Active Power Loss Minimization and Bus


Voltage Improvement with SVC Using Hybrid
NR-PSO Technique
Biswanath Bandyopadhyay 1, Subrata Majumdar 2
M.Tech Student, Power Electronics & Drives, Jalpaiguri Government Engineering College, West Bengal, India 1
Professor, Department of EE, Jalpaiguri Government Engineering College, West Bengal, India 2

ABSTRACT: This paper consists of Load flow, which is very important for any power system solution. A
comprehensive study of the Newton- Raphson (NR) method of load flow analysis with and without Flexible AC
Transmission System FACTS device is established. The major concerns of this paper is (1) Finding the sensitive buses,
(2) Connect FACTS device (here we use Static VAR Compensator (SVC)) to those buses to minimize the losses of the
system, (3) Make the voltage of those most sensitive buses constant irrespective of load on the respective buses, (4)
Solve the nonlinear equation of finding firing angle of SVC to find the firing angle of the thyristors of SVC. Here
sensitive buses are determined by “Load Changing Method”. Optimal size of SVC is evaluated by Particle Swarm
Optimization (PSO) Technique. PSO is also used to solve the nonlinear equation of finding firing angle of SVC for
each optimal sizing of SVC. It is a hybrid method in which optimal value of SVC and firing angle are calculated using
PSO method and load flow is done using NR method. All the programs have been implemented in MATLAB Software
and the IEEE 30-bus systems have been used as case studies.

KEYWORDS: Newton-Raphson method of load flow, Flexible AC Transmission System (FACTS) device, Static
VAR Compensator (SVC), Load Changing Method, Sensitive buses, Particle Swarm Optimization (PSO), IEEE 30-bus
system.

I. INTRODUCTION

Today electric power plays a very important role in the life of the community and in the development of various sectors
of economy. In fact the modern economy is totally dependent on the electricity. This in turn has led to increase in the
number of power stations and their capacities and consequent increase in power transmission lines which connect the
generating stations to the load centres. To meet the ever increasing demand it is now essential to maximize the
utilization of the existing transmission system. Not only that, in transmission system it is desirable to maintain the
receiving end voltage constant irrespective of load because most of the devices design to work on a constant supply
voltage.
For this reason it is important to make some arrangement to the transmission system so that the losses of the
transmission system get reduced as well as the voltage of the load end stay constant irrespective of load. FACTS
controllers minimizes loss, enhance the voltage profile and the load ability of power systems. In this paper we use
Static VAR Compensator (SVC) for several reasons. The most widely used shunt FACTS devices within power
networks is the SVC due to its low cost and good performance in system enhancement. Another very important and
challenging task to connect FACTS device is to find the appropriate location and the size of the FACTS. To find the
most sensitive buses in the transmission system, “load changing method” is used where the given load of the test data is
increased by 2%, 4%, 6%..............50% for each bus to find the variations of respective bus voltage. Here to find the
most suitable size of the SVC we use Particle Swarm Optimization (PSO) technique. PSO is also used to solve the
nonlinear equations to find the firing angle of SVC.

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5203


ISSN(Online): 2319-8753
ISSN (Print): 2347-6710

International Journal of Innovative Research in Science,


Engineering and Technology
(A High Impact Factor, Monthly, Peer Reviewed Journal)

