Masterpact M EN Catalogue PDF
Masterpact M EN Catalogue PDF
and switch-disconnectors
Schneider Electric SA 5, rue Nadar As standards, specifications and designs change from time to time, please ask for confirmation
92506 Rueil-Malmaison Cedex of the information given in this publication.
France
front face
1 opening push-button (O)
2 closing push-button (I)
3 keylock for "connected",
"disconnected" or "test" position
14 4 door interlock
5 stored-energy-mechanism charging
7 handle
6 operations counter
2 7 "open" position keylock
8 racking handle storage
5 9 functional position indicator:
"connected", "test" and "disconnected"
1 10 controls on fixed chassis (accessible
with cubicle door closed)
6 11 padlocking facilities for "connected",
"disconnected" or "test" position
12 12 stored-energy-mechanism status
indicator
E28760
13 charged
c "charged"
c "discharged" discharged
c "OFF" (O);
O OFF
c "ON" (I). I ON
8 9 10 11 3
14 fault-trip indicator/breaker reset button
LV circuit-breaker: blue figures
Enclosure: red figures
E28791
LG
IG
L
LI
off
G
LIG
V DC,
I1 I2 I3
I
O
I
MERLIN GERIN
masterpact
M32 H1
Ui 1000V
50/60Hz
v common height and length from 1000 to
push ON
500 V DC.
20% discharged
tr 120 240
O OFF
Ir
Io
0.8 .88
.9 .92
.95 60 00000
0.63
90 480
.98 30
%Ir .85
1
15
1 .8 at 1,5Ir
0.5
105 xIo
xIn tm.4
Im .3
4 5 .2
6 .3
3
.1
8 .2
2 .1 0
1.5 10
on I t off
2
xIo
I 8 12
Ir : 6 17
t
22
Ir fault 4
Im : 2 off
xIn T
tr th : th .4 .4
Ih 600 .3
500
800 .3
Ih 400
Im fault .2
fault 1000 .2
tm 320 .1
.1
1200
th on I t off
2
I 250
A
R
i Ic2.8 .85
Ic1 .9 .93 .9
.7
+S– .86
.95
.95
.98 .6
.85 1
test 1
.5
.8 xIr
xIr
–T+
F test
connected
test
disconnected
2 Merlin Gerin
10
drawout version
1 arc chute cover
2 auxiliary terminal shield
3 auxiliaries connection block
4 fixed chassis
5 safety shutters
6 arc chute
7 remote control voltage release
8 motor for electrical charging of
stored energy mechanism
9 control unit (AC system)
10 front cover
Merlin Gerin 3
50%
stored energy operating
mechanism
20%
Ir 120
tr 240
Io .9 .92
0.8 .88 .95 60
0.63
90
%Ir .98 30 480
.85
105 0.5
xIn
1
Im
.8
4
xIo
1
5
tm
15
at 1.5Ir
.4 .3
Masterpact circuit breakers are operated via
.2
8 .2 .1
2
.1 0
norm 1.5 10
xIr on I2t off
τ tr
instantaneous opening and closing.
min.
I 14
12
Ir : 8 19
Ir fault
test
–
ground
+
.85
.8
xIr
1
.98 .6
.5
xIr
1
.95
common auxiliaries
from 800 A to 6300 A
isolation renforcée séparation totale déclencheurs voltmétriques
classe II insulation
double entre phase
total chaque phase accessibles
voltage à l'avant
releases Auxiliaries
separation accessible from the c accessible from the front, mounted in a
front separate compartment insulated from power
circuits;
c secured by a single screw;
c adjustment-free;
c can be fitted on site.
moving part of the drawout circuit breaker by v mechanical interlocking for 2 or 3 circuit
adding a fixing bracket on each side. breakers, adaptable to various source-
c Switch version changeover configurations;
The switch (unprotected) version is derived v automatic source-changeover controller,
directly from the standard circuit breaker, but easy to implement on any two suitably
does not implement a control unit (or the equipped circuit breakers (electrically
magnetic trip units used with the DC circuit charged operating mechanism, etc.) (for 3
breakers). Available models are: circuit breakers, consult us);
v standard: type HI and NI; v complete assembly including 2 or
v high performance: type HF, equipped with 3 mechanically (rod assembly) interlocked
a protection system that instantaneously circuit breakers, adaptable to various
opens the circuit breaker in the event of source-changeover configurations;
Fixed circuit breaker
closure under fault conditions. v complete assembly including
2 mechanically (rod assembly) interlocked
c Earthing switch
circuit breakers and an automatic source-
A special short-circuit and earthing switch is changeover controller, adaptable to various
available on request for the M08 to M32H source-changeover configurations. Ready
053060
4 Merlin Gerin
device identification
M 20 H1
breaking capacity;
c N1: standard;
c H1: H2: high performance;
c L1: current limiting;
c DC: direct current.
rating
c rated current / 100.
family
c Masterpact: LV power air
circuit breaker.
Merlin Gerin 5
,
c 10 ratings; maintenance;
2500 A Masterpact circuit breaker c preventive indications: load-shedding
c 4 breaking-capacity levels;
c 6 control units; indication switch, long-time threshold
c a complete range of auxiliaries and overrun alarm, etc.;
025179
6 Merlin Gerin
Masterpact
2/ functions and
characteristics
page
generales characteristics 0
circuit breaker selection 0
switch-disconnectors 0
dimensions an weights 0
control unit selection 0
control unit accessories 0
electrical auxiliaries 0
mechanical accessories 0
source changeover systems 0
conformity with standards Masterpact circuit breakers comply with all IEC 947-2
the major international standards: This standard replaces IEC 157-1,
E29049
tropicalisation
As standard, Masterpact circuit breakers
comply with NF C 63-100 standard level 2
conditions (95 % relative humidity at 45 °C
or 80 % at 55 °C, hot and humid climate
conditions). They also comply with the
following standards:
c IEC 68-2-30 damp heat;
c IEC 68-2-2 dry heat;
c IEC 68-2-11 salt spray;
c IEC 68-2-1 low temperatures during
storage.
Corrosive atmospheres: Special grease or
other surface coatings available (please
consult us).
pollution degree
Masterpact circuit breakers are certified for
operation in pollution degree IV
environments as defined by
IEC standard 947 (industrial environments).
8 Merlin Gerin
E18569
a suitable distance apart.
installation
Masterpact circuit breakers may be installed
on horizontal metal surfaces or on rails.
They are secured by four points accessible
at the bottom of the chassis (drawout
versions) or on either side of the circuit
breaker (fixed versions). A single door
cut-out is required for the entire range and
provides access to Masterpact controls
(see the description on page 2).
.
degree of protection
(as defined by IEC 529)
E28757
Merlin Gerin 9
6 Merlin Gerin
200 to 800 (3) 200 to 1000 (3) 200 to 1250 (3) 200 to 1600 (3)
c c c c c c c c c c c c
c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
Merlin Gerin 7
8 Merlin Gerin
200 to 2000 (3) 300 to 2500 (3) 600 to 3200 2000 to 4000 2000 to 5000 2000 to 6300
c c c c c c c c c c c c c c
c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c (3P only)
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
Merlin Gerin 9
10 Merlin Gerin
200 to 800 (3) 200 to 1000 (3) 200 to 1250 (3) 200 to 1600 (3) 200 to 2000 (3) 300 to 2500 (3) 600 to 3200
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
c c c c c c c
Merlin Gerin 11
Masterpact switch-disconnectors
number of poles
electrical characteristics as per IEC 947-2 and EN 60947-2
rated current (A) In 40 °C
rating of 4th pole (A)
rated insulation voltage (V) Ui
rated impulse withstand voltage (V) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
type of switch-disconnector
short-time withstand current Icw AC 50/60 Hz 0.5 s
(kA rms) 1s
Masterpact M10 NI
3s
making capacity (kA peak) Icm AC 50/60 Hz 440 V
500/690 V
electrodynamic withstand (kA peak)
suitability for isolation
closing time
endurance (C-O cycles) x 1000 mechanical with maintenance
no maintenance
electrical no maintenance 440 V - In
690 V - In
motor control (AC3-947-4) (1) 690 V
protection
STR 08 dummy unit (no protection)
STR 18I (protection against short-circuits when closing)
installation and connections
connection
version drawout
fixed
indication and measurement auxiliaries
auxiliary switches
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
installation and connection accessories
locking by padlock or keylock/mismatch protection
safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)
12 Merlin Gerin
c c c c c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
Merlin Gerin 13
Masterpact switch-disconnectors
number of poles
electrical characteristics as per IEC 947-2 and EN 60947-2
rated current (A) In 40 °C
rating of 4th pole (A)
rated insulation voltage (V) Ui
rated impulse withstand voltage (V) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
Masterpact M50 HI
type of switch-disconnector
short-time withstand current Icw AC 50/60 Hz 0.5 s
(kA rms) 1s
3s
making capacity (kA peak) Icm AC 50/60 Hz 440 V
500/690 V
electrodynamic withstand (kA peak)
suitability for isolation
closing time
endurance (C-O cycles) x 1000 mechanical with maintenance
no maintenance
electrical no maintenance 440 V - In
690 V - In
motor control (AC3-947-4) (1) 690 V
protection
STR 08 dummy unit (no protection)
STR 18 I (protection against short-circuits when closing)
installation and connections
connection
version drawout
fixed
indication and measurement auxiliaries
auxiliary switches
control auxiliaries
auxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
installation and connection accessories
locking by padlock or keylock/mismatch protection
safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)
12 Merlin Gerin
c c c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c (3P only)
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
Merlin Gerin 13
sensor selection
In (A) 200 250 320 400 500 600 630 800 1000 1200
Ir threshold 80 100 125 160 200 240 250 320 400 480
settings (A) to 200 to 250 to 320 to 400 to 500 to 600 to 630 to 800 to 1000 to 1200
In (A) 1250 1600 2000 2500 3000 3200 4000 5000 6000 6300
Ir threshold 500 640 800 1000 1200 1280 1600 2000 2400 2500
settings (A) to 1250 to 1600 to 2000 to 2500 to 3000 to 3200 to 4000 to 5000 to 6000 to 6300
12 Merlin Gerin
435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367
550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367
422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290
537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290
65 65 65 69 82 82 130 82 130 130
80 80 80 85 102 102 150 102 150 150
43 43 43 46 55 55 80 55 80 80
54 54 54 58 69 69 90 69 90 90
M40 M50 M63
H1/H2 H1/H2 H1/H2
HI/HF HI/HF HI/HF
435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367
550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367
65 65 65 69 82 82 130
80 80 80 85 102 102 150
Merlin Gerin 13
E31218
All the protection functions are powered by
the AC system and no auxiliary power STR 18 M
supply is required. The same is true for most STR 28 D
of the complementary functions.
Each control unit of the Masterpact range STR 38 S
corresponds to a certain type of application STR 58 U
(instantaneous, distribution, selective,
universal). STR 68 U
All the STR control units measure the true
rms value of the current and are therefore
not affected by harmonics that may be instantaneous protection
present on the system.
distribution protection
selective protection
universal protection
STR 18 M protection
t Key:
E30703
E31219
push to reset
1 1 reset button: pops out when the circuit
3
breaker has tripped on a fault and must
be pressed (reset) before the circuit
breaker can be closed again.
2 maximum protection rating.
3 instantaneous pick-up.
4 test connector.
5 holes for sealable cover plate screws.
STR 18 M
5
0 I I
other functions
c fault indication.
I 12 14
8 19
4 22 3
2 max
xIn
+ –
test
4
14 Merlin Gerin
E31220
E30704
i
+ –
test
10
11
STR 38 S protection
E31221
t Key:
E33950
Merlin Gerin 15
STR 58 U protection
E31222
Key:
E30705
V t
1 I+T L+I
push to reset reset V I L+I+T I2t ON 1 reset button: pops out when the circuit
L+T T
2 8 breaker has tripped on a fault and must
L off
be pressed (reset) before the circuit
I2t OFF breaker can be closed again.
9 2 selection of fault type for segregated
3 alarm: Ir and/or Im and/or Ih
L: long-time fault (Ir)
I1 I2 I3
I I: short-time fault (Im/l)
90% 10 T: earth fault (Ih)
4 14 3 ammeter digital display.
