Professional Documents
Culture Documents
Liebert Pex TM Eng Asia PDF
Liebert Pex TM Eng Asia PDF
Notice
The purchased products, services, and features are stipulated by the contract made
between Vertiv Co., and the customer. All or part of the products, services, and features
described in this document may not be within the purchasing scope or the usage scope.
Unless otherwise specified in the contract, all statements, information, and
recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied. The information in this document is
subject to change without notice. Every effort has been made in the preparation of this
document to ensure the accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or
implied.
E-mail: support@Vertivco.com
• Asia Pacific
Homepage: www.vertivco.com.
E-mail: overseas.support@Vertivco.com
For Technical Support, users may contact the nearest Vertiv Co. local sales office or service
centre.
Purpose of the Document
This document applies to the Liebert PEX+ series of precision air conditioners cooling solutions
which maintain an optimal environmental control mainly for technological ecosystems at
minimal operating costs. This document gives an overview of the technical specification. The
figures used in this document are for reference only. Please read this manual carefully.
Situation Description
Version History
The Liebert PEX+ series is the next generation series of air conditioners that provide precise
environmental control. The Liebert PEX+ models are the latest in the long line of modern
enterprise-grade products from the Liebert family. Incorporating the high standards
associated with the Liebert name, the PEX+ series utilizes the latest technology, system
components, and streamlined manufacturing process.
Liebert PEX+ air conditioners are products that are specifically created and designed for the
data centers, computer rooms, and similar ecosystems which call for a high degree of accuracy
and precision. It addresses the needs and challenges associated with such applications and
setups. It caters to sensitive applications which need a suitable environment for optimal
performance. Therefore, care should be taken while testing these sensitive products or
maintaining a favorable environment for mission critical equipment, as even a slight deviation
may lead to inaccurate results. Precision Air Conditioning must not only keep room conditions
within a specific range but also must have the precision to react quickly to a drastic change in
heat load and prevent wide temperature fluctuations.
The PEX+ air cooled AC unit is packed with features such as high reliability, high sensible heat
ratio, and large airflow. It is an excellent system that adheres to the standards in Precision Air
Cooling in terms of energy-efficiency, space requirements, and reliability.
2.1 Components
2.1.1 Compressor
The Liebert PEX+ series models comprise of a Copeland scroll compressor which has a host of
promising features such as low operating noise, less vibration, and high reliability. The
Rotalock (screw thread) connection mode makes the maintenance easier. Its compactness,
smooth compression with scroll operation and high energy efficiency ratio make it an ideal
compressor to bank on for the PEX+ series.
2.1.2 Evaporator
The evaporator consists of a V-coil (for up flow)/A-coil (for down flow) incorporating draw-
through air design for uniform air distribution. The coil is constructed of enhanced surface
aluminum fins mechanically bonded to enhanced surface copper tubes. The coil frame is
fabricated from hot dipped galvanized sheet metal and the stainless-steel condensate drip
tray. Hydrophilic coating on cooling coil enhances longevity.
The sophisticated design of the distributor ensures that the refrigerant is distributed evenly in
each loop, thereby improving the effectiveness of the heat exchanger.
The infrared humidifier in the Liebert PEX+ series provides quicker and more responsive
operation which is quite important for mission-critical applications. These humidifiers reduce
the dependency of water quality and simultaneously achieve full capacity in quick time using
almost any water quality.
• Ability to regulate the airflow and reduce the fan input power leading to high energy-
efficiency.
• Easy-to-connect facility with minimum wiring leading to a high performance with a
great variety of possible air flow rates.
To counter that effect, Filter-driers are used to filter out particles and remove and hold
moisture to prevent it from circulating through the system. The Liebert PEX+ AC consists of
nylon filter material with big mesh. The filter features compact structure and easy
maintenance. It can be washed repeatedly.
2.1.10 Condenser
The Liebert range of air conditioners offers many advantages, some of which are listed below:
• Antirust aluminum cabinets
• Low sound levels
• High reliability over a wide range of ambient conditions
P 1 0 5 0 D A 1 3 S H S 1 2 S 1 D 0 0 0 C E 0 L 0
Figure 3- 1 Nomenclature
Item Requirement
General requirements Indoor, clean, no dust
Ambient humidity 5%RH to 85%RH (non-condensing)
Ambient temperature -20℃ to +54°C
Storage time Total transportation and storage time should not exceed six
months. Otherwise, the performance needs to be re-
calibrated
Item Requirement
Indoor 18°C ~ 32°C
Ambient temperature Outdoor Air-cooled: -35°C~+45°C (Low-temp. kit is
required when the temperature is below -15°C)
When the unit is used in the following condition, Contact Vertiv Co.
• If the unit voltage exceeds the operating voltage range.
• Derating for altitude above 1000m.
• Other applications outside of applicable scopes.
