Code 3 Comments : Code 3 for the top anchor. The load is applied
4 at the wrong location greatly understating the forces on the Noted ,revised design attached
anchor.
Arup Comments:
7 IBC partition load applies. Add load case. Partition Load included
10 Verify this is the correct weld stress to use. Specify filler. Weld stress verified with filler
Load acts at through bolt. This puts moment on the bracket and
11 Moment from bolt considered
concrete bolts.
12 All bolts in moving connections to have nylon locknuts or similar. Noted
Project: ABU DHABI INTERNATIONAL AIRPORT MIDFIELD TERMINAL BUILDING
Subject: DS/0401/10733/R0
???0401-USW-CA-GH-001???
13 There is tension on the bolt from the prying of the Fz force. Tension considered
These plates are in weak axis bending from Fz force. Plates are two
14 Plates checked for weak axis bending
independent plates and not composite.
15 Check deflections and compare to allowable deflections. Deflections checked and found to be within limits
17 Verify calc is applicable to overhead condition. Verified. Same anchor used for similar application
There will be significant rebar near the bottom of the slab. Verify
Forces on the bolts are very less and hence embedment
18 anchor bracket and bolts can accommodate one or more bolts
length also less.
being relocated to miss rebar in concrete.
19 There are moments. The 1.5kN load acts below the baseplate. Moments included.
Sl.No DESCRIPTION
1 DESIGN INFO
2 DESIGN CHECK
3 STAAD OUTPUT
DESIGN CHECK FOR STEEL FRAMING FOR SMOKE WALL PARTIITON- TYPE 01
SCOPE
1 DESIGN CODE
Generally all the design has been carried out in accordance with a particular reference
to the following codes of practice.
b) BS 6399- Part 1:1996 - Code of practise for dead & imposed loads
2 MATERIAL
2
a) Steel sections/plates -BS EN S 275 JR(fy = 275N/mm )
3 DESIGN LOADS
As per client data, steel members as subjected to a load of 0.8kN/m2 from Partition wall
Horizontal load according to IBC of 0.24 kPa have bben applied on steel frame.
Earthquake load according UBC 1997, please refer STAAD Report for Eartquake Load
d) Partition Load
As per IBC code provision, a min load of 0.74 kN/m2 for any partition loads
DL DL WL
span lw 1.6 0.74 0.24
2.1 1.05 1.68 0.78 0.25
2.1 2.1 3.36 1.55 0.50
2.2 2.15 3.44 1.59 0.52
1.1 1.76 0.81 0.26
STEEL FRAMING FOR SMOKE WALL PARTIITON 3 OF 8
Project :- ABU DHABI INTERNATIONAL AIRPORT MIDFIELD TERMINAL BUILDING
4 LOAD COMBINATION
Please see attached STAAD Report for Load Combinations
5 DESIGN OF MEMBERS
Actual deflection ( from staad) (conservatively, not considering col defl) = 5.3 mm Hence safe
