Professional Documents
Culture Documents
EC500 Handbook Issa1 PDF
EC500 Handbook Issa1 PDF
Operation Handbook
Issue A1
Eaton Corporation
Telecommunications Power Solutions
dcpower.eaton.com
DCinfo@eaton.com
EC500 Controller Handbook
The product discussed in this literature is subject to terms and conditions outlined in Eaton selling policies. The sole source
governing the rights and remedies of any purchaser of this equipment is the relevant Eaton selling policy.
No warranties, express or implied, including warranties of fitness for a particular purpose or merchantability, or warranties arising
from course of dealing or usage of trade, are made regarding the information, recommendations and descriptions contained
herein.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise
for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of
use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities,
or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and
descriptions contained herein.
The information contained in this literature is subject to change without notice.
Subject to the right to use its equipment, Eaton Corporation does not convey any right, title or interest in its intellectual property,
including, without limitation, its patents, copyrights and know-how.
No part of this literature may be reproduced or transmitted in any form, by any means or for any purpose other than the
Purchaser’s personal use, without the express written permission of Eaton Corporation.
Eaton®, Matrix, Powerware®, IntergyTM, CellSureTM, SiteSureTM, PowerManagerIITM and DCToolsTM are trade names, trademarks,
and/or service marks of Eaton Corporation or its subsidiaries and affiliates. Unless otherwise noted, brands, product names,
trademarks or registered trademarks are the property of their respective holders.
CONTENTS
About This Guide.............................................................................................................................. 6
Scope ................................................................................................................................................... 6
Audience ............................................................................................................................................. 6
Reporting Problem With This Guide ................................................................................................... 6
For Further Information and Technical Assistance ............................................................................. 6
Third Party Software ........................................................................................................................... 6
General Description ......................................................................................................................... 7
Overview ............................................................................................................................................. 7
EC500 Controller ................................................................................................................................. 7
DC Interface and IO Board .................................................................................................................. 8
IOB-6V3C ......................................................................................................................................... 8
Potential Free Input / Output Board................................................................................................... 9
Connections ...................................................................................................................................... 10
Board Options ................................................................................................................................... 11
EC500 Operation ............................................................................................................................ 12
Overview ........................................................................................................................................... 12
Starting the EC500 ............................................................................................................................ 12
Home Screen ................................................................................................................................. 13
EC500 Operation Using Keypad and Screen ..................................................................................... 13
Navigation Keys ............................................................................................................................. 13
Main Menu Navigation ................................................................................................................. 14
Changing a Configuration Setting using the Keypad ..................................................................... 14
Keypad Access Security ................................................................................................................. 14
Display Settings ............................................................................................................................. 15
Display Time-out ........................................................................................................................... 15
Alarm Indicators ............................................................................................................................ 15
EC500 Operation Using a PC/Laptop ................................................................................................ 16
EC500 Identity Information............................................................................................................... 17
Identity Information...................................................................................................................... 17
EC500 Internal Clock ......................................................................................................................... 18
Time Synchronization.................................................................................................................... 19
Language Options ............................................................................................................................. 19
Language Selection ....................................................................................................................... 20
EC500 Firmware Upgrade ................................................................................................................. 20
Software Downgrade .................................................................................................................... 20
Configuration File .............................................................................................................................. 21
System Operation .......................................................................................................................... 22
Overview ........................................................................................................................................... 22
Battery and Voltage Control ............................................................................................................. 22
VRLA Battery Charge Profile ......................................................................................................... 23
Battery Current Limit .................................................................................................................... 24
Multiple Battery Banks.................................................................................................................. 24
Battery Temperature Compensation ............................................................................................ 26
Equalize ......................................................................................................................................... 27
Battery Test ................................................................................................................................... 29
Battery Reverse Detection ............................................................................................................ 30
Manual Charge Mode ................................................................................................................... 30
Solar Charger Power Share ........................................................................................................... 31
Rectifiers ........................................................................................................................................... 34
Rectifier Registration .................................................................................................................... 36
Identify a Rectifier ......................................................................................................................... 37
Force Share Reset ......................................................................................................................... 37
Rectifier Sleep Mode..................................................................................................................... 38
Economy Mode ............................................................................................................................. 38
Rectifier Alarms ............................................................................................................................. 41
Low Voltage Disconnect (LVD) .......................................................................................................... 42
Bus Monitoring ............................................................................................................................. 42
Battery LVD ................................................................................................................................... 43
Load LVD ....................................................................................................................................... 44
Typical LVD Arrangements ............................................................................................................ 44
LVD Operation ............................................................................................................................... 44
DCDB Alarms ................................................................................................................................. 45
Alarms ............................................................................................................................................... 45
Type of Alarms .............................................................................................................................. 45
Active Alarm Indications ............................................................................................................... 46
Alarm Change Indication ............................................................................................................... 47
Alarm Grouping ............................................................................................................................. 47
System Alarms............................................................................................................................... 47
Potential Free Inputs / DI Alarms .................................................................................................. 48
Analog Alarms ............................................................................................................................... 49
Smart Alarms................................................................................................................................. 51
Potential Free Outputs.................................................................................................................. 52
Common Alarm Parameters ......................................................................................................... 53
Generator Control ............................................................................................................................. 53
Input / Output (I/O) .......................................................................................................................... 55
Identify an I/O Board .................................................................................................................... 55
Analog System Values ................................................................................................................... 55
Analog Inputs ................................................................................................................................ 56
System States ................................................................................................................................ 58
Digital Inputs ................................................................................................................................. 58
Digital Outputs .............................................................................................................................. 59
Energy Metering ............................................................................................................................... 60
Information ................................................................................................................................... 60
Configuration ................................................................................................................................ 61
Data Logging...................................................................................................................................... 62
Event Log ....................................................................................................................................... 62
Data Log ........................................................................................................................................ 63
Energy Log ..................................................................................................................................... 63
Run Hours Log ............................................................................................................................... 64
Status Logs .................................................................................................................................... 64
Change Logs .................................................................................................................................. 65
Performance logs .......................................................................................................................... 65
System Configuration..................................................................................................................... 67
Overview ........................................................................................................................................... 67
System Info ....................................................................................................................................... 67
Battery Configuration ....................................................................................................................... 68
Battery Mid-Point Configuration ...................................................................................................... 70
Load Configuration............................................................................................................................ 72
Current Sensing ................................................................................................................................. 72
See EC500 Identity Information on page 17 to determine the version of the embedded
software.
