used only as
SAES-B-069
A7 auxiliary equipment in support of eyewash and shower units, not in place of
Para 4.1.6
eyewash and shower units.
Emergency Eyewashes and Showers shall be accessible from the hazard SAES-B-069
A9
without the use of stairs, a ladder or a door. Para 6.2
Emergency Eyewashes and Showers shall be at least three (3) meter from
SAES-B-069
A10 electrical equipment and power outlets that are not protected by GFCIs.
Para 6.2
Note: For Battery Rooms see item No. A11 in this SAIC.ê
Emergency Eyewash (no Shower) in battery room shall be at least 1.5 meter
from electrical equipment and power outlets that are not protected by GFCIs.
SAES-B-069
A11
Note: Only an eyewash is required in the battery room, provided that there is Para 6.2
no acid mixing activity to be done inside the battery room. If a shower is
provided
Emergencythen 3 meter separation
Eyewashes is required
and Showers shall be installed in well lighted area SAES-B-069
A12
(100 lux minimum) Para 6.2
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Shower Enclosures, if used, shall provide for a minimum unobstructed area SAES-B-069
B9
of 34 inches in diameter. (ANSI Z358.1 Para 4.4) Section 6.1
Water supply systems shall be certified as suitable for the purpose by Saudi
SAES-B-069
B10 Aramco Environmental Compliance Division/ Environmental Protection
Para 6.7.1
Division.
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-B-069 -- Emergency Eyewash and Showers, 23 January 2012
2-SAES-B-067 -- Safety Identification and Color-Coding, 11 March 2015
3-SAES-S-070 -- Installation of Utility Piping System, 5 December 2012
4-ANSI Z-358.1 -- American National Standard for Emergency Eyewash and Shower Equipment, 2004
###