Visit: www.ijirset.com
Vol. 7, Issue 5, May 2018

II. RELATED WORK

To successfully implement the project it is very important to understand the concepts of each and every part of the
systems. All the sources i.e. a number of books and papers were referred to undertake this projects. The book at ref [1]
by D.P.Kothari & J.S.Dhillon explains the main formulation part. Here total concept of Economic Load Dispatch i.e
from making of admittance matrix to exact loss formula, all have discussed in details. A basic idea as well as the
algorithm for Newton-Raphson method is discussed. The whole idea of Newton-Raphson load flow analysis method is
taken from the paper at ref [2] by Aditya Sharma, Manyu Saini and MdIrfan Ahmed. A comparative study between
various FACTS devices are discussed in paper at ref [3] by Pavlos S. Georgilakis and Peter G. Vernados. It helps to
choose SVC over other FACTS devices because of its simple construction and fast and accurate response. The firing
angle concept of SVC is very important to understand for achieving the proposed goal in our project. For this a paper at
ref [4] by A.Hema Sekhar & Dr.A.Lakshmi Devi, is referred. It describe the relations between firing angle and the
other parameters which helps to generate the fitness functions for PSO to find out the firing angle of SVC for every
sizing of it. Another paper at ref [5] by H. Amhriz-PBrez, E. Acha, and C. R. Fuerte-Esquivel, used to understand the
firing angle model of SVC. The idea of “Load Changing method” of finding sensitive bus is taken from the paper at ref
[6] by Pushpendra Mishra, H. N. Udupa, Piyush Ghune. As discussed before it is a hybrid project where NR method
and PSO both are used to serve their purpose, a proper idea of PSO and how it works is required to understand. Ref [7]
by Manjun Cai, Xuejian Zhang, Guangjun Tian, and Jincun Liu. The said paper describes the concept of PSO in very
simple way. Though few changes are made to simplify the algorithms, the basic concept of PSO is taken from this
paper only. All the concept of semiconductor devices used in FACTS devices are discuss in a great extend in the book
at ref [8] by Muhammad H. Rashid. All the information about IEEE 30 bus system is collected from the paper at ref [9]
by Dharamjit, D.K.Tanti. Ref [10] by Ahmed A. A. Esmin and Germano Lambert-Torres helps to understand the
application of PSO in Power System. This paper described the use of PSO for solving the optimal distribution system
reconfiguration problem for power loss minimization. In paper at ref [11] by LakshyaBhat, Anubhav Shrivastava and
Shivarudraswamy, 3 method of finding sensitive buses is described and also the importance of finding the sensitive
buses are stated. An idea of various FACTS devices are also taken from the paper at ref [12] by S. K. Srivastava, S. N.
Singh and K. G. Upadhyay. This paper helps to understand there control features and difference of SVC from others.

III. PROPOSED METHODOLOGY AND DISCUSSION:

NEWTON-RAPHSON METHOD OF LOAD FLOW: This method was named after Isaac Newton and Joseph
Raphson. The origin and formulation of Newton-Raphson method was dated back to late 1960s. It is an iterative
method which approximates a set of non-linear simultaneous equations to a set of linear simultaneous equations using
Taylor’s series expansion and the terms are limited to the first approximation.
Load Flow equations constitute a set of non-linear algebraic equations in terms of |V| in per unit and δ in radians as
shown below,

=| | | |[ cos( − )+ sin( − )] ( = 1, 2, … , ) … (1)

=| | | |[ sin( − )− cos( − )] ( = 1, 2, … , ) … (2)

Where
Pi is the real power, Qi is the reactive power, NB is number of total buses, Vi is the voltage of the ith bus, |Vi| is the
magnitude of the voltage, δi is the angle of the voltage, Gik is the real part of Yik,
Bik is the imaginary part of Yik., Yik is the element of the admittance bus.
These equations are expanded in Taylor’s series about the initial estimate and neglecting all higher order terms, the
following set of linear equations are obtained.

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5204


ISSN(Online): 2319-8753
ISSN (Print): 2347-6710

International Journal of Innovative Research in Science,


Engineering and Technology
(A High Impact Factor, Monthly, Peer Reviewed Journal)

Visit: www.ijirset.com
Vol. 7, Issue 5, May 2018


∆ ∆
= … … … … … (3)

Size of the matrix = NB+ (NB-(NV+1))-1 = 2(NB-1)-NV
Where
= , = , = , =
The new estimates for bus voltage are
= + ∆ ( = 2, 3, … , ) … … . . … . (4)

= + ( = ) … … … . (5)
After some iteration we get the Newton-Raphson result of Bus Voltages (Vi) and angle of the voltages (δi ). The power
loss in the line between the bus i and k is the sum of the power flows in the line from ith bus and from kth bus,
respectively, i.e.
= +
Where
l indicates the line numbers, Sik is the power flows from bus no. i to bus no. k, Ski is the power flows from bus no. k to
bus no. i
The total transmission active power losses can be computed by summing all the line flows of the power system, i.e.