AUDIENCE
Please use this email address to report any problem you find in this guide:
dcinfo@eaton.com
This product includes an open source SSL library “mbed TLS” licensed by ARM Limited. Source code of
“mbed TLS” can be downloaded from https://tls.mbed.org/.
GENERAL DESCRIPTION
OVERVIEW
Topic Page
EC500 Controller 7
Connections 10
EC500 CONTROLLER
The EC500 Controller is an advanced control and monitoring solution which provides a full suite of
communications options, including built-in Ethernet interface, Web server, Modbus, and SNMP agents.
Alarm notifications may be by Email, SNMP traps, SMS text messaging or relay contact closures. Local
notifications are given on Display, Buzzer and LEDs.
1 7
2 5 9 6 10
8 11
3 4
ITEM NOMENCLATURE
1 Power LED/normal conditions
2 Major Alarm
3 Info Alarm
4 Display Screen
5 Left Key/ Scroll/Back
6 Right Key/Scroll
7 Up Key/Scroll/Parameter Value Change/ Latch reset
8 Down Key/Scroll/Parameter Value Change
ITEM NOMENCLATURE
9 Enter Key
10 Ethernet Port
11 USB Port
EC500 Rear View
3 4
5 1 2
ITEM NOMENCLATURE
1 CAN Port 1 + Power
The EC500 is supplied pre-configured with either a default configuration file, or with one factory customized
for a particular application. Some configuration file changes can be made with the keypad, or all settings can
be changed via a PC connected to the EC500 through a network. For essential configurations see System
Configurations on page 67.
For connector pin-outs see details on page100. See Troubleshooting on page Error! Bookmark not defined. for
details of EC500 alarm LEDs.
The DC Interface & IO provides the Analogue interfaces, I/O interfaces and connections for system bus.
The DC Interface board includes a range of sense inputs for dc power system control and monitoring. It also
allows real time data collection from building services and other external devices, relay outputs for alarm
signals or control of external devices and drives for DC Contactors.
DCIO board provide Shunt based current sensing. All voltage and current measurements are in reference to
Bus Common (-48V DC).
IOB-6V3C
• Sensors: Current – 3, Bus Voltage – 1, Battery/Mid-point – 5, Temperature – 2
This board provides 8 on board relays for alarm or other control functions.
For input and output specifications see details on page 94. For connector pin-outs see details
on page 102.
A variant of DCIO provides only 8 PFC Inputs and 8 PFC Outputs. This board can be used where additional
digital monitoring inputs and additional potential free contacts are required, but analogue inputs are not
required. The board communicates with the controller on the system CAN bus. For connector pin outs see
DCIF Connector Pin-outs on Page 102.
CONNECTIONS
The following diagram shows a system architecture using EC500 and its peripherals.
The following wiring diagram shows the connections between the EC500, the DC Interface board, the other dc
power system components and external devices for a generic power plant. Please refer to your system wiring
diagram for any system specific changes.
For connector pin-outs see details on page 100. For input and output specifications see details
on page 100.
BOARD OPTIONS
The EC500 system includes a number of options for controller and input / output boards. Contact Eaton for
any new or currently available options.
EC500 OPERATION
OVERVIEW
Topic Page
Language Options 19
When dc power is applied to the EC500 (via the connector CAN-1 / CAN-2 / RS485-L / RS485-U on rear panel)
the controller boots up and start-up sequence begins.
At power up, Boot loader Display system values, alarm Option selection displays
loads any new firmware and status, latest alarm and date / Main Menu. See
then jumps to application. time. Colour of particular navigation on page 13. If Logon is
Controller initializes block shows alarm status of required see Keypad Access
hardware, loads system that block. Security on page 14.
settings and starts operation.
CAN-2 and RS485-U are not part of standard offering and must be purchased as an option
(EC500-01)
HOME SCREEN
The Home screen displays important system parameter values and system block status. Block nomenclature
and colour relations are as given below.
Home Screen or default screen parameters are read only and are used to show important system parameters
such as Date and Time, Last event, AC phase (RYB) voltage, Rectifier Current, Battery current & voltage, Load
current and bus voltage.
NAVIGATION KEYS
EC500 provides a Joystick for navigation. For Navigation towards Right push the joystick Rightwards, for Left
push leftwards and similarly, for Up and Down directions. To select an option or Enter, press the joystick
towards the centre.
User can navigate through all enabled screen using the joystick. Joystick functions change according to context.
Important functions are given below.
To select a sub menu Select using Up / Down and then Enter. On Main menu use
Left / Right and then enter
Edit a parameter Up / Down to change value, Enter to select current displayed value
Increase / decrease number of characters When at last location of string, Right press will add one character
location. When at last display location, Left press will reduce string
length.
Fast Scroll push and hold the joystick in the respective direction
To navigate to Main Menu, from Home screen navigate to the Main Menu icon and press enter.
The following menu items will appear: System Status, Logs, Settings, System Configuration, Maintenance and
Accessories. These can be navigated using left and right navigation keys. To select a particular menu use the
Enter Key. Sub menu items under the selected menu will appear.
➢ To Login
• Select the system parameter that is to be modified.
• If user is already logged in, then the settings can be directly changed, if he/she has required
access rights else a login window will popup.
• Enter the access PIN.
• To enter PIN, move joystick up / down to scroll through numbers 0 -9. To enter next digit
move joystick to right and then up / down to select next digit.
• Selected digit will be displayed for a short duration and then will be hidden using a * symbol.
• Once all required digits are selected, push joystick to Enter.
• Cursor moves to Login button, again push joystick to Enter.
• If PIN is incorrect, user is taken back to Login window.
User will be auto logged out 5 minutes after last parameter edit.
For example, if a user wants to change Battery Capacity then go to Home Main Menu Settings
Battery Settings General Settings Battery Capacity and press Enter. If User is not already logged in, a
pop-up window for PIN entry will appear.