e Check for weld for box to end plate Reaction Summary- L/C 12: Node 13
Fx = 0.50 kN
Fz = 2.11 kN
Fy = 40.0 kN
Mx = 2.24 kN-m
Mz = 0.54 kN-m
table37
3 2
Resultant stress on weld = 0.199 x 10 = 66.23 N/mm BS 5950:
0.6 x 5 cl 6.8.6
2
< 220.0 N/mm Hence safe
STEEL FRAMING FOR SMOKE WALL PARTIITON 6 OF 8
Project :- ABU DHABI INTERNATIONAL AIRPORT MIDFIELD TERMINAL BUILDING
Fy = 0.0 kN
Fz = 1.5 kN
For endplate and anchor bolts,
moment due to eccentricity Mx = 1.5 x 0.14
ie Mx = 0.21 kN-m
Fz
3
Required Thickness t = √ 6M √ 6x 24.0 x 10 = 3.62 mm
=
b py 40.0 x 275
< 16.0 mm Hence safe
d Check for bracket plate bending about weak axis
iii) Design check for SHS 80x80x5 curved beam to column SHS 80x80x5 welded connection
Design Forces
LC- 24 ;beam 3
- 5, Node 23
Fy = 1.50 kN
Fx = 0.90 kN
Mz = 1.53 kN-m
By Date18-Feb-19 Chd
17
22
18
21
19 20
9
Y 14
X 10
Z 13 Load 6
11 12
Whole Structure
Reactions
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kNm) (kNm) (kNm)
9 101:DL+WL-X -0.99 16.93 0.25 0.39 -0.01 1.20
102:DL+WL-Z -0.20 14.12 -1.81 -1.35 -0.01 0.06
103:DL+EQ-X -0.14 16.28 0.06 0.05 -0.00 0.17
104:DL+EQ-Z -0.02 15.98 -0.26 -0.20 -0.00 0.01
10 101:DL+WL-X -1.62 30.18 0.17 0.37 0.01 1.45
102:DL+WL-Z -0.40 32.01 -2.27 -1.49 0.00 0.16
103:DL+EQ-X -0.23 31.44 0.03 0.05 0.00 0.21
104:DL+EQ-Z -0.05 31.63 -0.31 -0.22 0.00 0.02
11 101:DL+WL-X -1.90 30.84 -0.17 0.14 0.04 1.41
102:DL+WL-Z -0.41 32.25 -1.95 -1.42 0.03 0.08
103:DL+EQ-X -0.26 31.54 -0.03 0.01 0.00 0.21
104:DL+EQ-Z -0.05 31.68 -0.28 -0.21 0.00 0.01
12 101:DL+WL-X -2.16 31.31 -0.28 -0.06 0.02 1.40
102:DL+WL-Z 0.01 32.81 -1.82 -1.57 0.05 -0.22
103:DL+EQ-X -0.30 31.59 -0.05 -0.01 0.00 0.21
104:DL+EQ-Z 0.01 31.74 -0.26 -0.23 0.01 -0.03
13 101:DL+WL-X -2.33 32.46 -0.17 -0.08 0.00 1.46
102:DL+WL-Z 0.41 33.11 -1.62 -1.72 0.01 -0.41
103:DL+EQ-X -0.32 32.35 -0.03 -0.01 0.00 0.21
104:DL+EQ-Z 0.06 32.42 -0.24 -0.25 0.00 -0.05
14 101:DL+WL-X -1.81 18.55 -0.01 -0.01 -0.00 1.29
102:DL+WL-Z 0.38 15.95 -1.13 -1.43 -0.04 -0.41
103:DL+EQ-X -0.29 17.08 -0.00 -0.00 -0.00 0.20
104:DL+EQ-Z 0.04 16.81 -0.17 -0.20 -0.01 -0.05
Print Time/Date: 19/02/2019 08:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 1 of 1
Job No Sheet No Rev
PIC 1
Part
Software licensed to HP
Job Title Ref
By Date18-Feb-19 Chd
6.20m
0.68m2.07m
2.21m
1.10m 2.07m 2.07m
2.07m
Y
X
Z Load 1
Whole Structure
17
22
18
21
19 20
24
36
23
26
32 35
25 28 30
9 31
27 29
Y 14
X 10
Z 13 Load 1
11 12
Whole Structure
24
34
26
32
28
30
23
40
33
44
17
25
35
31
41
43
22
45
27
42
29
18
36
38
21
Y 37
19
X
20
Z Load 1
Whole Structure
Print Time/Date: 19/02/2019 08:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 1 of 3