= … … … … … … … (6)

Where
NL is number of line

FLEXIBLE AC TRANSMISSION SYSTEM (FACTS) DEVICE: The FACTS is a concept based on power-
electronic controllers, which enhance the value of transmission networks by increasing the use of their capacity. As
these controllers operate very fast, they enlarge the safe operating limits of a transmission system without risking
stability. FACTS can be categorized as Series Compensator and Shunt Compensator. SVC is one of the widely used
Shunt Compensator and the construction and operations are discussed below.

STATIC VAR COMPENSATOR (SVC): A static var compensator (SVC) is the first generation shunt compensator.
A typical SVC consists of Thyristor Controlled Reactor (TCR) and Thyristor Switched Capacitor (TSCs) or a fixed
Capacitor in parallel. The output of the compensator is controlled in steps by sequentially switching of TCRs and TSCs.
Figure (1) shows the basic firing angle model of SVC.

Figure 1: Basic model of SVC

From the model of SVC it is shown that a TCR and a fixed capacitor is connected parallel to each other where the
susceptance (BTCR) of the TCR is a function of thyristor firing angle (α).
1
= = … … … … … . . (7)
2( − ) + sin(2 )

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5205


ISSN(Online): 2319-8753
ISSN (Print): 2347-6710

International Journal of Innovative Research in Science,


Engineering and Technology
(A High Impact Factor, Monthly, Peer Reviewed Journal)

Visit: www.ijirset.com
Vol. 7, Issue 5, May 2018

Or,
2( − ) + sin(2 )
= … … … … … … … . (8)
Where
XL is the reactance (in per unit system) value of inductor connected to TCR
BL is the susceptance (in per unit system) value of inductor
XTSR is the value of reactance (in per unit system) of the TCR
BTCR is the susceptance (in per unit system) value of the TCR
α is the firing angle (red) of thyristors connected in TCR
The SVC equivalent susceptance (BSVC) can be determined by parallel operation of TCR with fixed capacitor as
2( − ) + sin(2 )
= − = − … … … … … … … . . (9)
Where
BSVC is the SVC equivalent susceptance (in per unit system)
BC is the susceptance (in per unit system) value of the fixed capacitor
After rearranging equation (9) we get
( − )
sin(2 ) − 2 = − 2 … … … … … … . (10)
Equation (10) is a non-linear equation. To find the value of α we use Particle Swarm Optimization (PSO) for
solving of the equation.
Here we use a SVC which has BL= 0.1pu and BC=0.06pu

LOAD CHANGING METHOD, SENSITIVE BUSES: A bus is said to be a sensitive bus if its voltage is heavily
fluctuate with load connected to that bus so sensitive bus is the one which is mostly suffered by the changes in load
demands. Here Load Changing Method is used to find the sensitivity index. It is a very simple method where test
system load data of each bus is increased one by one by 2%, 4%, 6%, 8%, 10%, 12% ………. 50% and then we have
compared all the results with the original power flow results of the test bus system for finding the sensitive buses.

PARTICLE SWARM OPTIMIZATION (PSO): Particle Swarm Optimization (PSO) algorithm originally is
developed by Kennedy and Eberhart based on the social behaviors of animal swarms (e.g. bird blocks and fish
schools).Due to the fact that PSO is a very easy, fast and powerful optimization technique, it is used for the solving of
various optimization problems in electrical engineering. Here to find the most suitable size of the FACTS device we
use PSO technique. PSO is also used to solve the nonlinear equations to find the firing angle of SVC.
PSO is initialized by a population of random solutions with random velocities. The potential solutions, called particles,
are then flows through the problem space. Each particle keeps track of its coordinates in the problem space, which are
associated with the best solution or fitness achieved so far. The fitness value is also stored. This value is called pbest.
Another ‘best’ value that is tracked by the global version of the particle swarm optimizer Is the overall best value, and
its location, obtained so far by any particle in the population. The value is termed gbest. Thus at each time step, the
particle changes its velocity and moves towards its pbest and gbest. At each iteration, new search points are generated
from the current search points using the following equations

