LOAD CARRING CAPACITY OF 157 FLOOR SLAB OF
WAREHOUSE AT MOUZA KRUSHNANAGAR OF
BHUBANESWAR, DISTRICT KHORDHA.
Client
VERMA LOGISTICS PVT. LTD.
Behind Rudra Hospital , NH 16 Bhanpur , Gopalpur ,
Cuttack
Prepared By
S.M. CONSULTANTS
'S. M. Tower, Plot No. 130,
Mancheswar Industrial Estate, Rasulgarh,
Bhubaneswar 751 010. Odisha.Consultant: ‘STABILITY ANALYSIS
S.M.CONSULTANTS.
BHUBANESWAR
CONTENTS
Chapter No. Description Pageno.| |
1.0 Introduction 1
2.0 Planning for investigation 1
| [30 Preliminary Investigation 1
31 Site Location 1
3.2 3° Floor Plan 2
4.0 Analysis of Structure 2
41 Loading 3
444 Dead load and Imposed Load 3
4.1.2 Live Loads 3
4.4.3 Earthquake Loads 3
4.14 Load Combinations 3
5.0 STAAD input File 48
6.0 Results of Analysis 8
7.0 ‘Checking of Slab 8-10 |
8.0 Conclusion and Recommendation 10 |
|
|
|
|
Name of Project: ‘Structural Assessment of existing Warehouse at Plot No 42/1766, 423/1767 of khata No
797/1 at MouzaKrushnanagar of Bhubaneswar, District Khordha.Consultant
STABILITY ANALYSIS Glient
ay
iF S.M.CONSULTANTS
BHUBANESWAR Verma logisties Pvt. Ltd,
1.0. INTRODUCTION
‘The building is situated atPlot No 422/176, 423/1767 of khata No 797/1 at Mouza Krushnanagar of
Bhubaneswar, District Khordha. The building is a (G+1) framed structure.The Client desires to know the
Maximum load that can be applied on the 1" Floor slab.
2.0 PLANNING FOR INVESTIGATION
The Consultants charted out the following process to investigate the structural stability of the building.
a. Physical inspection of the building to locate any structural deficiency |
b. Study of the Dimension &Reinforcement details provided by the client.
¢. Analysis of the structure by 3D modelling using STAAD Pro v8i
3.0 PRELIMINARY INVESTIGATION
3.1. Site Location
The building is located at Mouza Krushnanagar of Bhubaneswar, District Khordha. The city of ahuboneswa
experiences rain fall of about 1500mm per annum with 80% of rainfall during monsoon. The Highest and lowest|
annual temperature are 48°C and 10°C respectively. The area experiences wind speed of 50 m/second and is in the|
| seismic Zone ti
‘Name of Project:
‘Structural Assessment of existing Warehouse at Plot No 422/1766, 423/1767 of khata No
797/1 at Mouzakrushnanagar of Bhubaneswar, District Khordha.
EfiConsultant: STABILITY ANALYSIS
S.M.CONSULTANTS
BHUBANESWAR
Data Provided By Client
Reinforcement Details
Component _| Dimension/Thickness | Reinforcement
Main Beam 300mm x 600mm _| 6-16# (Top) +6 - 124 (Bottom)
Secondary Beam | 300mm x 300mm __| 2-124 + 1 - 16H (Top) + 3- 124 (Bottom)
Column 350mmx550mm_ | 4-16%+8-128
Slab 150 mm BH @ 150 c/c
Footing Designed for 4 stories as per Clients information.
4.0 ANALYSIS OF THE STRUCTURE
4.1. Loading
This section covers description of structural configuration and type of civil structures, specific design
considerations, design loading, load combinations and design basis including material specifications.
‘The design loads have been considered in conformance to the requirements of |S 875 and IS 1893, as a minimum
unless more stringent requirements are specified therein. The following loads have been considered in general for
the analysis of structure.