Login
Enter Enter
Window
Enter PIN to
Login
Enter Enter
DISPLAY SETTINGS
In Display Settings, a user can set brightness level.
Adjust display intensity according to ambient light, else you may not be able to see the
display values
DISPLAY TIME-OUT
If there is no keypad activity for 60 seconds, the display will jump back to the Home screen.
When the display is at Home screen and there is no user activity for 60 seconds, the display intensity
automatically reduces to half (minimum 10%). If there is no activity for further 180 seconds then the intensity
is reduced to 10%. Display intensity will increase automatically to set value when any key is pressed or any
event occurs.
ALARM INDICATORS
Active alarms are displayed at the bottom left side of the Display. Alarms are categorised as Critical, Major and
Minor. If a Critical or Major Alarm occurs than Status LEDs will glow in Red colour and if a Minor alarm occurs
than Status LEDs glow in Yellow colour.
Visual Indicators
Audio Indicators
Whenever any alarm is present, the Buzzer will beep every 2 seconds
The audible indicator will restart at the next active alarm or alert message.
➢ To enable / disable the audible alarm indicator
Either:
• Use the keypad to go to: Home Main Menu Settings System Settings Buzzer
• Set Buzzer status to Disable and save.
Or:
• On Web page go to: Home Settings System Settings Buzzer Status
• Set Buzzer status to Disable and save.
For IPv4:
Home Main Menu Settings Communication Settings Ethernet IPv6 Link Local / IPv6 Address
Refer section Ethernet Communication Set-up on page 79 for setting static IP address or
enabling DHCP client.
Refer section Communication via Web Browser on page 82 for establishing communication
using a Web browser.
Open any standard Web Browser, enter IP address of the controller and press enter. Browser will connect to
the controller and a Login page will be presented. Enter your credentials and you will be presented with EC500
data.
By default, the EC500 Controller comes enabled for HTTPS communication. You will need to add "https://"
before the IP Address.
Recommended web browsers: Microsoft Internet Explorer 10 or later, Mozilla Firefox 3.0 or
later, Chrome V63 or later.
It is recommended to keep web communication mode to HTTPS to ensure a secure network.
EC500 IDENTITY INFORMATION
IDENTITY INFORMATION
Parameter Description Where to find:
Following additional information can be stored to help system and site location.
Site Name User can store a 12 character Site Name where the Display:
system is installed.
Site ID User can store Site ID where the system is installed. Home > Menu > Settings >
Site ID can be allocated by monitoring servers for System Settings
network wide management. Site ID can be an
alphanumeric string with length 12. Web:
Home > Settings > System
System Part User can store System part number in which this Settings
Number controller has been used. This is to help inventory
management.
System Serial User can store Serial number of the system in which
Number this controller has been used. This is to help
inventory management.
The EC500 has a battery-backed clock for time stamping of log entries and Control Processes.
The time and date are factory set. They can also be set manually using a web browser or can be synchronized
to an SNTP reference time server.
Or:
TIME SYNCHRONIZATION
If required, the EC500 time can be synchronized to a reference time server using SNTP protocol (EC500 must
have access to the server).
For more information on SNTP, including a list of public SNTP servers, visit www.ntp.org
http://www.ntp.org.
Ensure that your network has an internal SNTP server or allows access to an external server.
It may be necessary to configure access through your network's firewall.
LANGUAGE OPTIONS
The EC500 Controller language default is English and is inbuilt. Text on the LCD can be shown in other
languages by loading the appropriate Translation File (EC500-xx-Vyyy.lng) into the EC500. Only Menu item
translation is supported. User entered strings and alarm strings are shown in English language only. Only one
language file can be loaded in addition to English.
The controller validates the language file for any corruption at power on / reboot. In case of any corruption the
language file is discarded and controller returns to English language, if another language was selected.
The existing language file will be normally supported in case of a firmware upgrade. In case translation of new
messages is not available, particular messages will be shown in English. In rare instances a firmware upgrade
may require a fresh language file compatible with this firmware.
Contact Eaton for available Translation Files. Current Firmware version does not support language translation
on Web pages.
LANGUAGE SELECTION
EC500 can hold one language file (in addition to inbuilt support for English) and it can be selected from the
Display or Web page.
• On the EC500 keypad go to: Home Main Menu Settings System Settings Set
Language
• Select Language (English or second loaded language).
• Go back to Home screen. Controller will start showing messages in selected language.
Or:
• Connect to the EC500 via a web browser (See Ethernet Communications on page 79).
• Go to Settings System Settings.
• Click on Edit button to enable editing
• Click Set Language field to select the Language from drop down.
• Click Save button. EC500 language will change to selected language.
If required, the embedded software (firmware) in the EC500 can be upgraded from a PC/Laptop via a web
browser.
Some configuration settings may be lost when the firmware in the EC500 is upgraded. Refer to the
new firmware Product Release Notes for details of specific configuration settings that may be affected. Check
the configuration after upgrading. Backup any changes to the configuration.
SOFTWARE DOWNGRADE
Some firmware may not be downgraded. Check with Eaton before downgrading the EC500 to an earlier
firmware version. This may not be possible, or downgrade with the wrong file may cause the EC500 to stop
operating, and require factory repair. Eaton may be able to supply a special downgrade file that will work
correctly.
It is likely that configuration settings will be lost if the firmware in the EC500 is downgraded. If a firmware
downgrade is required, trial the downgrade and check the configuration before implementing it at a site.
CONFIGURATION FILE
Configuration file for EC500 can be uploaded to Controller through Web Page.
SYSTEM OPERATION
OVERVIEW
Topic Page
Battery and Voltage Control 22
Rectifiers 34
Low Voltage Disconnect (LVD) 42
Alarms 45
Generator Control 53
Input / Output (I/O) 55
Energy Metering 60
Data Logging 62
The output voltage of the rectifiers is controlled by a number of control processes. The EC500 provides CC/CV
charging and can achieve typical three stage charging of a VRLA battery i.e. constant-current charge, topping charge
and float. The EC500 can also achieve CC/CV two stage charging for a Li-ION battery. Note that Li-Ion battery typically
does not require Float mode. The following diagram shows the various control processes, measured values and
operating values that determine the rectifier output voltage.