= ∗ 0.99 … … … … … … . . (11)
= . + . ( ). − + . ( ). − … … … . . (12)
= + … … … … … … . (13)

Where
c1 and c2 are the learning factors, rand() is the random numbers between 0 and 1
w is inertia weight, Vi is the particle velocity, k is the iteration number

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5206


ISSN(Online): 2319-8753
ISSN (Print): 2347-6710

International Journal of Innovative Research in Science,


Engineering and Technology
(A High Impact Factor, Monthly, Peer Reviewed Journal)

Visit: www.ijirset.com
Vol. 7, Issue 5, May 2018

The pbest and gbest value are updated after every iteration this processes is repeated until the convergence is obtained.
For applying PSO an objective function is required to be defined. Here we apply PSO on three different objective
functions to fulfill three different objects.
To find the optimal size of SVC connected to sensitive buses for improving voltage profile as well as minimizing the
active power loss, total active power loss equation (equation (6)) is used as minimal objective function.
To find the optimal size of SVC connected to sensitive buses for different values of load connected to the respective
buses, the below equation is used as minimal objective function.
= … … … … … … . (14)
= − … … … … … … … … . . (15)
Where
V is the value of bus voltage when respective bus load is kept as test data
Vp is the value of bus voltage when respective bus load is increase p% of test data
To solve the non-linear equation of finding firing angle of SVC to find the firing angle of the thyristor for each sizing
of SVC, a modified version of equation (10) is used as minimal objective function as shown below
( − )
= (sin(2 ) − 2 ) − −2 … … … … . . (16)

Table 1: The parameters of PSO we used here is


Population Size 50
Inertial Weight, w 1
Learning Factor (1), C1 1
Learning Factor (2), C2 1
Maximum number of iteration 100

IV. RESULTS AND OBSERVATION

The proposed system is applied in IEEE 30 bus systems by using MATLAB software. Newton Raphson result of
voltage profile of the system with given test data is shown in figure (2)

Figure 2: NR result of voltage profile of IEEE30 bus system with given test data

After obtaining the power flow results at each percentage change in load as said earlier we obtained voltage profile at
each change and find the sensitive buses according to their change in voltage with load.

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5207


ISSN(Online): 2319-8753
ISSN (Print): 2347-6710

International Journal of Innovative Research in Science,


Engineering and Technology
(A High Impact Factor, Monthly, Peer Reviewed Journal)

Visit: www.ijirset.com
Vol. 7, Issue 5, May 2018

Figure 3: Sensitivity index with “Load Changing Method”

From above bar graph it is clear that 30th bus is the most sensitive bus and 26th bus is the second most sensitive bus in
this system. A single SVC is connected to the 30th bus to minimize the active power losses and to improve the voltage
profile and then another SVC is connected to 26th bus along with the one connected to 30th bus and observed the same
as before with single SVC. The voltage profile for each case is shown in figure (4) for comparative study,

Figure 4: Voltage profile of IEEE30 bus system with and without SVC connected

From this figure (4) it is clear that the voltage profile is improved with double SVC as compared to singe SVC and
without SVC.

Figure 5: Comparative study of active power loss with and without SVC

This bar diagram indicates the active power loss is also minimized with double SVC connected to the system.
The optimal value of SVC size for which the active power loss is minimized is obtained by PSO technique. Also the
non-linear equations of finding firing angle of the thyristors of SVC are solved by PSO technique to find the firing

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5208


ISSN(Online): 2319-8753
ISSN (Print): 2347-6710

International Journal of Innovative Research in Science,


Engineering and Technology
(A High Impact Factor, Monthly, Peer Reviewed Journal)

Visit: www.ijirset.com
Vol. 7, Issue 5, May 2018

angle of each sizing of SVC.