STR 58 U 11 4 bar graph indicating load level (% Ir).
5 15
50% 5 maximum protection rating.
21 6 overcurrent indicator LED.
20% 13 7-8 long-time current setting as a function of:
8 Io x Ir x In.
Io Ir tr
6 90 0.63 0.8
.9 .92
.88 .95 60
120 240
0 Ir Im I I 9 long-time trip delay
%Ir 9
105 0.5 1
.85 .98 30 480
10 short-time pick-up.
7 Max. xIn
.8
xIo
1 15
at 1.5Ir
other functions 11 short-time delay.
Im tm
4 5 .4 .3
τ tr
12 3 6 .3 .2
c fault indication; 12 adjustment of thermal memory after
11
norm 2
1.5 10
8 .2
.1 0
.1
c indication of LT overrun; tripping.
10 t I 12 14
xIr on I2t off
c ammeter; 13 instantaneous pick-up.
Ir :
Ir fault
8
4
19
22 13 c self-monitoring (internal overheating); 14 earth fault pick-up.
Im :
16 tr
2 off
c fault type indication (F); 15 earth fault delay.
th : xIn
Ih 1200A Max th T
14 16 noted settings.
Ih
fault Im fault 500 600 .4 .4 c segregated alarm switch for selected
tm 400 800 .3 .3
fault type (V); 17-18 load monitoring settings.
th
I 320 1000 .2 .2
15
c zone selective interlocking (Z); 19 test connector.
19 i
250 1200
A
.1 .1
on I2t off
overcurrent Ic1
+ – Ic2 R c load monitoring (R); 20 battery supplying backup power for fault
.9 .93 .8 .85
21 test .86 .95 .7 .9 17 c communication (COM). indication.
– +
ground
.85
8 1
.98 .6
.5 1
.95 21 holes for sealable cover plate screws.
24 xIr xIr 18 22 fault indication reset and/or battery test.
F
test 23 re-indication of last fault.
20
24 LEDs indicating tripping on long-time,
23
22 short-time or earth fault.
STR 68 U protection
I2t ON
E33949
E31223
t Key:
reset 1
V
1 reset button: pops out when the circuit
N 1 2 3 LT setting breaker has tripped on a fault and must
(Ir) I2t OFF be pressed (reset) before the circuit
Hz 2
breaker can be closed again.
Cos ϕ
2 selection of displayed value (voltage,
kW LT time delay power, energy, power factor, frequency).
(tr)
MWh 2 3 display of current or interrupted current
(when flashing).
STR 68 U ST pick-up 4 local fault indication and indication reset.
earth fault (Im) 5 selection and indication of protection
pick-up (Ih) ST time delay parameter to be set.
(tm)
685812 6 selection and indication of load
A
monitoring parameters.
earth fault instantaneous 7 adjustment and saving of parameter
KA time delay (th) pick-up (I)
3 settings.
S 0 Ir Im I I 8 holes for sealable cover plate screws.
test 1 2 3 max 9 test connector.
other functions 10 test.
fault
11 maintenance indicator.
c fault indications and memorisation;
s c maintenance indicator;
4 c ammeter;
tr
c integrated test;
c power measurement;
tm
th c load monitoring (R);
Ih Ir Im I A
c self-monitoring (internal overheating,
5 malfunction of the microprocessor);
2 1 c zone selective interlocking for earth
11 % 6 faults.
maintenance load monitoring
10 – + 7
trip no trip MEM 24 V DC
9
8 test adjustments
16 Merlin Gerin
0 I
earth fault curves for the STR 58
load-shedding or load-reconnection
purposes.
Ic2
Ic1
0 I
load monitoring curves for the STR 58
communication: STR 58 U Transmission of the control unit settings, Other information that can be transmitted
circuit breaker position and current, voltage includes the value of the interrupted current,
transmission: STR 68 U and power measurements. the state of the thermal memory and the
maintenance indications
indication and c ammeter (I): a digital display c indication of type of fault (F);
measurement continuously indicates the current of the c segregated alarm switch for selected
phase with the greatest load (Imax). By fault type (V), wired in parallel with the
pressing a scroll button, it is also possible to opening button (MX), it disables circuit
display successively the readings of I1, I2, breaker closing for the selected type of fault.
I3, Ineutral and Ih.
In addition, three bargraphs provide an
immediate visual indication of the load on
each of the three phases.
Merlin Gerin 17
control unit
type of circuit breaker
basic protection
long time protection LT
current setting (Ir) as a function of Io and Ir Io = In x ...
settings tripping between 1.05 and 1.20 x Ir Ir = Io x ...
time delay (tr)
accuracy: + 0 - 20 % tr at 1.5 Ir (s)
tr at 6 Ir (s)
tr at 7.2 Ir (s)
short-time protection ST
pick-up (Im) adjustable by Im setting Im = Ir x ...
time delay (tm) tm setting with I2t OFF
tm setting with I2t ON
max. overcurrent time before tripping (ms)
max. break time (ms)
instantaneous protection I
pick-up setting
setting range
STR 58 U accuracy
OFF switch on front face
basic functions
fault indication
for tripping on a fault indicator button on front face
fault trip alarm contact (SDE)
for LT setting overrun LED (lights up at 0.9 Ir and flashes at 1.05 Ir)
LT overrun alarm contact (optional)
self-powered
self-monitoring internal overheating
optional functions
ammeter (I) display between 0.2 and 1.20 In
current readings with an accuracy of ± 1.5 % (1) (3)
bargraph indication of current levels with a resolution of 10 %
self-powered
earth fault protection: residual current (T) or source ground return (W) type on request
pick-up adjustable by Ih setting Ih = In x ...
time delay (th) th setting with I2t ON and I2t OFF
max. overcurrent time before tripping (ms)
max. break time (ms)
indication of type of fault (F) (LT - CT/Inst. - Earth) by LEDs on front face
power supply with battery module
with external power supply by AD module
segregated alarm switch for selected fault type (V) (LT - CT/Inst. - Earth)
output via relay contact
power supply by AD module
zone selective interlocking (Z)
by opto-electronic contact on ST and earth (T/W) fault
(1) Plus the uncertainty of the built-in transformers: load monitoring (R)
± 3 %.
adjustment of load limit thresholds by Ic1 and Ic2 settings Ic1 = Ir x ... / Ic2 = Ir x ...
(2) Max = In x ... N1/H1 H2 L1
time delay tr1 at 1.5 Ic1
630 A 22 28 14
800 - 1000 A 22 28 10 time delay tr2 at 1.5 Ic2
1200 - 1600 A 22 24 8 output via opto-electronic contact 0.1 A / 240 V
2000 A 17 20 6
2500 A 12 14 6 time delay for load reconnection
3000 - 3200 A 10 12 – communication (COM)
4000 - 6300 A 8 10 –
2 outputs for data transmission to Dialpact module
(3) Continuous display for the phase with the
greatest load.
transmitted values all control unit settings
(4) 0.2 x In to 1200 A without external power alarms: Ir warning, fault type, self-monitoring
supply or 0.1 x In with external power supply. load monitoring thresholds
(5) Accuracy with respect to the long time LT current values I1, I2, I3, IN
protection.
power supply by AD module
(6) Resettable maximum ammeter.
18 Merlin Gerin
c c c
0.5 to 1 (4 settings) 0.5 to 1 (4 settings) 0.5 to 1 (4 settings)
0.8 to 1 (8 settings) 0.8 to 1 (8 settings) 0.8 to 1 (8 settings)
fixed fixed adjustable
120 120 15 30 60 120 240 480
7.5 7.5 0.94 1.88 3.75 7.50 15 30
5.2 5.2 0.65 1.30 2.60 5.20 10 21
c c
1.5 to 10 ± 15 % 1.5 to 10 ± 15 %
0 0.1 0.2 0.3 0.4 0 0.1 0.2 0.3 0.4
0.1 0.2 0.3 0.1 0.2 0.3
0 80 140 230 350 0 80 140 230 350
80 140 230 350 500 80 140 230 350 500
c c c c
Im = In x ... Im = Ir x ... I = In x ... I = In x ...
2 x In to Max (2) 1.5 to 10 x Ir fixed at high set (Max) (2) 2 x In to Max (2)
± 15 % ± 15 % ± 20 % ± 15 %
on types N1 and H1 on types N1 and H1 on types N1 and H1
c c c c
c c c c
c c c
c c c
c c c
c c c
c c c
I1, I2, I3, IN, Imax (6) I1, I2, I3, IN, Ih, Imax (6) I1, I2, I3, IN, Ih, Imax (6)
I1, I2, I3 I1, I2, I3 I1, I2, I3
c c c
c c
0.1 at 1 (max 1200 A) (4) ± 15 % 0.1 at 1 (max 1200 A) (4) ± 15 %
0.1 0.2 0.3 0.4 0.1 0.2 0.3 0.4
60 140 230 350 60 140 230 350
140 230 350 500 140 230 350 500
c c
c c
c c
c
c
c
c
c
c
c
c
Merlin Gerin 19
presentation
The STR 68 U control unit offers
measurement, supervision and energy
management functions.
Microprocessor technology, liquid crystal
display and function keys ensure high
accuracy and easy adjustment.
The standard STR 68 U control unit provides
the following:
c universal protection;
c ammeter function;
c indication of fault type;
c values of interrupted currents;
c maintenance indicator;
c integrated test.
The following options can be added:
c power measurement module (P);
c "earth fault" protection module;
c control and indication modules (M) with or
without transmission to a supervisor.
Certain M modules can provide load
monitoring or zone selective interlocking for
earth fault protection.
protection The STR 68 control unit provides: c "earth" protection with time
c overload protection, with long time discrimination or zone selective interlocking.
protection LT including: The protection is of the residual current type
v adjustable time delay and thermal (or source ground return type on request).
memory possibility;
c short-circuit protection:
v delayed, with short time function ST, for
which the I2t curve can be disabled by the
user,
v instantaneous, with the INST function that
can be disabled by the user;
20 Merlin Gerin
Merlin Gerin 21
22 Merlin Gerin
(1) Depending on the equipment, the "self-monitoring" alarm signal may or may not trip the circuit breaker, see "service continuity" option on the order form.
Merlin Gerin 23
option m selection Option M can be incorporated in control unit The following table indicates the functions of
STR68U to provide the following functions: the different versions, designated m01 to
c RS485 data transmission at 9600 bauds to m31.
JBUS protocol; For terminal wiring see page xxxx.
c remote signal via opto-electronic output;
c zone selective interlocking for earth fault
protection.
24 Merlin Gerin
t t
E26042
ST pick-up Im 4 In
I2t ON I2t ON
time delay tm 0,2 s
1
INST pick-up I maxi
I2t OFF I2t OFF T earth fault pick-up Ih 0,2 In
2 time delay th 0,1 s
load monitor Ic1 In
Ic2 In
T1
3
T2
4
5
0 Ir Im I I 0 I
overcurrent settings earth fault protection settings
1 : LT setting Ir (long time) T1 : earth fault pick-up Ih
2 : LT time delay tr (long time) T2 : earth fault time delay th
3 : ST pick-up Im ( short time)
4 : ST time delay tm ( short time)
5 : INST pick-up I (instantaneous)
t t
E26037
E26038
Ic2
Ic2 Ic1
Ic1
0 I 0 I
load monitoring and control settings load monitoring and control settings
Ic1 pick-up (load limit) Ic1 pick-up (load limit)
Ic2 pick-up (load limit) Ic2 pick-up (load reconnection)
Merlin Gerin 25
units;
Providing a complement to the AD module,
c 1.5 h with STR 68 control unit.
the battery module provides backup power
for display indications and maintenance Installation: on vertical plate or symmetrical
indicator data in the event of a power failure. rail. (ambient temperature from: 0 °C to
Float connected between the power supply +50 °C).
and the control unit, it ensures a backup
time of approximately:
mini test kit (BU) This test kit is common to the Masterpact,
047035
portable test kit for STR 18 c for other control units, to check the
052172
26 Merlin Gerin
STR 28 / 58
protection : LT, ST, INST yes
option I if I u 20% In yes
if I < 20% In no no (1) yes (2) F1/F2 no
or single phase load
option F no no (1) yes F1/F2 yes
option FV no no (1) yes F1/F2 no
option ALR yes
option R yes
option T/W if Ih u 0.2 x In yes
if Ih < 0.2 x In no (3) no (1) yes F1/F2 no
STR 68
protection : LT, ST, INST, T, W yes
other functions : see drawings page 71
(1) Not recommended: possible with a 24 V DC source, class 2, 5 Watt, ripple factor < 10%.
