KFS-7118 Firmware Maintenance Release - FSR - FW1402 - PDF
KFS-7118 Firmware Maintenance Release - FSR - FW1402 - PDF
Revision: A
Overhead Medium Voltage Systems Date: 17.05.13
1 Release Scope
This release notification covers the following:
Fusesaver Firmware: FW1402 (available from https://sosdmc.siemens.cloud)
RELEASE CLASSIFICATON: MAINTENANCE
2 Coverage
Region: WORLD-WIDE
Customers: ALL
Applicable Fusesaver Types: All (3AD82**, 3AD84**)
3 Release Description
The Fusesaver firmware version covered in this release (FW1402) primarily resolves bug
fixes, listed in Section 4 below.
For convenience, we have indicated all the changes/fixes implemented over the last year.
Siemens recommends updating all devices to the latest firmware to ensure the most
reliable/consistent performance.
Unrestricted Page 1 of 9
Form: KMS-3098
Revision: A
Overhead Medium Voltage Systems Date: 17.05.13
Description:
The pseudo-three phase trip and synchronous reclose function has a vulnerability in how it
handles corrupted message rejection which may result in unexpected operations.
We have determined that this vulnerability may affect sites which:
· Are a multi-phase installation,
And
· Have open-close-open (OCO) functionality enabled
And
· Have Fusesaver Firmware older than FW1401
Severity: High
Although this bug is not considered a safety risk, upon occurrence it is a major functionality
non-conformity which may greatly impact customer and has the potential to damage
equipment.
Resolution:
To resolve this issue, preventing the unintended trip-close loop, the latest firmware must be
installed on the Fusesaver and Communications Module:
· Fusesaver => FW1402 or later
· Communication Module => FW1601 or later
Unrestricted Page 2 of 9
Form: KMS-3098
Revision: A
Overhead Medium Voltage Systems Date: 17.05.13
Description:
We have found that prior Firmware (FW1401 and older) has a vulnerability where the save
state data stored in the Fusesaver may (on rare occasions) become corrupted during the
following scenarios:
· Updating the firmware (Comms Module or Fusesaver) when the Fusesaver has no
line current.
· Removing and Attaching the Comms module.
The symptoms of this bug include:
· Resetting the Operations Count to zero.
· Incorrectly setting the VI expired flag (Resulting in VI Life showing as 0%)
· Unintentionally setting a Remote Protection Mode.
Severity: Medium
This vulnerability is considered a medium severity, as it is easy to detect and can be
resolved by reconfiguring or running a maintenance utility.
Resolution:
To resolve this issue, preventing save-state corruption, the latest firmware must be installed
on the Fusesaver and Communications Module:
· Fusesaver => FW1402 or later
· Communication Module => FW1601 or later
Unrestricted Page 3 of 9
Form: KMS-3098
Revision: A
Overhead Medium Voltage Systems Date: 17.05.13
Description:
We have found that Firmware V353 and older will log a protection change event (toggles
protection mode to and back from the de-energised line mode) during the battery test which
is programmed to run monthly. These events have caused confusion in analysing Fusesaver
Event and during remote SCADA monitoring.
Severity: Low
This issue is considered very low severity, as it does not affect the functionality of the device
but may cause some confusion when analysing events.
Resolution:
To resolve this issue, update the Fusesaver and Comms module to the latest firmware:
· Fusesaver => FW1402 or later
· Communication Module => FW1601 or later
Unrestricted Page 4 of 9
Form: KMS-3098
Revision: A
Overhead Medium Voltage Systems Date: 17.05.13
Notice
If the rechargeable communications module is fitted to a
Fusesaver with older firmware (≤V353), then the LED will
continuously blink rapidly to notify the user that the
Fusesaver firmware requires updating.
Unrestricted Page 5 of 9
Form: KMS-3098
Revision: A
Overhead Medium Voltage Systems Date: 17.05.13
The time current accuracy of the application of the instantaneous multiplier has been
improved.
The time current curve accuracy of the inverse curve for Fusesaver configured with partner
fuse has been improved.
Unrestricted Page 6 of 9
Form: KMS-3098
Revision: A
Overhead Medium Voltage Systems Date: 17.05.13
For example;
Unrestricted Page 7 of 9
Form: KMS-3098
Revision: A
Overhead Medium Voltage Systems Date: 17.05.13
6 Compatibility
The following compatibility issues are valid:
· The Fusesaver firmware version in this release is compatible with all earlier versions
of the Fusesaver hardware. Some limitations of the newly added functionality may
occur with older hardware platforms.
· The Fusesaver firmware in this release is only compatible with Communication
Module firmware versions FW1601 or later.
· The Fusesaver firmware version in this release is not compatible with versions of
Siemens Connect prior to V4.0.0.5
· The Fusesaver firmware version in this release is not compatible with versions of
RCU firmware prior to V133
· The Fusesaver firmware version in this release is compatible with all previously
created policy files.
Unrestricted Page 8 of 9
Form: KMS-3098
Revision: A
Overhead Medium Voltage Systems Date: 17.05.13
7 Installation
· Download the firmware installers and documentation from the Siemens outdoor
systems data management cloud at https://sosdmc.siemens.cloud
· Follow the Firmware Installation Instructions: KMS-0018
8 Contact
Please contact your local Siemens office for support.
The global headquarters for Overhead Medium Voltage Solutions can be contacted via this
email address:
Fusesaver.au@siemens.com