Parameters Without SVC With single SVC With double SVC


Location of SVC -- 30th bus (SVC1) 30th bus (SVC1)
26th bus (SVC2)
Susceptance value of SVC1 (pu) -- 0.0264 0.0219
Susceptance value of SVC2 (pu) -- -- 0.0242
Firing angle of SVC 1 (degree) -- 123.3978 120.5981
Firing angle of SVC 2 (degree) -- -- 122.0229
Real Power Loss (MW) 7.0892 7.0691 7.0443
Table 2: Comparative study of system parameters of IEEE 30 bus with and without SVC

After improving the voltage profile and minimizing the active power loss of the system our next object was to maintain
the voltage of 30th and 26th buses fixed, irrespective of change in load of respective buses. By changing the susceptance
value of SVC with the help of PSO we achieve that goal.

30th bus operation

Figure 6: Susceptance value of SVC to maintain voltage constant with variable load in 30th bus

At every 2% increase in given load at 30th bus the susceptance value of SVC get increased to maintain the voltage of
30th bus constant as shown in figure (6). Initially the susceptance value was 0.0219pu to minimise the active power loss
as shown before.

Figure 7: Firing angle of SVC to maintain voltage constant with variable load in 30th bus

To change the susceptance value of SVC, the firing angle of thyristor must also change. The firing angle with respect to
percentage change of load at 30th bus is shown in figure (7).

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5209


ISSN(Online): 2319-8753
ISSN (Print): 2347-6710

International Journal of Innovative Research in Science,


Engineering and Technology
(A High Impact Factor, Monthly, Peer Reviewed Journal)

Visit: www.ijirset.com
Vol. 7, Issue 5, May 2018

Figure 8: Change in voltage with and without SVC with variable load in 30th bus

Bus no. 30 was the most sensitive bus as stated before and the voltage waveform with respect to percentage increase in
load is shown in figure (8) (blue line) and the voltage profile after connecting the SVC is shown in figure (8) (red line).
From the figure (8) it can easily observed that the voltage variation is eliminated by SVC and bus no. 30 is no longer be
a sensitive bus.

Figure 9: Active power loss with and without SVC with variable load in 30th bus

Active power loss minimization is one of the main concerns of this paper. Figure (9) shows a comparative study of
active power loss of the system with and without SVC connected at 30th bus. It is easily observed that the active power
loss is reduced by connecting the SVC.

26th bus operation

Figure 10: Susceptance value of SVC to maintain voltage constant with variable load in 26th bus

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5210


ISSN(Online): 2319-8753
ISSN (Print): 2347-6710

International Journal of Innovative Research in Science,


Engineering and Technology
(A High Impact Factor, Monthly, Peer Reviewed Journal)

Visit: www.ijirset.com
Vol. 7, Issue 5, May 2018

At every 2% increase in given load at 26th bus the susceptance value of SVC get increased to maintain the voltage of
26th bus constant as shown in figure (10). Initially the susceptance value was 0.0242pu to minimise the active power
loss as shown before.

Figure 11: Firing angle of SVC to maintain voltage constant with variable load in 26th bus

To change the susceptance value of SVC, the firing angle of thyristor must also change. The firing angle with respect to
percentage change of load at 26th bus is shown in figure (11).

Figure 12: Change in voltage with and without SVC with variable load in 26th bus

Bus no. 26 was the second most sensitive bus as stated before and the voltage waveform with respect to percentage
increase in load is shown in figure (12) (blue line) and the voltage profile after connecting the SVC is shown in figure
(12) (red line). From the figure (12) it can easily observed that the voltage variation is eliminated by SVC and bus no.
26 is also no longer be a sensitive bus.

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5211


ISSN(Online): 2319-8753
ISSN (Print): 2347-6710

International Journal of Innovative Research in Science,


Engineering and Technology
(A High Impact Factor, Monthly, Peer Reviewed Journal)

Visit: www.ijirset.com
Vol. 7, Issue 5, May 2018

Figure 13: Active power loss with and without SVC with variable load in 26th bus

Figure (13) shows a comparative study of active power loss of the system with and without SVC connected at 26th bus.
It is easily observed that the active power loss is reduced by connecting the SVC.