(2) Display will in this case be "❊❊❊❊". Auxiliary supply allows to save maximeter information.
(3) Ih pick-ups for which protection is not self-powered are printed in red on the trip unit front face.
Merlin Gerin 27
14 Merlin Gerin
operation counter
(CDM)
With gear-motor option only. The operation
counter is read from the front and gives the
total number of breaker operating cycles.
Merlin Gerin 15
Release combinations
Each Masterpact circuit breaker can be
equipped with:
1 MX + 1 MN + 1 XF, or
2 MX + 1 XF
16 Merlin Gerin
reached;
As standard and independent from the
c optional: 24 additional changeover
differentiated fault indications on the control
switches (OFSUP block). These
unit, any fault-trip is indicated by:
microswitches can be parallel connected in
c 1 fault-trip indicator/reset button;
pairs to increase the rated current and
c 1 changeover contact (SDE).
breaking capacity (in drawout version only).
The reset button must always be pressed
after a fault-trip to enable breaker closing.
Additional changeover switches ("OFSUP" block)
"ready to close" contact Optional: automatic reset, allowing remote
(PF) breaker closing without local resetting (the
SDE contact operates up to the reset).
Optional:
016524
connected/disconnected
position carriage switches
In addition to the local "connected/test/
Changeover switches to indicate "connected"
position "CE" disconnected" position indicator, two series
of optional carriage switches are available
for the fixed chassis (of drawout circuit
breaker).
c a block of 4 changeover switches to
indicate "connected" position (CE);
c a block of 2 changeover switches to
indicate "disconnected" position (CD). The
disconnected position is indicated only when
the minimum isolating distance between
main and auxiliary circuits has been
reached.
By series connection of these contacts the
test position can be indicated.
c 1 changeover switch to indicate "test"
position (CT).
contact characteristics
auxiliary contacts type O OF OFSUP SDE PF CE CD CT CH
quantity changeover 4 24 1 1 4 2 1 1
NO 2 NO
NC 2 NC
current rating (A) 10 10 10 10 10 10 10 10 10
breaking capacity 110 V 15
AC 50/60 Hz (A rms.) 240 V 10 10 10 10 10 10 10 10 10
pf u 0.3 380 V 6 10 6 5 5 6 6 6 6
480 V 6 10 6 6 6 6 6
600 V 3 6 3 3 3 3 3
DC (A) 48 V 3 5 3 3 3 3 3 3 3
L/R i 0.01 s 125 V 0.5 3 0.5 0.3 0,3 0.5 0.5 0.5 0.5
250 V 0.25 3 0.25 0.15 0.15 0.25 0.25 0.25 0.25
500 V 0.5
Merlin Gerin 17
Optional: attached to the fixed portion of Optional: attached to the fixed portion of
drawout circuit breakers or on the fixed drawout circuit breakers, this cover prevents
circuit breaker, this cover eliminates the access to the electrical auxiliary connection
safety clearance requirement above the terminals.
breaker (this option is incompatible with front
connection on top).
Fixed portion of drawout circuit breakers with arc chute and
terminal shield
016818
360
plan de fixation
chassis
châssis
fixing
datum
référence 60
a b
18 Merlin Gerin
Optional: fixed to the cublicle door, this Optional: hinge-mounted and equipped with
frame provides an equipment seal function a screw-closure, this cover is designed for
(degree of protection IP 405). the door frame (CDP). It provides a degree
Suitable for fixed and drawout patterns. of protection of IP549.
Suitable for fixed and drawout patterns.
016814
2.5 mm2).
The breaker auxiliary circuits are connected
by connection blocks that operate
automatically to isolate the auxiliaries when
the breaker is in "disconnected" position.
On request, an additional 5-way terminal
block (BS) is available to provide five
common points.
c optional: by one or two plugs,
Auxiliaries for drawout version
disconnectable and accessible from the
front, installed on the mobile part of the
assembly.
breaker mismatch
035940
protection
Optional: for drawout version only, this
systems allows only correctly matched
breakers (rating, type wiring, etc.) to be
inserted in a given fixed frame.
Two matching parts (1 for the fixed chassis
and 1 for the mobile assembly) can be used
to create 20 different user selected
combinations.
Earth connection
The earth connection terminal (drawout
pattern) is on the left hand side of the
chassis. It is marked with the symbol t
Merlin Gerin 19
"disconnected", Remarks
c the keylocks are of the captive key type,
"connected" and "test" i.e. key free when locked;
position locking (1) c Profalux and Ronis keylocks can be used
together;
Mounted on the frame and accessible with c a second Profalux or Ronis lock, identical
the cubicle door locked, this system is to the one mounted on the chassis, can be
available in two versions: supplied separately.
c "disconnected" position locking;
v as standard by 1 padlocking device (1 to 3
padlocks not supplied),
v optional: by a locking device with 1 or 2
Profalux key locks;
c "disconnected", "connected" and "test"
position locking (optional);
v by 1 padlocking device, with 1 to 3
padlocks not supplied (VEC),
v by 1 locking device, with 1 or 2 Profalux
key locks (VSPEC),
20 Merlin Gerin
racking interlock
Optional: this lock prevents insertion of the
breaker racking handle when the cubicle
door is open. It can be defeated by pressing
a b on the unlocking mechanism.
door interlock
a: racking interlock
b: door latch right-hand side VPECD
left-hand side VPECG
racking interlock VPOC
withdrawal/spring charged interlock VEAA
Merlin Gerin 21
053060
interconnected by a set of rods;
c horizontally (two only), i.e. side-by-side
and interconnected by a set of cables.
Masterpact automatic source-changeover system
053058
An electrical interlock must be used when
the source changeover is part of an
053061
automatic system.
Controller
6 - controller BA or UA.
Each Masterpact circuit breaker is 2
equipped with:
c a motor mechanism;
c a shunt release (MX); 1 2
c a «ready to close» contact (PF);
c a block of 4 changeover switches (OF); 3
c an additional terminal block (BS) and a 3
block of 4 «connected» position switches
(CE) for source-changeover systems made
up of drawout breakers.
controller.
IN
GER
MERLIN O
UN =
N
UR 0,5s
R
UN
N I 0,5s
ON /
I /O
ON / OFF R
1
UN =
/O
OFF
fault
fault
stop
test
manu
6
MERLIN
9
GERIN
0 . OFF
multi
P25M
660V 2-1
0 . OFF
AC3-IEC29
GERIN
MERLIN
9
multi
P25M
660V 2-1
AC3-IEC29
Test
Test
B US
IN
GER O
MERLIN UN =
N
UR
R
UN
N I
ON /
I R
ON / /O 1
OFF UN =
/O
OFF
fault
fault
auto
stop
test
manu or
STOP
generat
R
5
36 Merlin Gerin
E33080
1 - 2 circuit breakers QN1 and QN2 predefined conditions must be provided by
connected to the "Normal" source; the customer.
2 - circuit breaker QR connected to the Note that we can provide diagrams for the
"Replacement" source; design of various automatic control systems
3 - mechanical interlocking system by rods; 1 for different sources.
for such applications (consult us)
automatic control of the system can be
provided by adding:
4 - 2 electrical interlocking unit IVE;
5 - auxiliaries control plate ACP; 3
6 - controller BA or UA.
Each Masterpact circuit breaker is 1
equipped with:
c a motor mechanism;
c a shunt release (MX);
c a "ready to close" contact (PF);
c a block of 4 changeover switches (OF); 3
c an additional terminal block (BS) and a
block of 4 "connected" position switches
(CE) for source-changeover systems made 2
up of drawout breakers.
MERLIN
9
GERIN
0 . OFF
multi
P25M
660V 2-1
0 . OFF
AC3-IEC29
GERIN
MERLIN
9
multi
P25M
660V 2-1
IN
AC3-IEC29
GER
MERLIN O
UN =
Test N
UR 0,5s
R
Test
UN
N I 0,5s
ON /
I /O
ON / OFF R
1
UN =
/O
OFF
fault
fault
stop
test
manu
4
6
B US
5 MERLIN
GER
IN
UN =
O
N
UR
R
UN
N I
ON /
I R
ON / /O 1
OFF UN =
/O
OFF
fault
fault
auto
stop
test
manu
gen erator
STOP
R
Merlin Gerin 37
mechanical interlocking by
025184
mechanical interlocking by
025186
38 Merlin Gerin
0 1 0
0 0 1
Q1 Q2 Q3
Merlin Gerin 39
MERLI
N GERIN
0 . OFF MERLI
9
N GERIN
0 . OFF
9 multi
multi
P25M
P25M
660V 292-1
660V
0 . OFF
292-1 AC3-IEC
0 . OFF
AC3-IEC N GERIN
N GERIN MERLI
MERLI 9
9 multi
multi
P25M
P25M
660V 292-1
660V 292-1 AC3-IEC
AC3-IEC
Test
Test
Test
B US
Test
RIN
IN GE UN =
O
MERL
N
UR
R
UN
N I
B US
ON /
I R
ON / /O
OFF UN =
1
/O
OFF
RIN fault
IN GE UN =
O
MERL fault
N
auto
UR
R
UN stop
N test
I
ON / manu tor
R STO
P genera
I /O
ON / OFF 1 R
UN =
/O
OFF
fault N
fault
auto
stop
test
manu tor
STO
P genera
R
customer
connection
mechanism.
Control voltage:
c 48 to 415 V, 50/60 Hz - 440 V 60 Hz.
The IVE control voltage must be the same
as the motor mechanism voltage.
c two P25M circuit breakers supplying and Power is supplied by the "Normal" and
protecting the automatic control circuits for "Replacement" sources. The control
the "Normal" and "Replacement" sources. voltage for the auxiliaries control plate must
These circuit breakers have an infinite be the same as for the IVE unit and the
breaking capacity; motor mechanisms.
c two relay contactors for the BA or UA Control voltages
controller; c 220 to 240 V 50/60 Hz;
c the terminal block for connection to the c 380 to 415 V 50/60 Hz - 440 V 60 Hz.
controller.
Installation:
The auxiliaries control plate ACP must be
wired to the IVE unit by the customer.
40 Merlin Gerin
053058
Controller UA
controller BA UA
compatible circuit breakers All Masterpact circuit breakers
4-position switch
automatic operation c c
forced operation on "Normal" source c c
forced operation on "Replacement" source c c
stop (both "Normal" and "Replacement" sources off) c c
automatic operation
monitoring of the "Normal" source and automatic changeover c c
generator set control c
load shedding and reconnection of non-priority circuits c
changeover to the "Replacement" source if one of the phases of the
"Normal" phase is absent c
test
by opening the P25M circuit breaker supplying the controller c
by pressing the test button on the front of the controller c
indications
circuit breaker status indication on the front of the controller: on, off,
fault trip, automatic mode indicating contact c c
automatic mode indicating contract c c
other functions
selection of type of "Normal" source (single-phase or three-phase) c
voluntary transfer to "Replacement" source (e.g. energy management commands) c c
during peak-tariff periods (energy management commands), forced operation
on "Normal" if "Replacement" source not operational c
supplementary control contact (not carried out by the controller). Transfer to
"Replacement" source only if contact closed. (ex: UR frequency control) c c
setting of maximum startup time for the replacement source c
power supply
control voltages (1) 220 to 240 V 50/60 Hz
380 to 415 V 50/60 Hz - 440 V 60 Hz
options
communication option c
(1) The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, then
the “Normal” and “Replacement” sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used.
Merlin Gerin 41
BA automatism v stop (both "Normal" and "Replacement" carried out by the controller). Transfer to
220/240 V 50/60 Hz
2 4 t1 sources off); "Replacement" source only if contact closed
1 8 s
N UN R UR N UN = 0 0.5 15 c adjustment of time delays in front: (ex: UR frequency control),
0.1 30
v t1 from 0.1 to 30 seconds; v outputs:
ON/I ON/I
0.5s
v t2 from 0.1 to 240 seconds; – indication of operation in automatic mode.
