The temperature of a transformer winding is an important indi- Standard microswitches High-perform. microswitches
cator of the load and performance and should be monitored Resistive Inductive Resistive Inductive
continuously to prevent unacceptable overload and possible VOLTAGE load load load load
thermal degradation. However the winding by its very nature
125V AC 5A 5A 10 A 10 A
will be at raised potential making direct sensing impossible.
Comem overcome this problem by indirect sensing using 250V AC 5A 5A 10 A 10 A
Thermal Image Technology.
Basically the sensor comprises a heat sensitive resistive circuit 30V DC 5A 3A 10 A 10 A
through which passes a current. The thermometer can be fine 50V DC 1A 1A 3A 2.5 A
tuned via the potentiometer on the indicator dial.
75V DC 0.75 A 0.25 A 1A 0.5 A
These instruments can be supplied with or without a fixing
125V DC 0.5 A 0.1 A 0.5 A 0.1 A
bracket (flange) and can be fitted with up to four changeover
micro-switches for control of cooling or for operating alarm and 250V DC 0.25 A 0.1 A 0.25 A 0.1 A
trip circuits.
OPTIONS
COMPONENT SPECIFICATION
Max. temperature pointer: a red drag hand pointer, with
Temperature sensing system: expansion type. The sen- reset knob located on the lens.
sing system is filled with a special organic fluid and has a built Back flange: bracket for wall mounting. Four holes 7 mm
in compensation for changes in ambient temperature. dia. on 175 mm PCD.
Sensing system components: Bulb - bronze or stainless Elastic suspension: this device offers damping for excess
steel. Capillary tube - copper or stainless steel. Bourdon spring - vibration.
bronze. Earthquake proof version: fitted with the elastic suspen-
Capillary tube protection: copper tube. Flex galvanized sion, and some modification to internal components.
steel + PVC armouring or flexible AISI 304 stainless steel PT 100 sensor: for remote monitoring.
armouring. Remote display: a 48 x 96 mm digital display from the PT
Casing: aluminium alloy, powder coated (RAL 7035). The 100 SENSOR.
paint finish is designed to resist even the most aggressive clima-
te and polluted atmosphere. The case is provided with a
breather to prevent condensation in the lens. Wiring is facilita-
ted by the provision of a large junction box separate from the
sensing system.
Mechanical Protection: IP 65. The instruments are suitable
for mounting outdoors in tropical or arctic climates (ambient
temperature from -40 to +70 °C). All components are manufac-
tured from corrosion proof material or given protective surface
treatments.
Lens: Special glass or polycarbonate.
Locking ring: chrome-plated brass.
Standard measuring ranges: 0/150 °C, 0/160 °C.
Measuring Tolerance: 1.5% of full scale value.
Repeat Accuracy: 2% of full scale value.
Microswitches: Insulation - 2000V, 50Hz between terminal
and earth for 60 secs. Make/break capacity - see table below.
Thermal image current: the heating resistance circuit
wound around the sensing bulb is powered by the CT fitted to
the transformer. Both this resistance and the potentiometer that
regulates it are sized according to the availble current from the
CT.
Standard values are: 1A, 1.5A, 2A, 5A. This value must be
clearly specified at the time of ordering.
NO MATCHING UNIT IS REQUIRED.
3
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 4
Ø 172 95
M14 3 50
3
4
1
6
9 260
12
7
11
10 2
5
50
115
Fig. A1
2 Locking glass ring 12 Potentiometer for thermal image heating system adjustment
4 Breather device
5 Capillary output
6 Dial
10 Terminal box
4
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 5
Ø 172 95
3
4
1
4
6
9
260
12
7
11
N. 4 HOLES
dia. 7 mm
10 at 45° 2
5
50
115
Ø 175
Ø 195
Fig. B1
2 Locking glass ring 12 Potentiometer for thermal image heating system adjustment
4 Breather device
5 Capillary output
6 Dial
10 Terminal box
5
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 6
0°/+150° C 0°/+160° C
Range :
1 2 3 4
Number of microswitches :
1m 2m 4m 6m other...
Capillary length :
Fig. 1 Fig. 2
Bulb : Fig. G1 (female connection) (male connection)
L=
Bulb length : Fig. G1
mm.
(thread
included in)
YES NOT
Maximum temperature resettable pointer :
PT 100 ELASTIC
Options : SENSOR SUSPENTION
4...20mA DIGITAL
TRANSMITTER READOUT
METER
1A 1.5A 2A 5A
Nominal current from current transformer:
6
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 7
7
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 8
8
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 9
Ø 172 95
M14 3 50
3
4
1
6
9 260
7
11
10 2
5
50
115
Fig. - C1
4 Breather device
5 Capillary output
6 Dial
9
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 10
Ø 172 95
3
4
1
6
9 4 260
7
11
N. 4 HOLES
dia. 7 mm
10 at 45° 2
5
50
115
Ø 175
Ø 195
Fig. - D1
4 Breather device
5 Capillary output
6 Dial
10
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 11
1 2 3 4
Number of microswitches :
1m 2m 4m 6m other...
Capillary length :
Fig. 1 Fig. 2
Bulb shape : Fig. G1 (female connection) (male connection)
L=
Bulb length L = Fig. G1
mm.
(thread
included in)
YES NOT
Maximum temperature resettable pointer :
PT 100 ELASTIC
Options : SENSOR SUSPENSION
4...20mA DIGITAL
TRANSMITTER READOUT
METER
11
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 12
F
F
L F F F
L
L
L L
Ø 11 Ø 11 Ø 12 Ø 16 Ø 16
fig. 1 fig. 2 fig. 3 fig. 1 fig. 2
Fig. - G1
ELASTIC SOSPENSION
M14
113
Ø 58
Fig. - H1
12
cat TERMOMETRI -GB- 29-03-2007 16:15 Pagina 13
96
48
14
142
122
6
Fig. - I1
13
Due to technical improvement of our products, the information contained in
this catalogue may be subjected to change without notice.
®
comem® - S.p.A