V. CONCLUSION

From figure (3), it is clear that 30th bus is mostly suffered due to the change in load demand followed by bus no 26th so
necessary action is taken to maintain the bus voltages constant. Here we use two SVC’s on each buses. We utilize the
SVC’s not only to make the voltage constant we use this to minimize the losses of the overall system as shown in figure
(5). Figure (8) & (12) shows that the SVC’s maintain the voltage constant. Figure (6) & (10) shows the respective SVC
susceptance required to maintain the voltage constant. Figure (7) & (11) are the respective firing angle of SVC’s.
Figure (9) & (13) shows how the losses get reduced due to the SVC’s.

REFERENCES

[1] “POWER SYSTEM OPTIMIZATION” D.P.Kothari & J.S.Dhillon, Printice Hall of India Private Limited, New Delhi-110001, 2004.
[2] “POWER FLOW ANALYSIS USING NR METHOD” Aditya Sharma, Manyu Saini and MdIrfan Ahmed, International Journal of Electrical and
Electronics Engineers, Vol no. 9, Issue no. 1, January-Lune 2017.
[3] “FLEXIBLE AC TRANSMISSION SYSTEM CONTROLLERS: AN EVALUATION” Pavlos S. Georgilakis and Peter G. Vernados, Trans Tech
Publications, Switzerland.
[4] “FIRING ANGLE SVC MODEL FOR ANALYZING THE PERFORMANCE OF TRANSMISSION NETWORK USING NEWTON
RAPHSON LOAD FLOW” A.Hema Sekhar & Dr.A.Lakshmi Devi, International Journal of Electrical Engineering & Technology (IJEET) Volume 7,
Issue 5, September–October, 2016, pp.44–61.
[5] “ADVANCED SVC MODELS FOR NEWTON-RAPHSON LOAD FLOW AND NEWTON OPTIMAL POWER FLOW STUDIES” H.
Amhriz-PBrez, E. Acha, and C. R. Fuerte-Esquivel, IEEE TRANSACTIONS ON POWER SYSTEMS. VOL. 15, NO. 1, FEBRUARY 2000.
[6] “CALCULATION OF SENSITIVE NODE FOR IEEE – 14 BUS SYSTEM WHEN SUBJECTED TO VARIOUS CHANGES IN LOAD”
Pushpendra Mishra, H. N. Udupa, Piyush Ghune.
[7] “PARTICLE SWARM OPTIMIZATION SYSTEM ALGORITHM” Manjun Cai, Xuejian Zhang, Guangjun Tian, and Jincun Liu Institute of
Electrical engineering YanShan University, QinHuangdao HeBei 066004, China.
[8] “POWER ELECTRONICS- CIRCUITS, DEVICES AND APPLICATIONS” Muhammad H. Rashid Third Edition, Person Education, Delhi
110092, 2005.
[9] “LOAD FLOW ANALYSIS ON IEEE 30 BUS SYSTEM” Dharamjit, D.K.Tanti, International Journal of Scientific and Research Publications,
Volume 2, Issue 11, November 2012.
[10]“APPLICATION OF PARTICLE SWARM OPTIMIZATION TO OPTIMAL POWER SYSTEMS” Ahmed A. A. Esmin and Germano Lambert-
Torres, International Journal of Innovative Computing, Information and Control Volume 8, Number 3(A), March 2012.
[11] “SENSITIVITY ANALYSIS FOR 14 BUS SYSTEMS IN A DISTRIBUTION NETWORK WITH DISTRIBUTED GENERATORS”
LakshyaBhat, Anubhav Shrivastava and Shivarudraswamy, IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-
1676,p-ISSN: 2320-3331, Volume 10, Issue 3 Ver. I (May – Jun. 2015), PP 21-27
[12] “FACTS DEVICES AND THEIR CONTROLLERS: AN OVERVIEW” S. K. Srivastava, S. N. Singh and K. G. Upadhyay, NATIONAL
POWER SYSTEMS CONFERENCE, NPSC 2002

Copyright to IJIRSET DOI:10.15680/IJIRSET.2018.0705207 5212