0.5s
OFF/O OFF/O c circuit breaker status indication on the Connection to the terminal block: see p.XXX.
t2 15 30 front of the controller: on, off, fault trip; c controller BA can be tested by opening
fault fault
s 8
4
60
120
UN = I R the P25M circuit breaker on the N circuit,
reset
0.1 240
thus simulating a failure of UN.
stop auto
See detailed transfer steps on page XXX.
manu
N R
42 Merlin Gerin
E21108
E27107
E30187
off QN et QR open operat. on N R 4-position switch N et UN présente
source N I O
UN fail (duration > t1) or voluntary
"auto" switching order received
UR present and supplementary QR opens
control contact N➡R closed
reset duration a 1 s
QN opens
t > 0,5 s
end of reset
t > 0,5 s QN closes
QR closes QN fermé
"stop"
operat. on N R
QR closed
source N I O
operat. on N R
source R action on 4-position switch
O I
t > 0,5 s
4-position switch in "R" position
UR present and supplementary control
contact N➡R closed
QN closes
QN opens
QN closed
t > 0,5 s
QR closes
QR closed
operat. on N R
source R O I
Merlin Gerin 43
automatic functions:
c switching from one source to another
depending on the presence of voltage UN
on the "Normal" source;
c control of an engine generating set;
c shedding and reconnection of non-priority
circuits;
c switching to the "Replacement" source in
the event of a failure on one of the phases of
the "Normal" source.
MERLIN GERIN
compact / masterpact
UA automatism
220/240 V 50/60 Hz
2 4 t1 Operation c integrated terminal block for connection of
N UN R UR N UN = 0
1 8 s
15
c a four-position switch can be used to the following signals:
0.5
0.1 30
select: v inputs:
ON/I ON/I
t4
s 2
5 10
15 2
5 10 t3
15 s
v automatic operation; – order for voluntary transfer to source R
OFF/O OFF/O
1
0.5 30
20 1
0.5 30
20
v forced operation on source N; (e.g. energy management commands),
t2 15 30
v forced operation on source R; – supplementary control contact: (not
s 8
4
60
120
UN = I R v stop (circuit breakers open and manual carried out by the controller). Transfer to
fault fault
reset
0.1 240 operation); "Replacement" source only if contact closed
stop auto
240 300 t5 c adjustment of time delays in front: (ex: UR frequency control),
manu 160 360 s
test 120 480 v t1 from 0.1 to 30 seconds; v outputs:
60 600
v t2 from 0.1 to 240 seconds; – control of engine generator set,
N R v t3 from 0.5 to 30 seconds; – load shedding of non-priority circuits,
generator
STOP
v t4 from 0.5 to 30 seconds; – indication of operation in automatic mode;
v t5 from 60 to 600 seconds; c 3 switches provide the following functions:
Front face of controller UA
c circuit breaker status indication on the v selection of the type of "Normal" source,
front of the controller: on, off, fault trip; i.e. single-phase or three-phase;
Time delay settings: c test button on the front of the controller v enable or disable voluntary energy
QN: Masterpact circuit breaker with motor to check the transfer from the “Normal” management transfer if the "Replacement"
mechanism on “Normal” source, source to the "Replacement" source and the source is not operational;
QR: Masterpact circuit breaker with motor
mechanism on “Replacement” source,
return to the "Normal" source; v selection of the maximum tolerated
t1: time delay before QN opens when the voltage starting time for the engine generator set
UN of the “Normal” source disappears, ("Replacement" source): 120 s or 180 s.
t2: time delay before QR opens when the voltage
UN of the “Normal” source is restored,
t3: time delay before QR closes once QN has Batibus option for controller UA In automatic mode, this communications
opened and the load has been shed,
A communication function can be used to option also offers the possibility of remote
t4: time delay before QN closes once QR has
opened and the load has been reconnected, check the following from a remote location: forced operation on the “Replacement”
t5: time delay for confirmation of presence of UN c status of the circuit breakers (open, source.
before stopping the generator set. closed or fault trip);
c voltage presence on the “Normal” and
“Replacement” sources;
c presence of an order forcing operation on
the “Replacement” source (e.g. for energy
management purposes);
c values of settings and configurations,
c status of the non-priority circuits (whether
subject to load shedding or not).
44 Merlin Gerin
E30185
E30187
E27107
reset duration a 1 s
genset startup t > t4
"stop"
operat. on N R
t > t3 genset off
source N I O
QR closed
QN closed
t > t3
genset remains on
QR closes
UN present for t > t5 and no
voluntary switching order received
QR closed
genset off
operat. on N R
genset on
source R O I
UR absent
action on 4-position switch
Merlin Gerin 45
Masterpact
3/ installation
and connection
page
installation
general 0
safety clearance 0
fixed circuit breakers M08 to M32 0
drawout circuit breakers M08 to M32 0
fixed circuit breaker M40 0
drawout circuit breaker M40 0
fixed circuit breaker M50 0
drawout circuit breaker M50 0
drawout circuit breaker M63 0
manual source changeover systems
manual and automatic source
changeover systems 0
connection
fixed and drawout circuit breakers
M08N/M10N/M12N 0
fixed and drawout circuit breakers
M08H,L/M10H,L/M12H,L/M16N,H,L 0
fixed and drawout circuit breakers
M20N,H/M25N,H 0
fixed and drawout circuit breakers
M20L/M25L/M32H 0
fixed and drawout circuit breaker M40 0
fixed and drawout circuit breaker
M08 to M16 0
fixed and drawout circuit breaker
M50 to M63 0
wiring diagrams:
c STR 18 M / 28 D / 38 S / 58 U 0
c STR 28 D / 38 S / 58 U avec options 0
c STR 68 U avec options m01 à m31 0
c automatic source changeover 0
c manual source changeover 0
41
E31255
E31257
E31256
26
45 305
42 Merlin Gerin
Certain distances must be maintained These distances are the results of tests
between a circuit breaker and other carried out in accordance with standard
elements such as panels, bars and other IEC 947-2 and are in part determined by the
circuit breakers. Taken together, these ultimate breaking capacities.
distances form the safety clearance for the
circuit breaker. The diagrams and the table
below indicate the required distances when
installing Masterpact circuit breakers.
E31233
E31230
A
D D A
A
B B
B B
E31231
A A
213 B B
Merlin Gerin 43
016807
electrodynamic forces c the first bar spacers must be located at c this maximum distance must be
less than a certain distance from the circuit respected to withstand the electrodynamic
breaker connection point; forces that are applied between the bars
during a short-circuit.
44 Merlin Gerin
Merlin Gerin 45
dimensions
553
E30749
3 or 4 poles necessary space for removing
E30748
438
the arc chutes
(with or without arc chute cover)
E30742
493
378
90 130
45
311
(*)
(*)
(*) Datum
mounting
on a base plate on rails mounting detail
E30765
E30766
Ø14
E30775
Ø11 A 2 Ø11 x 6
150
3 poles 4 poles
150
30 mini
A 150 150
30 mini
60 maxi 60 maxi B 400 515
cut-outs
cut-outs de porte holes for escutcheon
E30763
E30764
152,5
270
14,5
(*) 148,5
71,5 69
27
80 mini 37,5
325 80
mini 11 Ø5 180 180 17,5
(*)
(*) Datum
48 Merlin Gerin
dimensions
3 or 4 poles
(*) Datum
mounting
on a base plate
BTP207E-3.230-M08…32
101
cut-outs
100
mini
ACB's basis
Merlin Gerin
175
325
55
49
47
100
mini
270
19
E30746
E30768
E30760
a
128
60
101
11 Ø5
800
on rails
45
mini
"disconnected" position
101
175
(*)
180
175
71,5
85
180
439
152,5
148,5
18,5
17,5
69
E30747
E30775
21/12/01, 10:17
A
B
70
55
mounting detail
Ø11 A
325
435 (3p)
425
550 (4p)
3 poles
175
325
Ø14
B
55
55
2 Ø11 x 6
4 poles
175
425
(*)
49
Masterpact: installation
fixed circuit breaker M40
dimensions
3 or 4 poles 819
E30753
necessary space for removing
E30752
553
the arc chutes
E31226
130 493
90
45
311
(*)
(*)
11
30 mini 150 68 11 515
60 maxi
290 11 537 (3p)
780
802 (4p) 11
(*) Datum
mounting
on a base plate on rails mounting detail
E30771
E30772
E30775
Ø14
Ø11 A 2 Ø11 x 6
cut-outs
front panel cut-out holes for escutcheon
E30763
E30764
152,5
270
14,5
(*) 148,5
71,5 69
27
80 mini 37,5
325 80
mini 11 Ø5 180 180 17,5
(*)
(*) Datum
50 Merlin Gerin
BTP207E-3.240-M40
Masterpact: installation
drawout circuit breaker M40
dimensions
3 or 4 poles
(*) Datum
(1) 4-pole version only.
mounting
on a base plate
101
ACB's basis
175
cut-outs
front panel cut-out
ACB's side
Merlin Gerin
55
325
(1)
51
47
270
19
45 (1)
100
mini
E30750
E30774
E30760
a 800
mini
128
60
on rails
101
11 Ø5
45
"disconnected" position
101
175
(*)
180
175
367
71,5
(1)
180
85
(1)
152,5
148,5
18,5
17,5
439
69
484
E30751
E30777
21/12/01, 10:17
60
70
350
mounting detail
40
175
40
425
550 (3p)
815 (4p)
350
150
30
350
350
2 Ø11 x 6 (3p)
6 Ø11 x 22 (4p)
55
55
51
(*)
Masterpact: installation
fixed circuit breaker M40
dimensions
3 or 4 poles 819
E30753
necessary space for removing
E30752
553
the arc chutes
E31226
130 493
90
45
311
(*)
(*)
11
30 mini 150 68 11 515
60 maxi
290 11 537 (3p)
780
802 (4p) 11
(*) Datum
mounting
on a base plate on rails mounting detail
E30771
E30772
E30775
Ø14
Ø11 A 2 Ø11 x 6
cut-outs
front panel cut-out holes for escutcheon
E30763
E30764
152,5
270
14,5
(*) 148,5
71,5 69
27
80 mini 37,5
325 80
mini 11 Ø5 180 180 17,5
(*)
(*) Datum
50 Merlin Gerin
BTP207E-3.240-M40
Masterpact: installation
drawout circuit breaker M40
dimensions
3 or 4 poles
(*) Datum
(1) 4-pole version only.
mounting
on a base plate
101
ACB's basis
175
cut-outs
front panel cut-out
ACB's side
Merlin Gerin
55
325
(1)
51
47
270
19
45 (1)
100
mini
E30750
E30774
E30760
a 800
mini
128
60
on rails
101
11 Ø5
45
"disconnected" position
101
175
(*)
180
175
367
71,5
(1)
180
85
(1)
152,5
148,5
18,5
17,5
439
69
484
E30751
E30777
21/12/01, 10:17
60
70
350
mounting detail
40
175
40
425
550 (3p)
815 (4p)
350
150
30
350
350
2 Ø11 x 6 (3p)
6 Ø11 x 22 (4p)
55
55
51
(*)
Masterpact: installation
fixed circuit breaker M50
dimensions
necessary space for removing
E30756
3 poles
E30757
819
the arc chutes
(with or without arc chute cover) 759
E31227
130
90
45
311
(*)
(*)
(*) Datum
mounting
on a base plate on rails mounting detail
E30775
E30771
E30772
Ø14
Ø11 A 2 Ø11 x 6
cut-outs
front panel cut-out holes for escutcheon
E30763
E30764
152,5
270
14,5
(*) 148,5
71,5 69
27
80 mini 37,5
325 80
mini 11 Ø5 180 180 17,5
(*)
(*) Datum
52 Merlin Gerin
BTP207E-3.250-M50
Masterpact: installation
drawout circuit breaker M50
dimensions
3 or 4 poles
(*) Datum
mounting
on a base plate
101
cut-outs
ACB's basis
175
Merlin Gerin
55
325
53
47
100
mini
270
19
45 (1)
E30754
a
128
E30770
E30760
60
800
45
mini
on rails
101
11 Ø5
"disconnected" position
101
175
(*)
180
175
367
85
71,5
180
45
484
152,5
148,5
18,5
17,5
E30755
69
40
21/12/01, 10:18
E31228
60
475
350
mounting detail
40
175
815 (3p)
475
1045 (4p)
40
350
30
150
350
350
6 Ø11 x 22 (3p)
6 Ø11 x 33 (4p)
55
55
53
(*)
E30745
a
E30769
E30762
Masterpact: installation
drawout circuit breaker M63
dimensions
3 poles or 4 poles
(*) Datum
mounting
on a plate
54
101
cut-outs
175
base of c.b.
side of c.b.