If ac fails, then any active control process stops. No control process can start until the ac
supply is restored.
EC500 Supports both VRLA and Li-ION batteries. Monitoring & Configuration for both these batteries is
explained separately.
Configuration
Parameter Description Where to find:
Battery Capacity Set to the rated 10 hour capacity of the installed Display:
battery strings. Set it carefully as some parameters Menu>Settings>Battery
are referenced and dependent upon this value. Settings>General
Settings>Battery Capacity
Web:
Home>Settings>Battery
Settings>General
Settings>Battery Capacity
Battery Current BCL logic maintains the battery charge current Display:
Limit (Normal) below this value, which is a percentage of the Menu>Settings>Battery
installed C10 Battery Capacity. Settings>Charge
Battery Current The Battery Current Limit setting when Engine Run Profile>CC/CV Mode
Limit (Alternate) State is active. Alternate Current Limit is effective Web:
only if a PFC Input is mapped to DG Sense Function. Home>Settings>Battery
If no PFC is mapped to this function, this limit is not Settings>Charge
used. When mapped and if PFC input is Active, Profile>CC/CV Mode
Alternate Current Limit is applied.
Float Voltage Set to the voltage required to maintain optimum
charge for battery at reference ambient
temperature.
Charge Voltage Battery charge voltage as per battery manufacturer
specifications. Charge voltage is typically 55.2V for
48V VRLA battery.
Float to Charge Percentage of Battery Capacity.
Threshold When battery charge current increases above this
threshold, the controller will put the battery in
Charge mode by setting target voltage equal to
“Charge Voltage”. This is typically set to 3% and
should be less than “Charge to Float Threshold”.
Charge to Float Percentage of Battery Capacity.
Threshold When battery charge current falls below this
threshold, the controller will put the battery in Float
mode by setting target voltage equal to “Float
Voltage”. This is typically set to 5% and should be
greater than “Float to Charge Threshold”
Max. Charge If this function is Enabled and Battery temperature
Temperature reaches the Set temperature value, the controller
will abort the battery charging and maintain the
float voltage.
Max. Charge If this function is Enabled and Battery Charging time
Duration reaches the Set time value, the controller will abort
the battery charging and maintain the float voltage.
Monitoring
The following information is available about the current state of battery charging.
Charge State Indicates current charging state (Charge / Float / Idle) Home Screen (above date
for the battery. and time)
Battery Current Battery charging / discharging current. A discharge Home Screen (Adjacent to
current is indicated by a –ve sign. Battery Icon)
Two current limit values can be set (both are percentage of the C10 rating of the battery):
When the rectifier is switched ON, Rectifier voltage rises to below battery voltage and then increases to
achieve target voltage by maintaining set battery current limit. If alternate battery current limit is set and
engine is running, the controller will maintain alternate battery current limit while trying to achieve target
voltage.
Alternate Current Limit applies when the EC500 determines that an ac standby generator is
running. EC500 uses a Potential Free Input to determine If Engine is running. For Potential
Free mapping see section Digital Inputs.
Battery Current Limit (Normal) is always enabled
➢ To activate Alternate Battery Current Limit
• If a Digital Input is required, connect a voltage free relay contact (that will
operate when the standby generator starts) to a Digital Input.
• In Web go to Settings PFC Settings Input Configuration.
• Configure the selected Digital Input and set ‘DG Sense’ PFC on required Digital
Input. Input Sense can also be set here.
• In Web go to, Menu Settings Battery settings Charge Profiles CC/CV
Mode and set Alternate current limit.
Configuration – 1
Configuration – 2
Monitoring
The following information is available about Multiple Battery Banks:
No of Batt Fuses Set the number of Battery fuse as per Battery bank Display:
installed. Menu>System Config>DC
No of Batt LVD Set minimum one LVD or it can be set as per Config>Batt Config
configuration selection. Number of current sensing
or installed shunt and number of LVD installed are Web:
always same. Menu>System Config>DC
Config>Batt Config
Enable Temperature Compensation for optimum battery life and battery capacity over a wider temperature
range.
Temperature compensation function should work when all below conditions are true:
Monitoring
Parameter Description Where to find:
Configuration
Parameter Description Where to find:
EQUALIZE
Equalize charges batteries at a higher voltage after they have been fully charged to ensure that all individual
cell voltages are the same, that electrolyte is distributed evenly, and that sulphate crystal build-up on the
plates is reduced.
Equalize can be scheduled to occur at regular intervals and/or can be started/stopped manually.
The Bus voltage should gradually increase to Equalize voltage with Battery current approaching 10% of the
Battery Ah. Equalization Mode-Set Log should be stored in the event log. After the completion of the full
duration, voltage should gradually decrease to float voltage and the display will show Float mode instead of
Equalization mode.
If a system is in float mode and the Start Hour is reached, Equalize should start immediately.
If a system is not in float mode and the Start Hour is reached, then the system will wait for the float mode and
then start the Equalization.
Monitoring
Parameter Description Where to find:
Configuration
Parameter Description Where to find:
Equalize Voltage The bus voltage maintained during an Equalize cycle. Display:
Use the value recommended by the battery Menu>Settings>Battery
manufacturer. Controller will maintain this Equalize Settings>Charge Profile>Equalize
voltage for battery charging if function is enabled. Mode (Enable)
Start Hour Hour of the day (0 – 23) when Equalization will start Web:
after set interval time.
BATTERY TEST
Battery test is a preventative maintenance tool that monitors the discharge capabilities to ensure that the
condition of the battery has not deteriorated over time.
Battery test starts at the scheduled date and time, when the battery is in float mode or battery SOC is 100%.
Rectifiers stop sharing the load current and the load current is supplied by the battery. The battery will start to
discharge. Battery test-set log is stored in event logs.
Battery test will stop if any of the below conditions becomes true:
• Battery SOC is still greater than 80% but function reaches the duration time i.e. 1hr.
• Mains Fail-set
• Function disabled
• High Battery temperature
• Battery temperature sensor fail
Configuration
Set the following parameters.
