EES Ver. 6.220: #955

STATE POINTS
TEMPERATURE PRESSURE ENTHALPY DENSITY
STATE POINT 3
Additional information
[°C] [kPa] [kJ/kg] [kg/m ]

1 -5.0 200.7 245.1 9.9 Pressure ratio (p2 / p1 ) : 5.067

2 56.8 1016.9 285.8 45.2 T2,IS : 51.3 [°C]


3 56.8 1016.9 285.8 45.2 T2,IS is the temperature of the
4 38.0 1016.9 102.2 1155.9 discharge gas assuming reversible
and adiabatic compression
5 38.0 1016.9 102.2 1155.9
6 -10.0 200.7 102.2 ----- T2,W : 56.8 [°C]
T2,W is the temperature of the
7 -5.0 200.7 245.1 9.9
discharge gas assuming real and
8 -5.0 200.7 245.1 9.9 adiabatic compression

Calculate Print Help Cycle Spec. Auxiliary COP : 3.513 COP* :3.513