Job No Sheet No Rev
PIC 2
Part
Software licensed to HP
Job Title Ref
By Date18-Feb-19 Chd
-1.68 kN/m
-3.36 kN/m -1.76 kN/m
-1.68 kN/m -3.44 kN/m
-3.36 kN/m -3.36 kN/m
-3.36 kN/m -1.76 kN/m
-3.44 kN/m
-1.68 kN/m -3.36 kN/m -3.36 kN/m
-3.36 kN/m -1.76 kN/m
Y -3.44 kN/m
X -3.36 kN/m -3.36 kN/m
Z Load 1
DL
0.25 kN/m
0.26 kN/m
0.25 kN/m
0.50 kN/m 0.26 kN/m
0.52 kN/m
0.50 kN/m 0.50 kN/m
0.50 kN/m
0.25 kN/m
Y 0.52 kN/m
X 0.50 kN/m 0.50 kN/m 0.26 kN/m
Z Load 2
0.50 kN/m
0.52 kN/m
0.50 kN/m 0.50 kN/m
WL-X
0.25 kN/m
0.26 kN/m
0.25 kN/m0.50 kN/m
0.52 kN/m
0.50 kN/m 0.50 kN/m 0.26 kN/m
0.50 kN/m
0.52 kN/m
0.25 kN/m 0.50 kN/m 0.50 kN/m
Y 0.26 kN/m
X 0.50 kN/m
0.52 kN/m
Z Load 3
0.50 kN/m 0.50 kN/m
WL-Z
Print Time/Date: 19/02/2019 08:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 2 of 3
Job No Sheet No Rev
PIC 3
Part
Software licensed to HP
Job Title Ref
By Date18-Feb-19 Chd
0.39 kN
0.41 kN
0.77 kN
0.75 kN 0.75 kN
0.13 kN
0.03 kN 0.14 kN
0.03 kN
0.26 kN 0.06 kN 0.26 kN 0.06 kN
Y 0.26 kN
X 0.26
0.06 kN kN 0.06 kN
Z Load 4
EQ-X
0.13 kN
0.26 kN
0.26 kN 0.14 kN
0.26 kN 0.26 kN
0.03 kN
0.03 kN
0.06 kN
0.06 kN
0.06 kN 0.06 kN
Y
X
Z Load 5
EQ-Z
-0.78 kN/m
-1.55 kN/m -0.81 kN/m
-0.78 kN/m -1.59 kN/m
-1.55 kN/m -1.55 kN/m
-1.55 kN/m -0.81 kN/m
-1.59 kN/m
-0.78 kN/m -1.55 kN/m -1.55 kN/m
-1.55 kN/m -0.81 kN/m
Y -1.59 kN/m
X -1.55 kN/m -1.55 kN/m
Z Load 6
DL-PARTITION LOAD
Print Time/Date: 19/02/2019 08:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 3 of 3
Job No Sheet No Rev
1
Part
Software licensed to HP
Job Title Ref
By Date18-Feb-19 Chd
Print Time/Date: 19/02/2019 08:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 1 of 1
Job No Sheet No Rev
1
Part
Software licensed to HP
Job Title Ref
By Date18-Feb-19 Chd
Reaction Summary
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kNm) (kNm) (kNm)
Max FX 13 23:GENERATED UBC TABLE1
3.03 1720.10 0.21 0.10 -0.00 -1.89
Min FX 13 11:GENERATED UBC-3.03
TABLE1 5 38.96 -0.21 -0.10 0.00 1.89
Max FY 13 7:GENERATED UBC TABLE1
-0.00 1 45.28 -0.01 -0.00 -0.00 0.00
Min FY 9 22:GENERATED UBC-0.26
TABLE1 16 7.52 -2.36 -1.76 -0.01 0.08
Max FZ 10 24:GENERATED UBC TABLE1
0.53 1819.23 2.96 1.93 -0.00 -0.21
Min FZ 10 22:GENERATED UBC-0.52
TABLE1 1620.35 -2.96 -1.94 0.00 0.20
Max MX 13 24:GENERATED UBC-0.54
TABLE1 1819.25 2.10 2.24 -0.01 0.54
Min MX 13 12:GENERATED UBC TABLE1
0.53 6 39.81 -2.11 -2.24 0.01 -0.54
Max MY 12 22:GENERATED UBC TABLE1
0.01 1621.35 -2.36 -2.04 0.07 -0.28
Min MY 12 24:GENERATED UBC-0.00
TABLE1 1818.25 2.34 2.04 -0.07 0.28
Max MZ 13 11:GENERATED UBC-3.03
TABLE1 5 38.96 -0.21 -0.10 0.00 1.89