Battery Test Function need to set for enable the battery test. Display:
Status Menu>Maintenance>Battery>Battery
Date & Time The Date and Time that the first battery test cycle will Test>Battery1>Battery Test Status
occur. Subsequent test will occur at every Battery Test
Interval after that. Web:
Menu>Maintenance>Battery>Battery
End of Discharge If the Bus voltage drops below this value during a
Test>Battery1>Battery Test Status
Voltage battery test, then the test fails.
Duration The maximum time a Battery Test process will be
active. The Battery test will pass if the Bus Voltage
remains above the Battery Test Termination Voltage
for the duration of the test.
Information
The following information is available about Battery Test:
For Battery Reverse condition detection system must install a Normally Open (NO) type contactor between
battery fuse and negative bus bar connection. Battery contactor coil’s one end is connected with relay which is
triggered by controller and provides the positive path to contactor’s coil. The other end of coil is connected
with battery fuse which provides negative path to it.
Battery Reverse detection or Battery reverse alarm can be generated only at the time of system installation.
During run time it is not possible to detect the Battery Reverse condition. When the system is being installed
and we connect the battery in reverse condition, then contactor’s coil will not triggered due to incomplete
path. Controller will sense the voltage before battery fuse, if sense voltage is less than -20V then EC500 will
declare Battery Reverse alarm and protect the system.
Hazardous condition:
• When the system is running and rectifiers are providing the bus voltage to circuit, the battery
contactor will be ON and EC500 will not turn off the contactor. In this run state of the system, if
reverse battery connected to the system then it can be hazardous for human and system.
• If an N/C (Normally Closed) contactor installed in the system and a reverse polarity battery connected
to it, then before sensing the voltage system will fail.
If a battery is to be connected while system is in running condition, LVD must be isolated from Home >
Maintenance > Battery isolate.
Rectifiers will charge the battery until its SoC becomes 100%. When battery comes to float mode (i.e. Battery
charging current becomes less than 3% of Battery AH), this function will be disabled.
Configuration
Parameter Description Where to find:
Monitoring
Following information is available about Equalization:
Status Display will show the Manual Charge at the time of Display:
Manual Charging and after completion it will show System Status
Float.
Float mode: Solar charger rectifiers make 54.0V and AC rectifiers make 53.5V.
Charging mode: Solar charger rectifiers make 55.2V and AC rectifiers make 54.7V.
Solar chargers share maximum load by tracking MPPT (Maximum Power Point Tracking) point from solar panel.
Configuration
Parameter Description Where to find:
Web:
Menu>Settings>S-Charger Settings
Low Solar current When solar current is less than Low Solar
time Current Threshold for this time limit,
generate the Low Solar current Alarm.
Information
The following information is available about all Solar Chargers:
Common Information
Parameter Description Where to find:
RECTIFIERS
HPR48-ES 3kW
LPR48-ES 1.2kW
The Controller supports only one series of rectifiers in one system. Please refer to System Configuration for
Rectifier Type selection. Solar Charger is always supported irrespective of the type of rectifier selected.
Configuration 1P-N:
In this configuration all Rectifiers operates on a single phase and neutral. If system does not have any input
measurement unit (ACIF or HVLV) then Rectifiers can provide ac measurement with respect to Neutral.
Configuration 3P-N:
Rectifiers are equally distributed on three different phases, R-phase, Y-phase and B-phase with respect to
neutral. If the system does not have any other input ac measurement unit (ACIF or HVLV) then Rectifiers can
provide AC measurement for R-phase, Y-phase and B-phase with neutral.
Configuration 3P-P
In this configuration, the system uses Rectifiers which operates on phase to phase input. Single phase
Rectifiers cannot operate in this configuration. If the system does not have an HVLV card then rectifiers will
provide AC phase to phase measurement.
Monitoring
Parameter Description Where to find:
Rectifier Slot Slot number allotted to this rectifier. This is allotted Display:
Number as per sequence of registration and not actual Menu>System Status>
physical slot number Rectifier>Individual Rectifier
Status
Rectifier Serial Production Serial Number of rectifier. Can be used Web:
Number for verifying the registered slot number Home>System Status>
Rectifier>Individual Rectifier
ID 15 digit Identification number of rectifier provided Status
by EC500
If more rectifiers are installed than Install Rectifier Count, the rectifiers will work but no
alarms will be reported.
RECTIFIER REGISTRATION
All the rectifier slots in the DC Power system are identical. The Controller automatically registers all rectifier
modules and solar chargers as they are inserted into the dc power system. Rectifiers are assigned a sequence
number in the order these are registered. All further reference to rectifiers / solar chargers is with this
sequence number. To have one to one correspondence between the Rack Slot numbers and rectifiers, the
following procedure shall be followed.
The EC500 sends a LSS command to rectifier. In response, the rectifier sends it data. The EC500
checks, and if the rectifier is already registered then it will skip the registration process. Else it starts
the registration process.
IDENTIFY A RECTIFIER
The rectifier’s registration number does not correspond to a physical position in the DC power system.
➢ To Identify a Rectifier
Either:
• In EC500 keypad go to: Menu>System Status> Rectifier>Individual Rectifier Status. Press
Enter.
For identification Green LED on corresponding rectifier will start blinking fast when a User
selects this rectifier on LCD.
• Rectifier detail screen will appear and show rectifier’s identification number and
communication status.
Or:
• In Web page go to: Menu>System Status>Rectifier, appear screen will show rectifiers
identification number.
The controller automatically adjusts rectifier target voltage so that each rectifier equally shares DC load. To
achieve this, the controller periodically updates a share factor in each rectifier for a faster current sharing after
a power restore. The user can manually reset this current share factor to restart current share factor
calculation again.
Note that sharing is effective only when rectifier load is more than 25% of its capacity.
• On the EC500 keypad select: Home Settings Rectifier Settings Force Share Reset
• Confirm the action to reset current share factor.
Or:
• Connect to the EC500 via a web browser (See Ethernet Communications on page 79).
• Go to Settings Rectifier Settings Force Share Reset.
• Click on Edit button to enable editing
• Click on “Force Share Factor” action field to reset current share factor.
On Current Share Factor Reset, controller will restart current sharing adjustment. It may take
2 – 5 minutes to achieve less than 10% current share deviation.