Model P1020 P1025 P1030 P1035 P1040 P1050 P2060 P2070 P2080 P2090 P2100
Gross Cooling capacity and Sensible cooling capacity (kW)
Cooling 22.3 31.1 37.1 41.4 45.9 54.5 74.4 77.9 91.3 102.1 109.0
capacity*¹
(24 ºC DB
50%RH)
Sensible 19.4 26.9 32.4 35.9 40.1 48 64.9 68.7 80 89.6 95.8
cooling
capacity
(24ºC DB
50%RH)
Indoor unit Fan section
Std. Air 5500 6700 8000 9000 10600 12200 16000 18000 21200 24400 24400
volume
(m³/hr)
Fan 1 1 1 1 1 1 2 2 2 2 2
number
Fan power 0.64 1.02 1.47 1.83 1.51 1.86 2.94 3.65 3 3.72 3.72
(kW)*²
Downflow
Fan power 0.72 1.12 1.57 1.94 1.77 2.22 3.15 3.87 3.55 4.43 4.43
(kW)*² -
Upflow
Compressor*³
Number 1 1 1 1 1 1 2 2 2 2 2
PTC type Electric heater
Power 6 6 6 6 9 9 9 9 12 12 12
(kW)
Infrared humidifier
Humidifyin 4.5 4.5 4.5 4.5 4.5 4.5 10 10 10 10 10
g capacity
(kg/h)
Unit Footprint
Unit 853X874 X 1970 1130 X 995 X 1975 1330 X 995 1830 X 995 2230 X 995 X 1975
dimension X 1975 X 1975
(W*D*H)
(mm)
Indoor Unit Weight
Net weight 320 340 400 420 460 530 690 730 770 805 810
(kg)
• Performance tolerance is 5%
• For net capacities, deduct fan input power. Refer to the Liebert PEX+ Rating for
specific input conditions, air flow, and configuration
• *1: The above cooling capacity is based on condensing temperature of 45°C
• *2: For downflow unit ESP 20 Pa & for upflow unit ESP50Pa considered
• *3: Fixed Scroll compressor with R407C based refrigerant
• Standard offer is with TXV, EEV is available on request
• Water cooled condenser can be offered on request
Table 5.2
• Performance tolerance 5%
• For net capacities, deduct fan input power. Refer to the Liebert PEX+ Rating
for specific input conditions, air flow, and configuration.
• *1: The above cooling capacity is based on condensing temperature of 45°C
• *2: For downflow unit ESP 20Pa & for upflow unit ESP 50Pa considered
• *3: Digital Scroll compressor equipped with R407C refrigerant
• Standard offer is with TXV, EEV is available on request
• Water cooled condenser can be offered on request
6.1 Features
Large and Small Displays
The Liebert iCOM is available with either a large or small liquid crystal display.
• The Liebert iCOM with small display has a 128 x 64 dot matrix screen that
simultaneously shows two menu icons, along with descriptive text.
• The Liebert iCOM with large display has a 320 x 240 dot matrix screen that shows up
to 16 menu icons at a time, as well as descriptive text. This display may be used to
control a single cooling unit or any cooling unit on a network, regardless of how it is
connected - either integrated into a cooling unit or simply connected to the network
and mounted remotely.
Liebert iCOM’s menu-driven display is used for all programming functions on each
connected cooling unit. The Status menu shows the status of the conditioned space, such as
room temperature and humidity, temperature and humidity setpoints, alarm status and
settings, event histories and the current time.
Figure 6- 1 Wall Mount Large Display Figure 6 - 2 Direct Panel Mount Large Display
and Bezel
Figure 6 - 3 Direct Panel Mount Small Figure 6 - 4 Liebert iCOM Display and Bezel
Input/Output Board
• The Help key may be pressed at any time for a brief explanation of what is being
viewed.
• The risk of inadvertent system shutdown can cause loss of cooling and equipment
damage.
• Press the On/Off key on a Liebert iCOM large display while the system screen is
shown permits shutting down all units on the network.
• Large Liebert iCOM displays can view and control other units on the network when
they are in the same group. When turning a unit Off or On with the large display,
make sure that the unit to be shut down or started up is shown on the screen. If the
system screen is shown and the On/Off key is pressed, the Liebert iCOM shows a
notification that pressing the On/Off key again will turn Off all units on the network.
Table 6.1
Left and
Right Arrow Navigates through text and sections of the display
Keys
Green and Amber LEDs will flash alternately when the unit is in
Lower LED
Standby
Top View of cut-out location dimensions of at the base of P1020 and P1025 unit (unit: mm)
H: Water inlet for humidifier C/R: Condenser water inlet and outlet /refrigerant inlet and outlet
Figure 7-1 Cut-out location dimensions of at the base of P1030-P2100unit (unit: mm)
Table 7. 1 Dimensions of air outlet on top cover of Upflow unit (unit: mm)
Model A B C
P1020 to P1025 720 795 800
P1030 to P1035 650 900 700
P1040 to P1050 850 900 900
P2060 to P2070 650 900 1400
P2080 to P2100 850 900 1800
The equipment has knock-outs, be sure to mount sleeve to the cable holes to avoid
cutting the cables.
If the height of the plenum selected for air conditioner unit exceeds 600mm, consult
Vertiv Co. professional for non-standard production.
• Do not use the indoor unit in the open and severe outdoor environment.
• Avoid locating the indoor unit in concave or narrow areas, which can baffle
the airflow, shorten the cooling cycle and result in air return short circuit and
air noise.
• Avoid locating multiple indoor units close to each other. That can result in
crossing air patterns, unbalanced load and competitive operation.
• Do not install the unit near any precision equipment, and prevent the leaked
condensation water due to improper use of the air conditioner from affecting
the operation of precision equipment.
• Do not install any other devices (such as smoke detector) over the cabinet.
Condenser coil
Evaporator coil
• : Factory piping
The following points should be considered before checking out the overall layout
diagram:
Note:
1. Extension kit should be added to the “Eq. Length” marked with *.
2. D: discharge line, L: liquid line.
3. Consult Vertiv Co. If the line length exceeds 60m.
4. If the outdoor temperature of the unit is below -20℃, the low-temperature kit must be used, and please
consult Vertiv Co. for details.
• Designed for modulating control of the refrigerant mass flow with precision
• Ensures effective control on super-heating at the end of the evaporator
• Better low load capacity
• Designed for easy Installation-and-Service