Min MZ 13 23:GENERATED UBC TABLE1
3.03 1720.10 0.21 0.10 -0.00 -1.89
Print Time/Date: 19/02/2019 08:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 1 of 1
Job No Sheet No Rev
1
Part
Software licensed to HP
Job Title Ref
By Date18-Feb-19 Chd
Reaction Summary
Horizontal Vertical Horizontal Moment
Node L/C FX FY FZ MX MY MZ
(kN) (kN) (kN) (kNm) (kNm) (kNm)
Max FX 18 23:GENERATED UBC TABLE1
1.29 17 0.00 -0.08 0.00 0.00 0.00
Min FX 18 21:GENERATED UBC-1.29
TABLE1 15 0.00 0.08 0.00 0.00 0.00
Max FY 17 7:GENERATED UBC TABLE1
-0.00 1 0.00 -0.00 0.00 0.00 0.00
Min FY 17 7:GENERATED UBC TABLE1
-0.00 1 0.00 -0.00 0.00 0.00 0.00
Max FZ 21 24:GENERATED UBC-0.05
TABLE1 18 0.00 1.42 0.00 0.00 0.00
Min FZ 21 12:GENERATED UBC TABLE1
0.05 6 0.00 -1.42 0.00 0.00 0.00
Max MX 17 7:GENERATED UBC TABLE1
-0.00 1 0.00 -0.00 0.00 0.00 0.00
Min MX 17 7:GENERATED UBC TABLE1
-0.00 1 0.00 -0.00 0.00 0.00 0.00
Max MY 17 7:GENERATED UBC TABLE1
-0.00 1 0.00 -0.00 0.00 0.00 0.00
Min MY 17 7:GENERATED UBC TABLE1
-0.00 1 0.00 -0.00 0.00 0.00 0.00
Max MZ 17 7:GENERATED UBC TABLE1
-0.00 1 0.00 -0.00 0.00 0.00 0.00
Min MZ 17 7:GENERATED UBC TABLE1
-0.00 1 0.00 -0.00 0.00 0.00 0.00
Print Time/Date: 19/02/2019 08:53 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 1 of 1
Job No Sheet No Rev
1
Part
Software licensed to HP
Job Title Ref
By Date18-Feb-19 Chd
Print Time/Date: 19/02/2019 08:53 STAAD.Pro V8i (SELECTseries 6) 20.07.11.33 Print Run 1 of 1
Tuesday, February 19, 2019, 08:53 AM
PAGE NO. 1
****************************************************
* *
* STAAD.Pro V8i SELECTseries6 *
* Version 20.07.11.33 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= FEB 18, 2019 *
* Time= 14: 8: 0 *
* *
* USER ID: HP *
****************************************************
1. STAAD SPACE
INPUT FILE: C:\Users\Sudheesh Kumar\Desktop\usw\window steel framing\staad\WINDOW STEEL RV 01.STD
2. START JOB INFORMATION
3. ENGINEER DATE 18-FEB-19
4. END JOB INFORMATION
5. INPUT WIDTH 79
6. UNIT METER KN
7. JOINT COORDINATES
8. 9 -5.3 0 -6.49041E-016; 10 -4.89656 0 2.02822; 11 -3.74767 0 3.74767
9. 12 -2.02822 0 4.89656; 13 -9.73562E-016 0 5.3; 14 2.20822 0 5.3
10. 17 -5.3 6.2 -6.49041E-016; 18 -4.89656 6.2 2.02822; 19 -3.74767 6.2 3.74767
11. 20 -2.02822 6.2 4.89656; 21 -9.73562E-016 6.2 5.3; 22 2.20822 6.2 5.3
12. 23 -5.3 1.1 -6.49041E-016; 24 -5.3 1.78 -6.49041E-016; 25 -4.89656 1.1 2.02822
13. 26 -4.89656 1.78 2.02822; 27 -3.74767 1.1 3.74767; 28 -3.74767 1.78 3.74767
14. 29 -2.02822 1.1 4.89656; 30 -2.02822 1.78 4.89656; 31 -9.73562E-016 1.1 5.3
15. 32 -9.73562E-016 1.78 5.3; 35 2.20822 1.1 5.3; 36 2.21 1.78 5.3