• On the EC500 keypad Enable: Home Settings Rectifier Settings Force SMR to Sleep
• Then Select or Deselect individual rectifier to put it in sleep mode or to activate it.
Or:
• Connect to the EC500 via a web browser (See Ethernet Communications on page 79).
• Go to Settings Rectifier Settings Force SMR to Sleep.
• Click on Edit button to enable editing
• Select individual rectifier Sleep status from drop down.
• Click Save button.
Rectifiers can be put in Sleep mode manually only of Economy Mode Operation is disabled.
ECONOMY MODE
If Economy Mode operation is enabled, the Controller can automatically put the rectifiers in sleep mode when
the total load current is less than the total rectifier capacity.
This raises the average load on the remaining rectifiers which will then operate in higher efficiency range and
results decrease in system power consumption.
Controller will progressively enable rectifiers when load increases. User can select minimum number of
rectifiers which will always run.
Carefully select minimum number of rectifiers to run in Economy Mode taking care of battery
backup conditions and input power conditions.
• On the EC500 keypad Enable: Home Settings Rectifier Settings Eco Mode
Or:
• Connect to the EC500 via a web browser (See Ethernet Communications on page 79).
• Go to Settings System Settings Rectifier Settings.
• Click on Edit button to enable editing
• Click ECO Mode / Status field to select Enable / Disable drop down.
• Select Enable and Click Save button.
• On successful change, more options will appear.
When Economy Mode Operation is enabled, rectifiers cannot be put in Sleep Mode manually.
Any rectifiers already put in Sleep Mode manually will not participate in Economy Mode
operation. Eco mode will bypass that specific rectifier.
Monitoring
Parameter Description Where to find:
LED Indication If a rectifier is in Sleep Mode, Red LED starts flashing Rectifier front panel LED
at high rate on rectifier front panel.
Configuration
Parameter Description Where to find:
will start forcing rectifiers to sleep mode till rectifier Home> Settings >Rectifier
load increases to “Maximum Load threshold”. Settings >Eco Mode
Maximum Load Load percentage (of rectifier capacity). If rectifier
load is above this threshold the Economy mode logic
will start enabling rectifiers from sleep mode.
Sleep Sequence Two sleep sequences are supported, Linear & Cyclic.
Cyclic Period Duration after which a rectifier in sleep mode will be
made active and next rectifier put in sleep mode.
Operational only if cyclic sleep sequence is selected.
Operation
Economy mode logic, when enabled, monitors per rectifier current and if it is less than the Minimum Load
setting and number of active rectifiers is more than Minimum Active Rectifiers setting, then it will put one
rectifier in sleep mode. This cycle is continuously repeated and next rectifier put in sleep mode till either load
current per active rectifier is more than Minimum Load setting or number of active rectifiers is equal to or less
than Minimum Active Rectifiers setting.
In case rectifier current becomes more than Maximum Load per rectifier setting or number of active rectifiers
becomes less than Minimum Active Rectifiers setting, logic will start enabling rectifiers one by one, till per
rectifier current is less than Maximum Load setting or all rectifiers have been enabled. Each cycle takes
approximately 1 minute.
The following two types of sleep and wake up sequences are provided:
When the cyclic period is over (i.e. 60min), the cyclic index increments by one, so that the index becomes 2
and time t = 1. When the index is incremented by one, then ON/OFF status of rectifier is shifted by one
position in clock wise direction as shown in fig below.
Similarly, at every cyclic period completion, the cyclic index is incremented by one and reaches its maximum
value that is equal to installed number of active rectifiers.
When cyclic index reach at its maximum value (6 in this example), the cyclic index rolls back to value one at its
next completion of cyclic period.
The advantage of the cyclic sleep sequence over linear sleep sequence is that in cyclic sleep sequence each
rectifier goes to sleep mode for their dedicated time period. This gives equal running time for all rectifiers.
For the Linear sleep sequence, the Min Active Rectifier count of rectifiers from left to right direction are always
ON.
RECTIFIER ALARMS
Alarm Description Where to find:
Rectifier Fail The rectifier fail alarm is generated when Rectifier Display:
Fail condition is provided from the rectifier Menu>Setting>Rectifier
(however, if all rectifiers communicate “Rec Fail” Settings>Alarm Settings
alarm to MCM then we get “All Rec fail” alarm on Web:
MCM rather than “Rec Fail”). Home>Settings>Rectifier
Multiple Rectifier Multiple Rectifier Fail alarm is generated when one Settings>Alarm Settings
Fail more than one but not all rectifiers have Rectifier
Fail alarm.
All Rectifier Fail The “Rec Current Limit” alarm is generated by the
rectifier when the control loop switches from
constant voltage to constant current mode and
output voltage drops by 1V compared to previously
measured voltage.
Rectifier Comm. The “Rec CAN COMM Fail” alarm is generated inside
Fail the rectifier when the rectifier communication with
MCM is interrupted for continuous delay of 10
seconds. Whenever “Rec CAN Comm Fail” occurs,
rectifier re stores its default settings – a) Output
Voltage of 54.0V, Rectifier Current Limit of 63A,
Battery Temp Comp Factors and Values, Re-set of
previously disabled commands issued to the
rectifier.
All Rectifier Comm. In case, if 1) Rectifier Fail condition is provided from
Fail the individual rectifier (however, if all rectifiers
communicate “Rec Fail” alarm to MCM then we get
“All Rec fail” alarm on MCM rather than “Rec Fail”)
The controller continuously monitors system bus and battery voltages. It can generate system alarms and Low
Voltage Disconnect signals for protecting battery and loads.
• to protect a VRLA battery from deep discharge and premature failure, and/or
• to reduce the load on a battery under discharge so that high priority equipment operates for
a longer time after an AC supply failure.
In case multiple battery contactor drives are required same can be mapped. Please see Configuration on page
43Error! Bookmark not defined.. All battery contactors use the same disconnect and reconnect thresholds.
