This "MS/0401/C/0461-00 ” reviewed for ” Galvanized Steel-Screed Angle with PNT-11 finish”

and to be fixed as per IFC drawings with latest revisions as per applicable bulletin.

Detailed Comments:

-Contractor to coordinate the height of angle with its locations. Angle should not be visible
where having two different build up meet.

-Contractor to take into consideration regarding the height of the angle, the thickness of mastic
joint that will be applied on top of angle.

-Contractor to ensure compliance with project galvanizing standards and paint requirements.

-For FOH areas, follow interface details on IFC drawings.

-Mock-up to be approved prior to commencement of installation on site.

General Comments:

1) Contractor to ensure compliance with project specification including but not limited to
specification “099600 & 078100”.

2) Angle applicable as per indicated locations ONLY. Shop drawings/details to be submitted to


consultant for review and approval.

3) Contractor to satisfy performance requirements in accordance with the contract documents


and reviewed Method Statement by the Engineer (CMA).

4) Contractor to Comply with Warranty period & requirements as per Division 01 Section
"Warranties"

Status Code - 2