16. MEMBER INCIDENCES
17. 17 9 23; 18 10 25; 19 11 27; 20 12 29; 21 13 31; 22 14 35; 23 23 24; 24 24 17
18. 25 25 26; 26 26 18; 27 27 28; 28 28 19; 29 29 30; 30 30 20; 31 31 32; 32 32 21
19. 33 35 36; 34 36 22; 35 23 25; 36 25 27; 37 27 29; 38 29 31; 40 24 26; 41 26 28
20. 42 28 30; 43 30 32; 44 32 36; 45 31 35
21. DEFINE MATERIAL START
22. ISOTROPIC STEEL
23. E 2.05E+008
24. POISSON 0.3
25. DENSITY 76.8195
26. ALPHA 1.2E-005
27. DAMP 0.03
28. TYPE STEEL
29. STRENGTH FY 253200 FU 407800 RY 1.5 RT 1.2
30. END DEFINE MATERIAL
31. MEMBER PROPERTY BRITISH
32. 35 TO 38 40 TO 45 TABLE ST TUB80805.0
33. 17 TO 34 TABLE ST TUB80805.0
34. CONSTANTS
35. BETA 10 MEMB 17 23 24
36. BETA 24 MEMB 18 25 26
37. BETA 45 MEMB 19 27 28
38. BETA 340 MEMB 20 29 30
P R O B L E M S T A T I S T I C S
-----------------------------------
***********************************************************
* *
* X DIRECTION : Ta = 0.335 Tb = 0.237 Tuser = 0.000 *
* C = 2.7500, LOAD FACTOR = 1.000 *
* UBC TYPE = 94 *
* UBC FACTOR V = 0.0485 x 111.72 = 5.42 KN *
* *
***********************************************************
56. CHANGE
57. *
58. LOAD 5 LOADTYPE SEISMIC TITLE SEISMIC LOAD X-DIRECTION
59. UBC LOAD Z 1
60. PERFORM ANALYSIS
***********************************************************
* *
* Z DIRECTION : Ta = 0.335 Tb = 0.263 Tuser = 0.000 *
* C = 2.7500, LOAD FACTOR = 1.000 *
* UBC TYPE = 94 *
* UBC FACTOR V = 0.0485 x 111.72 = 5.42 KN *
* *
***********************************************************
61. CHANGE
62. *
63. LOAD 1 LOADTYPE DEAD TITLE LOAD CASE 1
64. SELFWEIGHT Y -1
65. MEMBER LOAD
66. 17 23 24 UNI GY -1.68
67. 18 TO 20 25 TO 30 UNI GY -3.36
68. 21 31 32 UNI GY -3.44
69. 22 33 34 UNI GY -1.76
70. LOAD 2 LOADTYPE WIND TITLE LOAD CASE 2
71. MEMBER LOAD
72. 17 23 24 UNI GX 0.25
73. 18 TO 20 25 TO 30 UNI GX 0.5
74. 21 31 32 UNI GX 0.52
75. 22 33 34 UNI GX 0.26
76. LOAD 3 LOADTYPE WIND TITLE LOAD CASE 3
77. MEMBER LOAD
78. 17 23 24 UNI GZ 0.25
79. 18 TO 20 25 TO 30 UNI GZ 0.5
80. 21 31 32 UNI GZ 0.52
81. 22 33 34 UNI GZ 0.26
82. *
83. LOAD 6 LOADTYPE DEAD TITLE LOAD CASE 6
84. MEMBER LOAD
85. 17 23 24 UNI GY -0.78
86. 18 TO 20 25 TO 30 UNI GY -1.55
87. 21 31 32 UNI GY -1.59
88. 22 33 34 UNI GY -0.81
89. ***
90. LOAD COMB 7 GENERATED UBC TABLE1 1
91. 1 1.4 6 1.4
92. LOAD COMB 8 GENERATED UBC TABLE1 2
93. 1 1.2 6 1.2
136. *
137. PARAMETER 1
138. CODE BS5950
139. CHECK CODE ALL
140. FINISH
************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://selectservices.bentley.com/en-US/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) 1997-2015 Bentley Systems, Inc.