Name of Project: ‘Siructural Assessment of existing Warehouse at Plot No 422/1766, 423/1767 of Khata No
° 797/41 at Mouzakrushnanagar of Bhubaneswar, District Khordha.Client:
[ Consultant: STABILITY ANALYSIS
Job No.: 77
S.M.CONSULTANTS
BHUBANESWAR
Verma logistics Pvt. Ltd.
4.1.1 Dead Imposed loads:
Self-weight:
It comprises of self-weight of all frame members modelled into the structure as well as the self-weight of
slabs applied as trapezoidal/ triangular/ uniform loads as applicable on the beams based on the yield line pattern
hes:
It comprises of floor finishes, partitions, false ceiling loads
Self- weight of structure including finishing and treatments as per relevant code of practices or from actual weight
of material used.
Materials : Unit weight
Plain cement concrete 224 KN/cum
Reinforced cement Concrete 225 KN/cum
Floor Finish 1 KN/sqm_
4.1.2 Live loads:
‘The superimposed load or otherwise live load is assessed based on the occupancy classifications as per IS.
875 (Part 2)-1987.
The imposed live load on 1" floor: 4 KN/sqm (i.e. 400 kg/sqm)
4.1.3 Earthquake load
The loading due to earthquake is assessed based on the provisions of IS 1893:2002 and as the site in
Bhubaneswar falls under Zone ill. The considerations made are as follows:
+ Zone factor - 0.16
* Importance factor - 1s
4.1.4 Load Combinations:
The various loads have been combined in accordance with the stipulations in IS 875 (Part 5):1987 and IS
456:2000. The combination that produces most unfavorable effect in the building foundation or structural |
member concerned has been adopted for analysis.
Basic load cases:
1. Dead Load DL
2. Live Load uw
3. Earthquake Load EQX& EQZ
Name of Project ‘Structural Assssment of existing Warehouse al Plot No 422/1766, 4239/1767 of Khata No
797/1 at MouzaKrushnanagar of Bhubaneswar, District Khordha.
aeConsultant:
Load Combinations for Analysis
Client:
STABILITY ANALYSIS
S.M.CONSULTANTS
BHUBANESWAR Verma logistics Pvt. Ltd.
1, 15x (DL+LL)
2. 1.2.x (DL+LL+EQX)
3. 1.2 x (DL+LL-EQX)
4. 1.2.x (DL+LL+EQ2Z)
5. 12x (DL+LL-£QZ)
SSTAAD INPUT FILE |
STAAD SPACE
‘START JOB INFORMATION
ENGINEER DATE 18-Sep-19
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER KN
JOINT COORDINATES
1000; 27.765 00; 3 15.53 0 0; 4 23.295 0.0; 5 0.0 3.883; 6 7.765 0 3.883;
7 15.53 0 3.883; 8 23.295 0 3.883; 900 7.766; 10 7.765 07.766;
11 15.53 0 7.766; 12 23.295 0 7.766; 13 0 0 11.649; 14 7.765 0 11.649;
| 15 15.53 0 11.649; 16 23.295 0 11.649; 17 0 -1.5 0; 18 7.765 -1.5 0;
19 15.53 -1.5 0; 20 23.295 -1.5 0; 210 -1.5 3,883; 22 7.765 -1.5 3.883;
23 15.53 -1.5 3.883; 24 23.295 -1.5 3,883; 25 0-1.5 7.766;
26 7.765 -1.5 7.766; 27 15.53 -1.5 7.766; 28 23.295 -1.5 7.766;
29 0-1.5 11.649; 30 7.765 -1.5 11.649; 31 15.53 -1.5 11.649;
32 23.295 -1.5 11.649; 33 0 4.594 0; 34 7.765 4,594 0; 35 15.53 4.594 0;
36 23.295 4.594 0; 37 0 4.594 3.883; 38 7.765 4.594 3,883;
Name of Project: ‘Structural Assessment of existing Warehouse at Plot No 422/1766, 423/1767 of Khata No
_ 797/1 at MouzaKrushnanagar of Bhubaneswar, District Khordha.
aConsultant STABILITY ANALYSIS Client:
S.M.CONSULTANTS.