325
BTP207E-3.260-M63+inv sour
55
47
270
45 (1)
100
mini
19
54
E30758
E30770
E30760 a 800
mini
128
60
on rails
101
11 Ø5
45
"disconnected" position
101
175
(*)
180
175
367
71,5
85
180
45
152,5
148,5
18,5
17,5
484
69
E30759
E30778
40 475
mounting detail
40
21/12/01, 10:18
175
1045
40
475
30
475
150
475
6 Ø11 x 33
55
(*)
Merlin Gerin
Masterpact: installation
source-changeover system
E30780
50
50
5 14 30
40 52 30 125
125
900
900 max.
max.
900
max.
153 175
(*)
105
163 (*)
30 base of c.b. 44
45
180 (*)
base of c.b. base of c.b. 30 mini
65 for ratings : for ratings : 82
60 maxi
166 M08 to M40 (3p) M40 (4p) to M63 (*)
E30782
50
5 14 60
40
52 60 180
180
900
max.
900
max.
50
50
5 14 60
40 52 60
180 180
900
900 max.
max.
153 175
900
max.
(*)
163 (*) 105
45 30 base of c.b. 62
base of c.b. base of c.b. 180 (*)
65 for ratings : for ratings : 100 30 mini
166 M08 to M40 (3p) M40 (4p) to M63 60 maxi
(*) Datum
Merlin Gerin 55
2m maxi
200 mini
r= 120 mini r= 120 mini
E33353
E33352
E30784
11 1 2 1 3 1 4 1 5 1 6
10
9
8
7
H48
H47 6
5
4
3
2
1
H43 H49
controller
N
L33 P58
L34 P62
M32(4p)
L35
M40(3p)
M32(3p)
P60
E33354
2100
1940
H51
1640 H50
H52
940 L36 P61
L37 P59
P63
E33364
56 56 56 56
600 750
C34
C34
Dimensions (mm)
type C34 H43 H47 H48 H49 H50 H51 H52 L33 L34 L35 L36 L37 P58 P59 P60 P61 P62 P63
140 120 151 137 160 200 255 22 6 48 84 138 150 61,5 170 95 90 150(min) 187
56 Merlin Gerin
E30786
115 115 115 85
E30785
45
front connectors screen 12,5 25 10
N
10 (1)
2 Ø12 (*)
50
335
E30787
12,5 45
107 23
175 (**) 15 17 17,5 25 10
(*)
221 12,5
2 Ø12
10 (*)
233
278 12,5 vertical terminals
E30788
115 115 115 85
10
25 25 15
front connectors screen
12,5
N
(1)
3 Ø12
10 (*)
45
rear connection
306 112 25
112 horizontal terminals
115 115 115 47,5
E30791
92 74,5 45
10
25 10
30
175 25 12,5 15
12,5 12,5
273
10 2 Ø12
300,5
306 (*)
(*) vertical terminals
2 Ø12
(*) Datum.
(1) On request, neutral on the right. (*)
Merlin Gerin 57
100
30
112 200
53
25
25
(*) 25 15 25 52
246 55 12,5
306 15
100
30
112
25 157
25
25
92
137
79,5
12,5
25 43
345 15
363 15
(*)
100
30
112
25 157
25
25
92
137
79,5
12,5
25 43
345 15
363 15
(*)
(*) Datum.
64 Merlin Gerin
E30827
35
E30826
Ø12
(*) 145
(*)
35 72,5
E30830
N Ø12 N
(1) (*) (1)
70 145
(*)
Ø12 10 10
260
25 25 25 85 25 25 25
Ø12
(*) 185 (*)
Ø12 10 10
100 260 260 260
25 25 25 25 25 25 85 25 25 25
N Ø12 N
(1) (*) (1)
70 185
(*) Datum.
(*)
(1) On request, neutral on the right.
Merlin Gerin 65
100
30
112
252
53
25
25
(*) 25 15 25
243 55 12,5
306 15
(*) Datum.
100
30
112
25 157
25
25
92
137
79,5(4p)
12,5
175 34,5(3p)
345 15
363 15
(*)
(*) Datum.
62 Merlin Gerin
E30812
172,5 172,5 85
180 165 85 35
E30811
Ø12 (*)
80
(*)
(*) Datum.
(1) On request, neutral on the right.
35
100 155
10 10
12,5 25 25 25 25 25 25 40
Ø12
Ø12 (*)
70
(*)
35
155 155 100 155 10 10
25 25 25 25 25 25 40
12,5 Ø12
N Ø12 (*) N
(1) (1) 70
(*)
(*) Datum.
(1) On request, neutral on the right.
Merlin Gerin 63
E30901
80
E30802
15 25 25 15
front connectors screen
N
(1)
100 3 Ø12 (*)
30
335
112
rear connection
horizontal terminals
25 162
25 115 140 115 72,5
E30803
53
25
85,5
87 25 25 11,5
175 (**) 18 15 12,5 7
(*) 18 15
221 30 15 3 Ø12 (*)
236
268 vertical terminals
115 140 140 60
E30804
25
4 Ø12 (*)
(*) Datum.
(**) Hole for securing front connection support bracket.
(1) On request, neutral on the right.
60 Merlin Gerin
E30806
100
E30805
25 25 25 12,5
front connectors sceen
15
N
(1)
4 Ø12 (*)
100
30
363 rear connection
112 horizontal terminals
25 157
115 125 125 37,5
E30807
25
25 100
92
34,5 25 25 25 12,5
37 12,5
329 15
4 Ø12 (*)
30
344 15
344 15
(*) vertical terminals
115 152,5 152,5 10
E30808
25
4 Ø12 (*)
(*) Datum.
(1) On request, neutral on the right.
Merlin Gerin 61
E30901
80
E30793
N
10 (1)
3 Ø12 (*)
80
335
112
132
rear connection
25 horizontal terminals
25
53
115 115 115 85
E30832
15 80
107 8
175 (**) 15 17 17,5 25 25 15
(*)
221 12,5
10 3 Ø12 (*)
233
278 12,5
vertical terminals
115 115 115 85
E30794
10
3 Ø12
(*) Datum. (*)
(**) Hole for securing front connection support bracket.
(1) On request, neutral on the right.
80
E30795
25 25 15
front connectors screen
12,5
N
(1)
3 Ø12
10 (*)
80
rear connection
306 112
horizontal terminals
25 112
25 115 115 115 47,5
E30796
92 80
57
15 25 25 15
30
175 25 12,5 15
12,5 12,5
273
10 3 Ø12
300,5 (*)
306
(*) vertical terminals
10
3 Ø12
(*) Datum.
(1) On request, neutral on the right. (*)
58 Merlin Gerin
E30901
115 115 115 85
80
E30798
12,5 25 25 15
front connectors screen
N
(1)
80 3 Ø12 (*)
20
335
E30832
80
15 3
175 (**) 107 15 18 17,5 25 25 15
12,5
(*)
221 12,5
3 Ø12 (*)
16
233
283 vertical terminals
E30799
115 115 115 85
20
80
E30800
25 25 15
front connectors screen
12,5
N
(1)
3 Ø12
(*)
20 80
rear connection
306 112
horizontal terminals
25 112
25 115 115 115 47,5
E30796
92 80
62
15 25 25 15
30
175 25 12,5 15
12,5 12,5
273
20 3 Ø12
300,5 (*)
306
(*) vertical terminals
E30801
3 Ø12
(*) Datum.
(1) On request, neutral on the right. (*)
Merlin Gerin 59
AT ready
BPO to
close
BPF
connected disconnected fault closed open
springs
charged
314 312 324 322 334 332 344 342 352 354 362 364 372 374 82 84 212 222 234 244 12 14 22 24 32 34 42 44 D4 C12 C2 A4 252 254 262 B4
CE
or
M
MN
or MX XF
MNR
MX
OF
F F O O
SDE CH
processing
unit PF
CD CT
311 321 331 341 351 361 371 81 211 221 231 241 11 21 31 41 D1 C11 C1 A1 251 B1
Fu
CN2 - CN –
AT: emergency off c diagram shown with circuits deenergised, Wiring of the MNR (modified diagram).
BPO: "open" pushbutton breaker open and in "connected" position, Instantaneous tripping with MNR when
BPF: "close" pushbutton springs charged and relays in released contact 254-262 opens.
CE: "connected" position contact position;
(10 A/240 V AC) c accessories such as pushbuttons, lamps
E30718
M: spring charging motor and fuses are not supplied with the circuit D4 254 262
(180 VA/240 V AC) breaker.
XF: closing release MNR
(20 VA/240 V AC)
MX: shunt release (20 VA/240 V AC) D1
MN: undervoltage release
(20 VA/240 V AC)
Note: the wiring of the external contact
MNR: time delayed undervoltage release
replaces the spring charged indication and
(20 VA/240 AC)
the contact PF.
OF: auxiliary changeover contacts
(10 A/240 V AC)
O: 2 auxiliary NO contacts
(10 A/240 V AC)
F: 2 auxiliary NC contacts
(10 A/240 V AC)
SDE: fault trip indication contact
(10 A/240 V AC)
CH: charging motor limit switch contact
PF: "ready to close" contact
(10 A/240 V AC) (closing possible if
breaker is open, not locked and
operating mechanism charged)
CD: "disconnected" position contact
(10 A/240 V AC)
CT: test posiiton contact
(10 A/240 V AC)
66 Merlin Gerin
P1 S1
AT ready
BPO to
P2 S2 close
(4) (4)
BPF
connected disconnected LR fault closed open
(2) alarm springs
Ic1 Ic2
charged
(5)
362
364
372
374
344
342
314
312
324
322
352
334
332
354
Z11 Z12 LR2 T2 T1 V2 R1 R2 e+ e– 82 84 212 222 234 244 12 14 22 24 32 34 42 44 D4 C12 C2 A4 252 254 262 B4
CE
or
M
MN
or MX XF
MNR
T
MX
OF
F F O O
F V
CH
SDE
ammeter
ALR
PF
proce-
ssing C
R
unit
CD CT
Fu
CN2 - CN –
AT: emergency off CD: "disconnected" position contact Wiring of the MNR (modified diagram).
BPO: "open" pushbutton (10 A/240 V AC) Instantaneous tripping with MNR when
BPF: "close" pushbutton CT: test position contact (10 A/240 V AC) contact 254-262 opens.
LR: long time trip (LT) indicating lamp C: communication.
CR: short time trip (ST) indicating lamp
E30718
T: earth fault trip indicating lamp c Ic1: load shedding command according to D4 254 262
CE: "connected" position contact Ic1 setting
(10 A/240 V AC) Ic2: load shedding command according to MNR
M: spring charging motor Ic2 setting;
(180 VA/240 V AC) c diagram shown with circuits deenergised, D1
R: load monitoring and control breaker open and in "connected" position,
XF: closing release (20 VA/240 V AC) springs charged and relays in released
Note: the wiring of the external contact
T: earth fault protection (EZ and SZ: position;
replaces the spring charged indication and
input and output for zone selective c accessories such as pushbuttons, lamps
the contact PF.
interlocking) and fuses are not supplied with the circuit
MX: shunt release (20 VA/240 V AC) breaker.
MN: undervoltage release
(20 VA/240 V AC) V contact wiring:
MNR: time delayed undervoltage release for breaker locking, depending on the
(20 VA/240 V AC) selected fault.
OF: auxiliary changeover contacts
(10 A/240 V AC)
E30719
CN1/CN +
O: 2 auxiliary NC contacts BPO
(10 A/240 V AC)
F: 2 auxiliary NC contacts V C2
(10 A/240 V AC)
V MX
SDE: fault trip indication contact
(1) Power supply terminals for I or T or F options
(10 A/240 V AC) (AD module with BAT battery module for backup V C1
CH: charging motor limit switch contact power). CN2/CN –
F: fault trip local indicator (2) Zone selective interlocking with line side
FV: segregated fault trip indication contact breaker.