BUS MONITORING
The following thresholds can be set to generate alarms whenever the system bus is lower / higher than these
thresholds:-
Monitoring
Parameter Description Where to find:
System Current System Current, sum of load and all battery currents. Home Screen (Below
rectifier Icon)
Configuration
Parameter Description Where to find:
DC High Voltage Set Whenever Bus voltage is higher than this set Display:
Threshold threshold, system generates a DC high Voltage Home>Settings>DC
alarm. This alarm can be latched. Settings>DC Alarm Settings
DC High Voltage Restore point for clearing DC High Voltage alarm.
Restore Offset Web:
Home>Settings>DC
DC Over Voltage If Enabled DC High Voltage alarm will be latched,
Settings>DC Alarm Settings
Latch requiring a manual clearing of alarm.
DC Low Voltage Set Whenever Bus voltage is lower than this set
Threshold threshold, system generates a DC Low Voltage
alarm.
DC Low Voltage Restore point for clearing DC low voltage alarm.
Restore Offset
DC Overload Set If system current (sum of load and all battery
Threshold currents) exceeds this DC Overload Alarm Threshold
(Normally 105% of System Capacity) system
generates DC Overload alarm. This alarm can be
latched.
DC Overload Offset Restore point for clearing DC Overload alarm.
Threshold
DC Over Current If Enabled DC Over Current alarm will be latched,
Latch requiring a manual clearing of alarm.
When the DC High Voltage alarm condition becomes true, the system generates the DC High Voltage alarm.
The rectifier stops providing current for battery charging , but Loads are connected to system and remain
powered.
BATTERY LVD
The user can define Disconnect & Reconnect thresholds. These apply to all battery LVDs.
Configuration
Parameter Description Where to find:
LOAD LVD
The user can define up to 4 Load connect & disconnect thresholds.
Configuration
Parameter Description Where to find:
Load x Low Voltage Indicates “disconnect voltage threshold” for Load x Display:
Disconnect contactor. Menu>Settings>DC Settings
Threshold > LLVD Settings
Load x Low Voltage Indicates “re-connect voltage offset” for Load x Web:
Re-connect Offset contactor. Home>Settings>DC Settings
>LLVD Settings
Refer Hardware Channel Mapping on page 74 for LVD physical channel mapping.
TYPICAL LVD ARRANGEMENTS
The simplest use of an LVD is as a single battery disconnect contactor.
The following diagram shows a typical arrangement of one battery and one Load LVD. This arrangement allows
lower priority loads to be disconnected first (contactor controlled by control channel LLVD 1), at a specified
battery voltage lower than Battery LVD. This prolongs battery availability for the higher priority loads
(contactor controlled by control channel BLVD). The battery will be disconnected when the battery voltage
reaches its BLVD set threshold.
LVD OPERATION
The battery LVD operates (opens) if the bus voltage is below the BLVD Set Threshold. Battery LVD will
reconnect if Battery voltage is higher than BLVD Restore Threshold. A fixed delay of 15 seconds is provided
before operating (activating / de activating) the LVD when voltage conditions are met.
The load LVD operates (drops) if Bus voltage falls below the respective LLVD Set Threshold. Load LVD will
reconnect when Bus voltage rises above respective LLVD Restore point. A fix delay of 15 seconds is provided
before operating (activating / de activating) LVD when voltage conditions are met.
DCDB ALARMS
Alarm Description Where to find:
ALARMS
EC500 provides a number of alarms to indicate any abnormal system condition to the user. The EC500 is
supplied with a standard configuration file has a default set of alarms configured and enabled. This will be
sufficient for standard dc power system operation.
For specific alarm arrangements all EC500 alarms can be individually enabled or disabled and are configurable.
TYPE OF ALARMS
EC500 provides following four type of alarms:
System Alarms Generated by the operating values of dc power See details on page 47.
system (voltages, currents, temperatures, and so
on), operation of power system modules (rectifiers,
circuit breakers, fuses, and so on) and
communication alarms. The EC500 system alarms
are listed in Alarm Descriptions on page 97.
Analog Alarms Activated when the result of Analog compare logic is See details on page 49.
active.
Potential Free / Activated when mapped PFC / DI is in its active See details on page 48.
Digital Input Alarms state.
Smart Alarms Software simulation of logic gates to allow the See details on page 51.
logical combination of multiple alarms.
• Critical
• Major
• Minor
Critical Major LED (RED) on front panel will turn ON. See details on page 16.
Major Major LED (RED) on front panel will blink. See details on page 15.
Minor Minor LED (Amber) on front panel will turn ON. See details on page 15.
Critical If the audible indicator is enabled, it will sound until See details on page 16.
Major joystick is operated. Audio indicator will sound for a
Minor maximum of 1 minute if no keyboard operation is
done.
ALARM GROUPING
EC500 has provision for grouping of individual alarms. A maximum of 64 alarm groups can be configured. The
user can map individual alarm to up to two alarm groups. Grouping provides an OR function. User can edit
group names to match the requirement. Some of the group names may not be editable. Only Groups can be
mapped to operate output relays. Alarms cannot be mapped directly to relays. In case alarm grouping is not
required, users can map individual alarms to independent group.
If a Potential Free alarm output is required, the alarm should be mapped to at least one
alarm group.
Refer section Digital Outputs on 59 for mapping Groups to Potential Free outputs.
SYSTEM ALARMS
These are generated by the operating values of dc power system (voltages, currents, temperatures etc.),
operation of power system modules (rectifiers, circuit breakers, fuses etc.) and communication alarms. The
EC500 system alarms are listed in Alarm Descriptions on page 97. The user can define alarm severity, Trap
operation and output mappings for System alarms. The user cannot change alarm names from Web page
though these can be changed in Configurator.
Configuration
The following system alarm parameters can be configured for individual system alarm.
Enable Alarm If set to Disabled then the alarm will not activate. These settings are available
Note that for some alarms enable / disable may not under respective resource
be available. settings e.g. alarm settings
for Battery will be available
Alarm Severity Alarm Severity (Critical / Major / Minor) of individual under Battery Settings.
alarm.
Display:
Enable Audible Enable or disable the audible alarm indicator for Menu>Settings> xxx
Alarm Indication particular alarm. Settings>Alarm Settings
Enable SNMP If Enabled, SNMP Trap will be sent for this alarm. For Web:
SNMPv3, alarm severity should be equal to or higher Home>Settings>> xxx
than Trap receiver’s configured alarm severity. See Settings>Alarm Settings
page 86 for details.