BHUBANESWAR Verma logistics Pvt. Ltd.
39 15.53 4.594 3.883; 40 23.295 4.594 3.883; 41 0 4.594 7.766;
42 7.765 4.594 7.766; 43 15.53 4.594 7.766; 44 23.295 4.594 7.766;
45 0 4.594 11.649; 46 7.765 4.594 11.649; 47 15.53 4.594 11.649;
48 23.295 4.594 11.649; 49 0 8.532 0; 50 7.765 8.532 0; 51 15.53 8.532 0;
| 52 23.295 8.532 0; 53 08.532 3.883; 54 7.765 8.532 3.883;
55 15.53 8.532 3.883; 56 23.295 8.532 3.883; 57 0 8.532 7.766;
58 7.765 8.532 7.766; 59 15.53 8.532 7.766; 60 23.295 8.532 7.766;
| 61 0 8.532 11.649; 62 7.765 8.532 11.649; 63 15.53 8.532 11.649;
64 23.295 8.532 11.649;
MEMBER INCIDENCES
1117; 2218; 3319; 44 20; 55 21; 6 6 22; 7 7 23; 88 24; 99 25;
10 10 26; 11 11 27; 12 12 28; 13 13 29; 14 14 30; 15 15 31; 16 16 32; 1712;
18 23; 193 4; 204 8; 218 12; 22 12 16; 23 5 6; 246 7; 25 7 8; 269 10;
27 10 11; 28 11 12; 29 13 14; 30 14 15; 31 15 16; 32 3 7; 337 11; 34.1115;
35 26; 36 6 10; 37 10 14; 38.15; 39 59; 409 13; 41 133; 42 234; 43 3.35;
44 4 36; 45 5 37; 46 6 38; 47 7 39; 48 8 40; 49 9 41; 50 10 42; 511143;
52 12 44; 53 13 45; 54 14 46; 55 15 47; 56 16 48; 57 33 34; 58 34 35; 59 35 36;
60 36 40; 61 40 44; 62 44 48; 63 37 38; 64 38 39; 65 39 40; 66 41 42; 67 42.43;
68 43 44; 69 45 46; 70 46 47; 71 47 48; 72 35 39; 73 39 43; 74 43 47; 75 34 38;
76 38 42; 77 42 46; 78 33 37; 79 37 41; 80 41 45; 81 33 49; 82 34 50; 83 35 51;
84 36 52; 85 37 53; 86 38 54; 87 39 55; 88 40 56; 89 41 57; 90 42 58; 91 43 59;
92 44 60; 93 45 61; 94 46 62; 95 47 63; 96 48 64; 97 49 50; 98 50 51; 99 5152;
100 52 56; 101 56 60; 102 60 64; 103 53 54; 104 54 55; 105 55 56; 106 57 58;
107 58 59; 108 59 60; 109 61 62; 110 62 63; 111 63 64; 1125155; 113 55 59;
114 59 63; 115 50 54; 116 54 58; 117 58 62; 118 49 53; 119 53 57; 12057 61;
DEFINE MATERIAL START
ISOTROPIC CONCRETE
£2.17185e+007
POISSON 0.17
DENSITY 23.5616
ALPHA 1e-005
DAMP 0.05
TYPE CONCRETE
STRENGTH FCU 27579
END DEFINE MATERIAL
MEMBER PROPERTY AMERICAN
17 TO 19 23 TO 31 57 TO 59 63 TO 71 97 TO 99 103 TO 111 PRIS YD 0.6 ZD 0.3
20 TO 22 32 TO 40 60 TO 62 72 TO 80 100 TO 102 112 TO 120 PRIS YD 0.3 2D 0.3
1 TO 16 41 TO 56 81 TO 96 PRIS YD 0.55 2D 0.35
CONSTANTS:
MATERIAL CONCRETE ALL
SUPPORTS
17 TO 32 FIXED
DEFINE 1893 LOAD
Name of Project: ‘Structural Assessment of existing Warehouse at Plot No 420/1766, 423/1767 of Khata No
° 797/1 at MouzaKrushnanagar of Bhubaneswar, District Khordha.
aEGaiians STABILITY ANALYSIS Client
Verma logistics Pvt. Ltd.