(5 A/240 V AC) (3) Zone selective interlocking with load side Selective locking needs:
breaker (remove jumper). c external power supply (F1, F2);
PF: "ready to close" contact (4) DC power supply. R contacts reset request
(10 A/240 V AC) (closing possible if c an additional terminal (BS).
wiring of an external contact.
breaker is open, not locked and (5) With Z and/or C options, terminal 84 is not
operating mechanism charged) available.
Merlin Gerin 67
P1 S1
AT ready
BPO
to
P2 S2 close
BPF
connected disconnected (5) closed open
springs
charged
334
332
354
374
344
342
362
372
314
312
324
322
352
364
T2 T1(3) T21 T22 82 212 222 234 244 12 14 22 24 32 34 42 44 D4 C12 C2 A4 252 254 262 B4
CE
or
M
MN
or MX XF
MNR
MX
OF
F F O O
SDE CH
EZ(4)
processing M01
unit to
M16 PF
CD CT
311 321 331 341 351 361 371 F1 F2 F12 F11 512 522 532 542 552 562 81 211 221 231 241 11 21 31 41 D1 C11 C1 A1 251 B1
+
power supply (2)
–
power supply MR6
E51
E52
E53
E54
E55
E56
E2
(1)
412
414
421
422
424
431
432
434
441
442
444
451
452
454
461
462
464
411
Fu
CN2 - CN –
AT: emergency off CD: "disconnected" position contact Wiring of the MNR (modified diagram).
BPO: "open" pushbutton (10 A/240 V AC) Instantaneous tripping with MNR when
BPF: "close" pushbutton CT: test position contact contact 254-262 opens.
CE: "connected" position contact (10 A/240 V AC).
(10 A/240 V AC)
E30718
M: spring charging motor c diagram shown with circuits deenergised, D4 254 262
(180 VA/240 V AC) breaker open and in "connected" position,
XF: closing release (20 VA/240 V AC) springs charged and relays in released MNR
MX: shunt release (20 VA/240 V AC) position;
MN: undervoltage release c accessories such as pushbuttons, lamps D1
(20 VA/240 V AC) and fuses are not supplied with the circuit
MNR: time delayed undervoltage release breaker.
Note: the wiring of the external contact
(20 VA/240 V AC) replaces the spring charged indication and
OF: auxiliary changeover contacts the contact PF.
(10 A/240 V AC)
O: 2 auxiliary NO contacts
(10 A/240 V AC)
F: 2 auxiliary NC contacts
(10 A/240 V AC)
SDE: fault trip indication contact
(10 A/240 V AC)
CH: charging motor limit switch contact
M01: indication option equipped with
to 6 opto-decoupled
M16 outputs to contacts (0.2 A/24 V DC),
for programming as per table on
page C54 (EZ: input for earth fault (1) Power supply for control unit and modules.
protection zone selective interlocking) (2) Power supply for option M and module MR6 by
module AD.
PF: "ready to close" contact
(3) Terminals T1 and T2 must be imperatively
(10 A/240 V AC) (closing possible if short-circuited when the external CT is not
breaker is open, not locked and connected.
operating mechanism charged) (4) The zone selective interlocking output is
MR6: relay module with 6 changeover provided by one output of module m01 to m32..
(5) Zone selective interlocking with load side
contacts (3 A, 24 V DC)
breaker: remove the jumper.
68 Merlin Gerin
+ –
power supply 1 2 3 4
(2)
(3)
0V ET 44 interface (1) 4 RD–
5 TD– Sub D9
(3) S1 (4) S2 (4) connector
8 RD+
24V 9 TD+ (5)
(1) Communication interface for RS485 - 9600 baud
network.
(2) Power supply for m option and ET44 interface
(AD module).
1 3 2 1 3 2
(3) Provided connectors.
(4) Remote controlled relay output (10 A, 220 V AC).
(5) JBUS, RS485, 9600 baud network. (3)
Merlin Gerin 69
E30725
T2 T1 T21 T22
module P
1 3 2 1 3 2
H1 H2 H3 H4
4 RD–
r– 5 TD– Sub D 9
S1 S2
r+ 4 8 RD+ connector
(6) H1 H2
e– 3 ET 44 9 TD+
e+ 2
1 BAT
H4 H3
processing M17 (4)
unit to
M31 e+e–r+ r–
Sub D 9
connector
(1)
Sub D 15 (1) Provided cable: length 1.5 m (connected to
connector chassis).
(2) Available supply sources:
module P 24-48 V DC, 125 V DC, 100-240 V AC.
F1 F2 F12 F11 512 522 (3) Backup power for trip unit information with BAT
N L1 L2 L3
(7) (7) (7) module (remove jumpers).
CN1 CN2 H1 H2 H3 H4 (4) Provided cable.
(5) (5) Voltage connection (load side shown, line side
(3)
+ – also available). 3 or 4 poles available.
power supply (6) JBUS, RS 485-9600 baud network.
(2) (7) MR6 module wiring.
power supply for control All the protection functions of the control unit To ensure proper isolation of the circuits,
are powered by current sensors built into the two separate power supplies are required.
units and complementary circuit breaker. They can be implemented as follows:
functions However power must be supplied: c for terminals F1 and F2:
c to terminals F1 and F2 for the indication v by direct supply of AC current (specify the
and display functions: required voltage when ordering: 100, 220,
v if the device has a low 3-phase load (less 380 V 50/60 Hz),
than 20% of the rated current) or a single- v or by an AD module, with or without BAT
phase load, (1 AD for each STR68),
v if display and indications are required v or by direct supply of 24 V DC current (5
when the circuit breaker is off; W, Class 2 insulation, < 10% ripple);
c to terminals F11 and F12 for the M c for terminals F11 and F12:
modules. v by another AD module (1 AD for each
STR68, in addition to the modules supplying
terminals F1 and F2),
v or by direct supply of 24 V DC current,
isolated from the circuit supplying terminals
F1 and F2 (5 W, Class 2 insulation, < 10%
ripple).
70 Merlin Gerin
E30728
control M01 to M16 module control M17 to M31 module
unit option MR6 unit option ET 44
- + - +
module module
AD AD
- +
module module module module
BAT BAT BAT BAT
- + - + - + - +
module module module module
AD AD AD AD
E30732
module module
BAT P
module module
BAT P
Cn1+ Cn2-
Cn1+ Cn2-
Merlin Gerin 71
"SOURCE 1" BREAKER AUXILIARIES "COUPLING" BREAKER AUXILIARIES "SOURCE 2" BREAKER AUXILIARIES
S1 S2 CN1
CN2
to A
t1
COUPLING
t2
t3
t4
R1
R2
R3
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
82
84
32
34
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
82
84
32
34
CE CE
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
82
84
32
34
XF CE CE
M
MX XF CE CE
Q1 OF OF OF M
MX XF
SDE
QC OF OF OF M
CH MX
SDE OF OF OF
PF Q2
CH
SDE
PF
CH
PF
251
B1
21
81
31
11
A1
C1
311
321
251
B1
21
81
31
11
A1
C1
311
321
251
B1
21
81
31
11
A1
C1
311
321
Q1: Masterpact on source 1 M: motor mechanism c diagram shown with circuits de-energised,
QC: Masterpact used for coupling XF: closing release breakers open and in «connected» position,
Q2: Masterpact on source 2 MX: shunt release springs charged and relays in released
D: P25M circuit breaker (2 x 10 A) CE: «connected» position switch position.
t1: coupling signal: «source 1 failure» OF: auxiliary changeover switch
(minimum time delay 250 ms) SDE: overcurrent fault-trip indication switch Note: All indicating signals by O, F, OF,
t2: coupling signal: «source 2 failure» CH: «springs charged» switch SDE, PF and CH auxiliary switches should
(minimum time delay 250 ms) PF: «ready to close» contact (closing be protected by fuses that discriminate with
t3: uncoupling signal: «source 1 possible if device is open, unlocked respect to the protection devices on the
restored» (minimum time delay 250 and operating mechanism charged). automatic control circuits to avoid disturbing
ms) the operation of the source-changeover
t4: uncoupling signal: «source 2 system.
restored» (minimum time delay 250
ms) The relays are not supplied with the circuit
R1,R2,R3: external relays for interlocking of breakers.
SDE auxiliary switches.
88 Merlin Gerin
"SOURCE 1" BREAKER AUXILIARIES "COUPLING" BREAKER AUXILIARIES "SOURCE 2" BREAKER AUXILIARIES
S1 S2 CN1
CN2
to A
t1
COUPLING
t2
t3
t4
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
32
34
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
32
34
CE
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
32
34
XF CE
M
MX CE
XF
Q1 OF OF OF M
MX XF
QC OF OF OF M
CH MX
PF Q2 OF OF OF
CH
PF
CH
PF
251
B1
21
31
11
A1
C1
311
321
251
B1
21
31
11
A1
C1
311
321
251
B1
21
31
11
A1
C1
311
321
Q1: Masterpact on source 1 M: motor mechanism c diagram shown with circuits de-energised,
QC: Masterpact used for coupling XF: closing release breakers open and in «connected» position,
Q2: Masterpact on source 2 MX: shunt release springs charged and relays in released
D: P25M circuit breaker (2 x 10 A) CE: «connected» position switch position.
t1: coupling signal: «source 1 failure» OF: auxiliary changeover switch
(minimum time delay 250 ms) SDE: overcurrent fault-trip indication switch Note: All indicating signals by O, F, OF,
t2: coupling signal: «source 2 failure» CH: «springs charged» switch SDE, PF and CH auxiliary switches should
(minimum time delay 250 ms) PF: «ready to close» contact (closing be protected by fuses that discriminate with
t3: uncoupling signal: «source 1 possible if device is open, unlocked respect to the protection devices on the
restored» (minimum time delay 250 and operating mechanism charged). automatic control circuits to avoid disturbing
ms) the operation of the source-changeover
t4: uncoupling signal: «source 2 system.
restored» (minimum time delay 250
ms)
Merlin Gerin 89
"SOURCE 1" BREAKER AUXILIARIES "SOURCE 2" BREAKER AUXILIARIES "SOURCE 3" BREAKER AUXILIARIES
S1 S2 S3 CN1
CN2
to A
t1
t2
t3
R1
R2
R3
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
82
84
32
34
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
82
84
32
34
CE CE
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
82
84
32
34
XF CE CE
M
MX XF CE CE
Q1 OF OF OF M
MX XF
SDE
Q2 OF OF OF M
CH MX
SDE OF
PF Q3 OF OF
CH
SDE
PF
CH
PF
251
21
81
31
C1
11
A1
B1
311
321
251
B1
21
81
31
C1
11
A1
311
321
251
B1
21
81
31
C1
11
A1
321
311
Q1: Masterpact on source 1 M: motor mechanism c diagram shown with circuits de-energised,
Q2: Masterpact on source 2 XF: closing release breakers open and in «connected» position,
Q3: Masterpact on source 3 MX: shunt release springs charged and relays in released
D: P25M circuit breaker (2 x 10 A) CE: «connected» position switch position.
t1: signal for transfer to source 1 OF: auxiliary changeover switch
(minimum time delay 250 ms) SDE: overcurrent fault-trip indication Note: All indicating signals by O, F, OF,
t2: signal for transfer to source 2 switch SDE, PF and CH auxiliary switches should
(minimum time delay 250 ms) CH: «springs charged» switch be protected by fuses that discriminate with
t3: signal for transfer to source 3 PF: «ready to close» contact (closing respect to the protection devices on the
(minimum time delay 250 ms) possible if device is open, unlocked automatic control circuits to avoid disturbing
R1,R2,R3: external relays for interlocking of and operating mechanism charged). the operation of the source-changeover
SDE auxiliary switches. system.