* http://www.bentley.com *
************************************************************
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200-A + HIT-V (5.8) M12
Effective embedment depth: hef,opti = 70 mm (hef,limit = 170 mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 28-07-2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: without clamping (anchor); restraint level (baseplate): 2.00; eb = 10 mm; t = 16 mm
Hilti Grout: , multipurpose, fc,Grout = 30.00 N/mm2
Baseplate: lx x ly x t = 150 mm x 200 mm x 16 mm; (Recommended plate thickness: not calculated
Profile: Square hollow; (L x W x T) = 80 mm x 80 mm x 5 mm
Base material: cracked concrete, C25/30, fc,cube = 30.00 N/mm2; h = 200 mm, Temp. short/long: 40/20 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
R
- The anchor calculation is based on a rigid baseplate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200-A + HIT-V (5.8) M12
Profile: Square hollow; 80 x 80 x 5 mm Installation torque: 0.040 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 14 mm
Plate thickness (input): 16 mm Hole depth in the base material: 70 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
75 75
30
3 4
100
140
x
100
1 2
30
35 80 35
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200-A + HIT-V (5.8) M12
Effective embedment depth: hef,opti = 70 mm (hef,limit = 170 mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 28-07-2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: without clamping (anchor); restraint level (baseplate): 2.00; eb = 10 mm; t = 16 mm
Hilti Grout: , multipurpose, fc,Grout = 30.00 N/mm2
Baseplate: lx x ly x t = 150 mm x 250 mm x 16 mm; (Recommended plate thickness: not calculated
Profile: Double flat bar; (L x W x T) = 150 mm x 90 mm x 16 mm
Base material: cracked concrete, C25/30, fc,cube = 30.00 N/mm2; h = 200 mm, Temp. short/long: 40/20 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
R
- The anchor calculation is based on a rigid baseplate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200-A + HIT-V (5.8) M12
Profile: Double flat bar; 150 x 90 x 16 mm Installation torque: 0.040 kNm
Hole diameter in the fixture: df = 14 mm Hole diameter in the base material: 14 mm
Plate thickness (input): 16 mm Hole depth in the base material: 70 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 100 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
75 75
30
3 4
125
190
x
125
1 2
30
30 90 30
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ch Profis Anchor 2.8.0
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 19-02-2019
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
BOLT AND WELD CAPACITIES - To BS5950 - Pt1: 2000
General Grade Pretensioned HSFG Bolts Higher Grade Pretensioned HSFG Bolts
Non-Slip under Factored Load Non-Slip under Factored Load
for bolts in standard clearance holes for bolts in standard clearance holes
Min. Shank Tension Slip Min. Shank Tension Slip
Bolt Tension Capacity Resistance Bolt Tension Capacity Resistance
Size (kN) (kN) µ = 0.4 Size (kN) (kN) µ = 0.4
PO 0.9Po PsL PO 0.9Po PsL
M12 49.4 44.5 17.8 ~ ~ ~ ~
M16 92.1 82.9 33.2 M16 103.9 93.5 37.4
M20 144 130 51.8 M20 161.8 146 58.2
M24 207 186 74.5 M24 233.4 210 84.0
M30 286 257 103 M30 370.0 333 133
M36 418 376 151 ~ ~ ~ ~