ZONE 0.016 RF 511.5551 DM 0.05
JOINT WEIGHT
1 WEIGHT 3.463
2 WEIGHT 5.228
3 WEIGHT 5.228
4 WEIGHT 3.463
|5 WEIGHT 3.912
6 WEIGHT 5.628
7 WEIGHT 5.628
8 WEIGHT 3.912
9 WEIGHT 3.912
10 WEIGHT 5.628
11 WEIGHT 5.628
12 WEIGHT 3.912
13 WEIGHT 3.463
14 WEIGHT 5.228
15 WEIGHT 5.228
16 WEIGHT 3.463
17 WEIGHT 0.347
18 WEIGHT 0.347
19 WEIGHT 0.347
20 WEIGHT 0.347
21 WEIGHT 0.347
22 WEIGHT 0.347
23 WEIGHT 0,347
24 WEIGHT 0.347
25 WEIGHT 0.347
26 WEIGHT 0.347
27 WEIGHT 0.347
28 WEIGHT 0.347
29 WEIGHT 0.347
30 WEIGHT 0.347
31 WEIGHT 0.347
32 WEIGHT 0.347
33 WEIGHT 8.018
34 WEIGHT 14.35
35 WEIGHT 14.35
36 WEIGHT 8.018
37 WEIGHT 12.598
38 WEIGHT 23.568
39 WEIGHT 23.568
40 WEIGHT 12.598
41 WEIGHT 12.598
42 WEIGHT 23.568
Name of Project: Structural Assessment of existing Warehouse at Plot No 4221766, 4239/1767 of Khata No
* 797/1 at MouzaKrushnanager of Bhubaneswar, District Khordha.
=O=Consultant:
STABILITY ANALYSIS Client :
S.M.CONSULTANTS
BHUBANESWAR
Verma logistics Pvt. Ltd.
43 WEIGHT 23.568
44 WEIGHT 12.598
45 WEIGHT 8.018
46 WEIGHT 14.35
47 WEIGHT 14.35
48 WEIGHT 8.018
49 WEIGHT 5.9
50 WEIGHT 11.417
51 WEIGHT 11.417
52 WEIGHT 5.9
53 WEIGHT 9.546
54 WEIGHT 18.774
55 WEIGHT 18.774
56 WEIGHT 9.546
57 WEIGHT 9.546
58 WEIGHT 18.774
59 WEIGHT 18.774
60 WEIGHT 9.546
61 WEIGHT 5.9
62 WEIGHT 11.417
63 WEIGHT 11.417
64 WEIGHT 5.9
1893 LOAD X 1
1893 LOADZ1
SELFWEIGHT Y-1
FLOOR LOAD
FLOOR LOAD
YRANGE 2 6 FLOAD -4 GY
LOAD COMB 5 1.5 (DL+LL)
315415
312412112
31.24121-12
312412212
31.241.22-12
LOAD 1 LOADTYPE Seismic TITLE EQX |
LOAD 2 LOADTYPE Seismic TITLE EQZ |
| LOAD 3 LOADTYPE Dead TITLE SELF WEIGHT
YRANGE 2 10 FLOAD -3.5 GY
LOAD 4 LOADTYPE Live REDUCIBLE TITLE LIVE LOAD
YRANGE 6 10 FLOAD -1.5 GY
LOAD COMB 6 1.2 (DL+LL¥EQX)
LOAD COMB 7 1.2(DL+LL-EQX)
LOAD COMB 8 1.2(DL+LL+EQZ)
LOAD COMB 9 1.2(DL+LL-EQZ)
Name of Project:
Structural Assessment of existing Warehouse at Plot No 422/1766, 423/1767 of Khata No
797/1 at MouzaKrushnanagar of Bhubaneswar, District Khordha.
aesmconsuutants [262 [7
PERFORM ANALYSIS
‘START CONCRETE DESIGN |
CODE INDIAN
FC 20000 ALL |
FYMAIN 500000 ALL
DESIGN BEAM 17 TO 4057 TO 80 97 TO 120
DESIGN COLUMN 1 TO 16 41 TO 56 811096
‘Verma logistics Pvt. Ltd.