86 Merlin Gerin
"SOURCE 1" BREAKER AUXILIARIES "SOURCE 2" BREAKER AUXILIARIES "SOURCE 3" BREAKER AUXILIARIES
S1 S2 S3 CN1
CN2
to A
t1
t2
t3
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
32
34
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
32
34
CE
314
312
324
322
252
254
262
C2
A4
B4
12
14
22
24
32
34
XF CE
M
MX XF CE
Q1 OF OF OF M
MX XF
Q2 OF OF OF M
CH MX
PF Q3 OF OF OF
CH
PF
CH
PF
251
21
31
C1
11
A1
B1
311
321
251
21
31
C1
11
A1
B1
311
321
251
21
31
C1
11
A1
B1
311
321
Q1: Masterpact on source 1 M: motor mechanism c diagram shown with circuits de-energised,
Q2: Masterpact on source 2 XF: closing release breakers open and in «connected» position,
Q3: Masterpact on source 3 MX: shunt release springs charged and relays in released
D: P25M circuit breaker (2 x 10 A) CE: «connected» position switch position.
t1: signal for transfer to source 1 OF: auxiliary changeover switch
(minimum time delay 250 ms) SDE: overcurrent fault-trip indication switch Note: All indicating signals by O, F, OF,
t2: signal for transfer to source 2 CH: «springs charged» switch SDE, PF and CH auxiliary switches should
(minimum time delay 250 ms) PF: «ready to close» contact (closing be protected by fuses that discriminate with
t3: signal for transfer to source 3 possible if device is open, unlocked respect to the protection devices on the
(minimum time delay 250 ms) and operating mechanism charged). automatic control circuits to avoid disturbing
the operation of the source-changeover
system.
Merlin Gerin 87
"NORMAL 1" BREAKER AUXILIARIES "NORMAL 2" BREAKER AUXILIARIES "REPLACEMENT" BREAKER AUXILIARIES
N1 N2 R auxiliary
genset startup signal source
G D
undervoltage relay
U=0 to B
C
genset fault
contact OFF N
R AUTO
Fu CMa
Fu
Fu
N1-2
N1 N2
RTn2
RTn3
Fu RX3
RTn1
RX2
RX1
R1
R2
334
332
324
322
314
312
252
254
262
D4
A4
B4
82
84
12
14
22
24
334
332
324
322
314
312
252
254
262
D4
A4
B4
82
84
12
14
22
24
CE CE CE
324
322
314
312
252
254
262
D4
A4
B4
82
84
12
14
22
24
XF CE CE CE
M
MN
QN1 OF OF XF CE CE
M
SDE MN
QN2 OF OF XF
M
SDE MN
CH
PF QR OF OF
CH SDE
PF
CH
PF
251
81
21
11
A1
B1
D1
311
331
321
251
B1
81
21
11
A1
D1
311
331
321
251
B1
81
21
11
A1
D1
311
321
QN1: Masterpact on «Normal1» source M: motor mechanism c diagram shown with circuits de-energised,
QN2: Masterpact on «Normal2» source XF: closing release breakers open and in «connected» position,
QR: Masterpact on «Replacement» MN: undervoltage release springs charged and relays in released
source CE: «connected» position switch position.
D: P25M circuit breaker (2 x 10 A) OF: auxiliary changeover switch
C: operation selection switch SDE: overcurrent fault-trip indication Note: All indicating signals by O, F, OF,
Cma: source selection switch switch SDE, PF and CH auxiliary switches should
FU: fuses CH: «springs charged» switch be protected by fuses that discriminate with
Rtn1: voltage relay with 0.1 to 30 s time PF: «ready to close» contact (closing respect to the protection devices on the
delay possible if device is open, unlocked automatic control circuits to avoid disturbing
Rtn2: voltage relay with 10 to 180 s time and operating mechanism charged). the operation of the source-changeover
delay system.
Rtn3: voltage relay
RX1: relay with 0.25 s time delay The two relays and selection switches are
RX2: relay with 0.25 s time delay not supplied with the circuit breakers.
RX3: relay
R1/R2: external relays for interlocking of
SDE auxiliary switches (equipped
with 2 contacts O).
84 Merlin Gerin
"NORMAL 1" BREAKER AUXILIARIES "NORMAL 2" BREAKER AUXILIARIES "REPLACEMENT" BREAKER AUXILIARIES
N1 N2 R auxiliary
genset startup signal source
G D
undervoltage relay
U=0 to B
C
genset fault
contact OFF N
R AUTO
Fu CMa
Fu
Fu
N1-2
N1 N2
RTn2
RTn3
Fu RX3
RTn1
RX2
RX1
R1
R2
324
322
314
312
252
254
262
D4
A4
B4
82
84
12
14
22
24
324
322
314
312
252
254
262
D4
A4
B4
82
84
12
14
22
24
CE CE
324
322
314
312
252
254
262
D4
A4
B4
82
84
12
14
22
24
XF CE CE
M
MN
QN1 OF OF XF CE CE
M
SDE MN
QN2 OF OF XF
M
SDE MN
CH
PF QR OF OF
CH SDE
PF
CH
PF
251
81
21
11
A1
B1
D1
321
311
251
B1
81
21
11
A1
D1
321
311
251
B1
81
21
11
A1
D1
311
321
QN1: Masterpact on «Normal1» source M: motor mechanism c diagram shown with circuits de-energised,
QN2: Masterpact on «Normal2» source XF: closing release breakers open and in «connected» position,
QR: Masterpact on «Replacement» MN: undervoltage release springs charged and relays in released
source CE: «connected» position switch position.
D: P25M circuit breaker (2 x 10 A) OF: auxiliary changeover switch
C: operation selection switch SDE: overcurrent fault-trip indication Note: All indicating signals by O, F, OF,
Cma: source selection switch switch SDE, PF and CH auxiliary switches should
FU: fuses CH: «springs charged» switch be protected by fuses that discriminate with
Rtn1: voltage relay with 0.1 to 30 s time PF: «ready to close» contact (closing respect to the protection devices on the
delay possible if device is open, unlocked automatic control circuits to avoid disturbing
Rtn2: voltage relay with 10 to 180 s time and operating mechanism charged). the operation of the source-changeover
delay system.
Rtn3: voltage relay
RX1: relay with 0.25 s time delay The relays and selection switches are not
RX2: relay with 0.25 s time delay supplied with the circuit breakers.
RX3: relay
Merlin Gerin 85
"NORMAL 1" BREAKER AUXILIARIES "NORMAL 2" BREAKER AUXILIARIES "REPLACEMENT" BREAKER AUXILIARIES
N1 N2 R
CN1
CN2
to A
t1
t2
R1 (1)
R2 (1)
314
312
252
254
262
C2
A4
B4
12
14
82
84
22
24
314
312
252
254
262
C2
A4
B4
CE
12
14
82
84
22
24
314
312
252
254
262
C2
A4
B4
12
14
82
84
22
24
XF CE
M
CE
MX XF
QN1 OF OF
M
XF
MX
SDE
QN2 OF OF M
MX
CH
PF SDE QR OF OF
CH SDE
PF
CH
PF
251
B1
81
21
11
A1
C1
311
251
B1
81
21
11
A1
C1
311
251
B1
81
21
11
A1
C1
311
QN1: Masterpact on «Normal1» source M: motor mechanism c diagram shown with circuits de-energised,
QN2: Masterpact on «Normal2» source XF: closing release breakers open and in «connected» position,
QR: Masterpact on «Replacement» MX: shunt release springs charged and relays in released
source CE: «connected» position switch position.
D: P25M circuit breaker (2 x 10 A) OF: auxiliary changeover switch
t1: signal for transfer to «Normal1» and SDE: overcurrent fault-trip indication switch Note: All indicating signals by O, F, OF,
«Normal2» sources (minimum time CH: «springs charged» switch SDE, PF and CH auxiliary switches should
delay 250 ms) PF: «ready to close» contact (closing be protected by fuses that discriminate with
t1: signal for transfer to «Replacement» possible if device is open, unlocked respect to the protection devices on the
source (minimum time delay 250 ms) and operating mechanism charged). automatic control circuits to avoid disturbing
R1/R2:external relays for interlocking of the operation of the source-changeover
SDE auxiliary switches (equipped system.
with 2 contacts O).
(1) The two relays are not supplied with the
circuit breakers.
82 Merlin Gerin
"NORMAL 1" BREAKER AUXILIARIES "NORMAL 2" BREAKER AUXILIARIES "REPLACEMENT" BREAKER AUXILIARIES
N1 N2 R
CN1
CN2
to A
t1
t2
314
312
252
254
262
C2
A4
B4
12
14
22
24
314
312
252
254
262
C2
A4
B4
12
14
22
24
CE
314
312
252
254
262
C2
A4
B4
12
14
22
24
XF CE
M
MX XF CE
QN1 OF OF
M
MX XF
QN2 OF OF M
CH MX
PF QR OF OF
CH
PF
CH
PF
251
B1
21
11
A1
C1
311
251
B1
21
11
A1
C1
311
251
B1
21
11
A1
C1
311
QN1: Masterpact on «Normal1» source M: motor mechanism c diagram shown with circuits de-energised,
QN2: Masterpact on «Normal2» source XF: closing release breakers open and in «connected» position,
QR: Masterpact on «Replacement» source MX: shunt release springs charged and relays in released
D: P25M circuit breaker (2 x 10 A) CE: «connected» position switch position.
t1: signal for transfer to «Normal1» and OF: auxiliary changeover switch
«Normal2» sources (minimum time SDE: overcurrent fault-trip indication switch Note: All indicating signals by O, F, OF,
delay 250 ms) CH: «springs charged» switch SDE, PF and CH auxiliary switches should
t2: signal for transfer to «Replacement» PF: «ready to close» contact (closing be protected by fuses that discriminate with
source (minimum time delay 250 ms) possible if device is open, unlocked respect to the protection devices on the
and operating mechanism charged). automatic control circuits to avoid disturbing
the operation of the source-changeover
system.
Merlin Gerin 83
N R
genset startup signal
G auxiliary
source
unvoltage relay D
U=0
to B
genset fault
contact C
OFF N
AUTO
STANDBY
Fu
RTn2
RX3
Fu RTn1
RX1
RX2
324
322
314
312
252
254
262
D1
A4
B4
82
84
12
14
22
24
324
322
314
312
252
254
262
D1
A4
B4
82
84
12
14
22
24
CE CE
XF CE CE
M
MN XF
QN OF OF M
MN
SDE QR OF OF
CH
SDE
PF
CH
PF
251
81
21
B1
11
A1
D4
321
311
251
81
21
B1
11
A1
D4
321
311
QN: Masterpact on «Normal» source M: motor mechanism c diagram shown with circuits de-energised,
QR: Masterpact on «Replacement» XF: closing release breakers open and in «connected» position,
source MN: undervoltage release springs charged and relays in released
D: P25M circuit breaker (2 x 10 A) CE: «connected» position switch position.
C: 4-position switch OF: auxiliary changeover switch
FU: fuses SDE: overcurrent fault-trip indication switch Note: All indicating signals by O, F and OF
Rtn1: voltage relay with 0.1 to 30 s time CH: «springs charged» switch auxiliary switches should be protected by
delay PF: «ready to close» contact (closing fuses that discriminate with respect to the
Rtn2: voltage relay with 10 to 180 s time possible if device is open, unlocked protection devices on the automatic control
delay and operating mechanism charged). circuits to avoid disturbing the operation of
RX1: relay with 0.25 s time delay the source-changeover system.
RX2: relay with 0.25 s time delay
RX3: relay
80 Merlin Gerin
N R
auxiliary
source
to B
OFF N
STANDBY AUTO
Fu
RTn2
Fu RTn1
Fu
RTn3
RX1
Fu
RX2
324
322
314
312
252
254
262
D1
A4
B4
82
84
12
14
22
24
324
322
314
312
252
254
262
D1
A4
B4
82
84
12
14
22
24
CE CE
XF CE CE
M
MN XF
QN OF OF M
MN
SDE QR OF OF
CH
SDE
PF
CH
PF
251
81
21
B1
11
A1
D4
321
311
251
81
21
B1
11
A1
D4
321
311
QN: Masterpact on «Normal» source CE: «connected» position switch c diagram shown with circuits de-
QR: Masterpact on «Replacement» M: motor mechanism energised, breakers open and in
source XF: closing release «connected» position, springs charged and
D: P25M circuit breaker (2 x 10 A) MN: undervoltage release relays in released position.
C: 4-position switch OF: auxiliary changeover switch
FU: fuses SDE: overcurrent fault-trip indication switch Note: All indicating signals by O, F and OF
Rtn1: voltage relay with 0.1 to 30 s time delay CH: «springs charged» switch auxiliary switches should be protected by
Rtn2: voltage relay with 10 to 180 s time PF: «ready to close» contact (closing fuses that discriminate with respect to the
delay possible if device is open, unlocked protection devices on the automatic control
Rtn3: voltage relay and operating mechanism charged). circuits to avoid disturbing the operation of
RX1: relay with 0.25 s time delay the source-changeover system.