END CONCRETE DESIGN
FINISH
6.ORESULTS OF ANALYSIS:
| |
‘Member Steel Required Steel Provided Remark
Column 1540mm 82H + 4-168 =1708mm" | OK
‘Main Beam Top=1i27mm Top 6-16#=1206mm' OK
Bottom=529.63 mm’ Bottom6-12# =678 mm”
Secondary Beam Top = 367 mm’ Top2- 12#+1-16#= 427 _| OK
i mm?
Bottom = 205 mm’
Bottom 3-12# = 339 mm*
7.0 CHECKING OF SLAB REINFORCEMENT:
DESIGN OF SLAB |
Design parameters
| Span of slab
te - 3.882m = 11.833 ft
| if . 7.765m = 23.667 ft
Wik = 2.000
Material grade
concrete M20 steel FeS00
20
Fek= MPa Fy = 500 MPa
design constants
Xumax/d= 0.46 Qu= — 2,65451729
load calculation for slab |
Name of Project: ‘Structural Assessment of existing Warehouse at Plot No 422/1766, 423/1767 of Khata No
797/1 at Mouzakrushnanagar of Bhubaneswar, District Khordha.
~8-Consultant: STABILITY ANALYSIS
S.M.CONSULTANTS.
BHUBANESWAR
Assuming slab
thickness 150 mm
dead load of slab = 25x1x1x 0.15 = 3.75. kN/m?
Miscellaneous = 1 kN/m’?
liveload 5 4 kN/m?
total = 8.75 kN/m*
factored load = 13.125 kN/m?
for interior panel Ref. table 26 of IS 456:2000
Gas 0.049 Oye 0.024
546 0.065 G50 0.032
Mag ae ‘Maximum Bending moment = 12.8587 kNm
Depth required = / Mu = 69.599 mm
Qu*b |
Providing 8 mmdia bars with 20. mmclear cover
depth provided = 126 mm oK
Reinforcement
calculation ( / a
ent: 1 46/fck*Mupodr2 . ose
Fy/Fck
Ast
| req 246.808 mm?
‘minimum tension reinforcement = 0.12
| Ast -
| amin . 151.2. mm?
Ast to be provided . 246.8084 mm’
spacing required = 203.5587 mm
spacing should not less than = 300 mm
required spacing = 203.5587 mm
ard = 378 mm
. mm
provide spacing 150 c/c
Ast provided = 334.9333 mm?
| Pt provided = 0.266
check for deflection
Service stress f= 0.S8*fy*Ast,req/Ast,provided = 213.698 N/mm?
Modification factor = 2
Maximum L/d ratio s 52
Name of Project: ‘Structural Assessment of existing Warehouse at Plot No 422/1766, 423/1767 of Khata No
797/1 at MouzaKrushnanagar of Bhubaneswar, District Khordha.
=92Consuftant: ‘STABILITY ANALYSIS
S.M.CONSULTANTS
BHUBANESWAR Verma logisties Pvt Lid
{ provided id rat a 30.812 OK
Check for shear
vu - 9.045 kN
‘yeVu/bd 0.072 N/mm? |
for Pt 0.266
t 0.368
k 13
kx. * 0.478 Ok
8.0 CONCLUSION & RECOMMENDATION
From all the Informations provided by client and collected from site measurements it is concluded that, the
1" floor of the existing building is found to be adequate for carrying a load up to 400 kg per sqm.
Name of Project: ‘Structural Assessment of existing Warehouse af Plot No 42/1766, 423/1767 of khata No
° 797/1 at MouzaKrushnanagar of Bhubaneswar, District Khordha.
~10-