RX2: relay with 0.25 s time delay
Merlin Gerin 81
BA operation
E27121
I
UN or KT
O
I
UR
O
I
KR
O
I
QN
O
I
QR
O
T1 500 ms T2 500 ms
250 ms 250 ms
0,1…30 s 0,1…240 s
UA operation
UN or KT I
E30189
O
I
UR
O
I
KR
O
I
KG
O
SH I
O
QN I
O
QR I
O
T1 T3 T2 T4 T5
0,1...30s 120-180s 0,5...30s 10...240s 0,5...30s 60...600s
78 Merlin Gerin
Version represented: With lockout after a The indication circuits, represented on the possible states
fault. diagram by broken lines, are optional. "Normal" 0 1 0
If lockout after a fault is not required, contact Accessories such as voltage relays,
"Replacement" 0 0 1
PF of the «Normal» breaker must be indicating lights and fuses are not supplied
connected directly in series with auxiliary with the circuit breaker.
switch OF of the «Replacement» breaker
and vice versa, without passing through the
switch SDE.
E33088
N R CN1 control
voltage
CN2
F1 (1) F2 (1)
D
to B
to A
C
to C
RTs
fault closed fault closed
RTn
open open
F3 (1) F4 (1)
314
312
252
254
262
C2
A4
B4
82
84
22
24
(2)
12
14
314
312
252
254
262
C2
A4
B4
82
84
22
24
(2)
12
14
CE
XF CE
M
MX XF
QN OF OF M
MX
SDE QR OF OF
CH
SDE
PF
CH
PF
81
21
B1
11
A1
251
C1
311
81
21
B1
11
A1
251
C1
311
B
A
QN: Masterpact on «Normal» source M: motor mechanism c diagram shown with circuits de-energised,
QR: Masterpact on «Replacement» source XF: closing release breakers open and in «connected» position,
D: P25M circuit breaker (2 x 10 A) MX: shunt release springs charged and relays in released
F1, F2, F3, F4: protective fuses 2 A CE: «connected» position switch position.
Rts: «Replacement» source voltage relay OF: auxiliary changeover switch
(minimum time delay 250 ms) SDE:overcurrent fault-trip indication switch (1) The fuses clear faults occurring on the
Rtn: «Normal» source voltage relay CH: «springs charged» switch indication circuits without disturbing the
(minimum time delay 250 ms) PF: «ready to close» contact (closing operation of the source-changeover system.
possible if device is open, unlocked (2) Terminal 84 does not exist on control
and operating mechanism charged). units STR58 with options Z and/or C or
STR68UM/UTM; in this case there is
discrimination between the indications.
Merlin Gerin 79
N R
(1)
N
WH
GN
RD
BK
VT
(3) IVE
(1)
R
314
312
WH
GN
RD
252
254
262
BK
VT
C2
A4
B4
12
14
82
84
(3)
314
312
252
254
262
C2
A4
B4
CE
12
14
82
XF CE 84
M
MX
QN OF XF M
SDE MX
QR OF
SDE
CH
PF
CH
PF
251
81
11
A1
B1
C1
311
251
81
11
A1
B1
C1
(3) (2)
311
GY
BN
YE
(3) (2)
GY
BN
YE
QN: Masterpact on «Normal» source OF: auxiliary changeover switch c diagram shown with circuits de-energised,
QR: Masterpact on «Replacement» source SDE: overcurrent fault-trip indication switch breakers open and in «connected» position,
IVE: electrical interlocking and terminal CH: «springs charged» switch springs charged and relays in released
block unit PF: «ready to close» contact (closing position.
M: motor mechanism possible if device is open, unlocked and This diagram doesn't operate with
XF: closing release operating mechanism charged). "automatic reset" option.
MX: shunt release
CE: connected position switch (1) provided ready to connect wiring.
(2) Don't wire for option "without lockout after fault".
(3) Don't wire in fixed position.
72 Merlin Gerin
N R controller UA
load shedding and genset
management
E33076
1 3 5 1 3 5 UA load genset
shedding startup
Q1 Q2
2 4 6 2 4 6
ACP
23 22 27 26 28 30 29 31
load genset
24 N O L 9 10 R E 25 shedding startup
load reconnection genset shutdown
BatiBUS option
E33077
24 N O L R E 25
BatiBUS BatiBUS
loop loop
23 22
controller status
indication + – 0V 24V
BA/UA
17 18 20
24V 0V – +
21
supplementary 11 12 13 14 15 16 10 9 8 7 6 5
11 12 13 14 15 16
N
IVE
R
1 2 3 4 5 6 7 8 9 10
Q1 : circuit breaker supplying and protecting c diagram shown with circuits de-energised, Tests on "Normal" and "Replacement"
the automatic control circuits for the all devices open and relays in the released voltages
"Normal" source position. BA:
Q2 : circuit breaker supplying and protecting c single-phase check for UN and UR:
the automatic control circuits for the v tested across terminals 1 and 5 of circuit
"Replacement" source breakers Q1 and Q2.
IVE : electrical interlocking and terminal
block unit UA:
ACP : auxiliaries control plate c three-phase check for UN:
BA/UA : controller v tested across terminals 1, 3 and 5 of
circuit breaker Q1,
v selection switch A of controller set to 1;
c single-phase check for UN :
v tested across terminals 1 and 5 of circuit
breaker Q1,
v selection switch A of controller set to 0.
Merlin Gerin 73
"SOURCE 1" BREAKER AUXILIARIES "COUPLING" BREAKER AUXILIARIES "SOURCE 2" BREAKER AUXILIARIES
S1 S2
CMa
Fu
OFF
auto
permanent
RTn1
Fu RTn2
Fu
CMb
RTn3
RTn4
N1+N2
Fu
N1+C
N2+C
COUPLER RX1
Fu
RX2
Fu
RX3
324
322
314
312
252
254
262
C2
A4
B4
82
84
12
14
22
24
324
322
314
312
252
254
262
C2
A4
B4
82
84
12
14
22
24
CE CE
324
322
314
312
252
254
262
C2
A4
B4
82
84
12
14
22
24
XF CE CE
M
MX XF CE CE
OF OF M
MX XF
SDE
OF OF M
CH MX
SDE OF OF
PF
CH
SDE
PF
CH
PF
B1
251
81
21
11
A1
C1
321
311
251
B1
81
21
11
A1
C1
321
311
B1
251
81
21
11
A1
C1
311
321
Q1: Masterpact on source 1 M: motor mechanism c diagram shown with circuits de-energised,
QC: Masterpact used for coupling XF: closing release breakers open and in «connected» position,
Q2: Masterpact on source 2 MX: shunt release springs charged and relays in released
Cma: 3-position switch CE: «connected» position switch position.
FU: fuses OF: auxiliary changeover switch
Rtn1: voltage relay with 10 to 180 s time SDE: overcurrent fault-trip indication Note: All indicating signals by O, F, OF,
delay switch SDE, PF and CH auxiliary switches should
Rtn2: voltage relay with 0.1 to 30 s time CH: «springs charged» switch be protected by fuses that discriminate with
delay PF: «ready to close» contact (closing respect to the protection devices on the
Rtn3: voltage relay with 10 to 180 s time possible if device is open, unlocked automatic control circuits to avoid disturbing
delay and operating mechanism charged). the operation of the source-changeover
Rtn4: voltage relay with 0.1 to 30 s time system.
delay
Cmb: coupling selection switch The relays are not supplied with the circuit
RX1: relay with 0.25 s time delay breakers.
RX2: relay with 0.25 s time delay
RX3: relay with 0.25 s time delay
90 Merlin Gerin
Masterpact
4/ complementary technical
information
page
tripping curves 0
effect of ambient temperature 0
77
10000
5000
Ir = 0,4…1 x In
2000
Ic1 = 0,2…1 x In
1000
Ic2 = 0,2…1 x In
500
tr = 15…480s
200
tr1 = tr / 2
100
tr2 = tr / 4
50
20
10
t(s)
2
.5
.2
.1
.05
.02
.01
.005
.002
.001
.05 .06 .08 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
x In
86 Merlin Gerin
10000
5000
Ir = 0,4…1 x In
2000
Ic1 = 0,2…1 x In
1000
Ic2 = 0,2…1 x In
500
tr = 15…480s
200
tr1 = tr / 2
100
50
20
tr2 = 60s
10
t(s)
2
.5
.2
.1
.05
.02
.01
.005
.002
.001
.05.06 .08 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
x In
Merlin Gerin 87
STR 68 U
E30714
10000
5000
Ir = 0,4 …1 x In
2000
tr = 15…480s
1000
500
200
100
50
20
10
t(s)
2 I2t ON
Im = 0,4 …15 x In
1
.5
0,4 0,4
0,3 0,3
.2
0,2 0,2
.1 I2t OFF 0,1 0,1
.05 I (*)
.02
.01
.005
.002
.001
.5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300
x In kA
(*)I
In (A) 800 1000 1250 1600 2000 2500 3200 4000 5000 6000
5000
2000
Ih = 0,2…1 x In…
1000 Max. 1200A
500
200
100
50
20
10
t(s)
2
.5
0,4
0,3
.2
0,2
.1 0,1
.05
.02
.01
.005
.002
.001
.05 .06 .08 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
x In
Merlin Gerin 85
5000
2000
Ih = 0,1…1 x In
1000 Max 1200A
500
200
100
50
20
10
5 I2t ON
t(s)
2
.5
0,4
0,3
.2
0,2
.05
.02
.01
.005
.002
.001
.05 .06 .08 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
x In
In: CT rating
Ih: earth fault protection pick-up (delay: th)
82 Merlin Gerin
10000
5000
Ir = 0,4…1 x In
2000
Ic1 = 0,8…1 x Ir
1000
Ic2 = 0,5…1 x Ir
500
tr1 = tr / 2
200
tr2 = tr / 4
100
50
20
10
t(s)
2
.5
.2
.1
.05
.02
.01
.005
.002
.001
.05 .06 .08 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
x In
Merlin Gerin 83
STR 38 S
E30711
10000
5000
Ir = 0,4 …1 x In
2000
1000
500
200
100
50
20
10
Inst (*)
t(s) I2t ON
2
Im = 1,5 …10 x Ir
1
.5
0,4
0,3 0,3
.2
0,2 0,2
.05
.02
0
.01
.005
.002
.001
.5 .6 .8 1 2 3 4 5 6 8 10 20 3 4 5 6 8 10 20 30
x Ir x In
(*)Inst
In (A) 630 800/1000 1200/1600 2000 2500 3000/3200 4000/5000/6300
I = In x ... (N-H) 28 28 24 20 14 12 10
I = In x ... (L) 14 10 8 6 6 - -
80 Merlin Gerin
10000
5000
Ir = 0,4 …1 x In
2000
tr = 15…480s
1000
500
200
100
50
20
10
5 Im = 1,5 …10 x Ir
t(s)
2 I2t ON
.5
0,4
0,3 0,3
.2
0,2 0,2
2 0,1 0,1
.1 I t OFF
.05
0
I = 2 x In…Max (*)
.02
.01
.005
.002
.001
.5 .6 .8 1 2 3 4 5 6 8 10 20 3 4 5 6 8 10 20 30
x Ir x In
(*)Max
In (A) 630 800/1000 1200/1600 2000 2500 3000/3200 4000/5000/6300
Merlin Gerin 81
STR 18 M
E30708
10000
5000
2000
1000
500
200
100
50
20
I = 2 x In… Max (*)
10
t(s)
2
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300
x In
(*)Max
In (A) 630 800/1000 1200/1600 2000 2500 3000/3200 4000/5000/6300
Max = In x ... 28 28 24 20 14 12 10
78 Merlin Gerin
10000
5000
Ir = 0,4 …1 x In
2000
1000
500
200
100
50
20
10
t(s)
2
Im = 1,5 …10 x Ir Inst (*)
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .6 .8 1 2 3 4 5 6 8 10 20 3 4 5 6 8 10 20 30
x Ir x In
Merlin Gerin 79
88 Merlin Gerin