Enable Input Enable it to use the PFC input. If set to Disabled then
the input will not be polled.
User Alarm Map Map input PFC to one of the User alarms. Some of
the user alarms may be pre-defined and not
configurable.
Enable Alarm If set to Disabled then the alarm will not activate.
Note that for some alarms enable / disable may not
be available.
Alarm Name Set Alarm name for respective user alarm. This name
will appear in alarm windows and reported on
SNMP.
Enable SNMP If Enabled, SNMP Trap will be sent for this alarm. For
SNMPv3, alarm severity should be equal to or higher
than Trap receiver’s configured alarm severity. See
page 86 for details.
• Map PFC hardware: Home System Configuration Hardware Mapping PFC Input
• Enable PFC: Home Settings PFC Settings Input Configuration Status
• Enable Sense: Home Settings PFC Settings Input Configuration Sense
• Map User Alarm: Home Settings PFC Settings Input Configuration Map
• Alarm Name: Home System Configuration Alarm Management User Alarms (on
web only)
• Enable Alarm: Home Settings PFC Settings Alarm Settings Status
• Set Severity: Home Settings PFC Settings Alarm Settings Severity
• Group Map 1& 2: Home Settings PFC Settings Alarm Settings Map 1 / 2
• Enable Trap : Home Settings PFC Settings Alarm Settings Trap
ANALOG ALARMS
EC500 provides 16 analogue compare engines. Predefined parameters can be compared against fixed values or
other parameters. High / low compare to absolute value or analogue parameters, offset and hysteresis are
provided. Following configurations can be done. User can set names of Analog Alarms as given in Analog Alarm
Configuration.
Enable Engine If set to Disabled then the analogue alarm will be Web (only view):
disabled and engine will not execute the Home>Settings> Analog
comparison. Alarm Configuration.
Enable Alarm If set to Disabled then the alarm will not activate. Display:
Note that for some alarms enable / disable may not
be available.
Alarm Name Set Alarm name for respective analogue engine Menu>Settings> Alarm
alarm output. This name will appear in alarm Management > Analog
windows and reported on SNMP. Alarms
Enable SNMP If Enabled, SNMP Trap will be sent for this alarm. For
SNMPv3, alarm severity should be equal to or higher
than Trap receiver’s configured alarm severity. See
page 86 for details.
SMART ALARMS
EC500 provides 16 user configurable logic block. Each combinational logic block provides three inputs and two
function blocks. Each function block provides three logic functions i.e. AND, OR & XOR and two inputs. Each of
the two inputs can be inverted before presentation to function blocks. A graphical interface is provided for
selecting the inputs and functions. Alarm activation and de activation delays can be set. The output of each
logic alarm generator can be mapped to any available User alarm so that all functions available with User
alarms can be used seamlessly. A truth table for alarm helps in verifying the logic.
Enable Engine If set to Disabled then the smart alarm will be Web (only view):
disabled and engine will not execute the function. Home>Settings> Smart
Alarm Configuration.
Input Alarm 1/2 Select Alarm input 1 / 2 for function block 1.
Configurator:
Function Block 1 Select AND / OR / XOR function for function block 1.
Home>Settings> Smart
Invert Input 1 / 2 Invert input 1 / 2 of function Block 1 Alarm Configuration
FB1
Note that Smart Alarms inputs can be System Alarms, User alarms and Analog alarms. Since
output of Smart alarm is mapped to User alarms, care should be taken not to loop the
alarms.
Alarm Flow
The following diagram indicates various alarms types available and their input / output paths.
User Alarms
System Alarms
Alarm Attributes
{severity, snmp trap}
Web:
Home>Settings>System
Settings>Buzzer
GENERATOR CONTROL
Generator control function is used to delay the start of a standby ac generator until the batteries are partially
discharged (rather than immediately after the ac supply fails). This can save fuel by preventing the generator
running during short ac supply failures.
Generator logic provides control for two digital outputs (relays) which can be used to control running and load
control of generator. EC500 provides option to start / stop generator based on Bus voltage and / or Battery
SOC. Once generator start condition is met it activates Relay 1 and after a user configured delay (Ton) activates
Relay 2. Relay 2 can be used to transfer load to generator. Once generator stop conditions are met, it de-
activates Relay 2 first and then deactivates Relay 1 after user configured delay (Toff). Below timing diagram
demonstrates the relay operation.
Ton Toff
Relay 1
Relay 2
In any case, if stop conditions is not met i.e. Battery SOC does not reach at its Stop SOC Threshold or Battery
Voltage does not reach at its Stop Voltage Threshold, but DG Run Timeout (4 hours by default) is over, then
EC500 will start Generator off sequence.
EC500 can also monitor one potential free input to sense generator run condition provided by generator. A
generator fail alarm is activated if EC500 does not detect ac supply (rectifiers have turned on) or does not
sense the digital input, once generator Relays have been activated.
A digital input can be mapped to monitor generator run status. On activation of this input,
controller applies alternate battery current limit and enables DG energy and run hour
counters.
Configuration
Set the following parameters:
Drive ON Delay Time delay between Relay 1 activation and Relay 2 Display:
activation at the time of generator ON condition. Menu>Settings>DG Settings
Drive OFF Delay Time delay between Relay 2 de-activation and Relay
1 de-activation at the time of generator OFF Web:
condition. Menu>Settings>DG Settings
DG Max Run The maximum run time of generator, whatever is the
Timeout status of battery SOC and battery voltage, if this
timeout expires then generator will be turned off.
DG Function SOC If enabled, controls generator On or Off as per the
Based battery SOC threshold.
Start SOC Generators is turned On if Battery SOC falls below
this threshold limit; default 40% of battery capacity.
If both SOC and Voltage based control are enabled, then generator will start if any start
condition is true and generator will be turned off both conditions are true.
The following section describes the input/output functions available with a single DCIO and PFCIO board.
Bus Voltage Each card’s first channel is allocated for Bus voltage;
EC500 reads the Bus voltage from each card. The
card which provides the Bus voltage greater than or
equal to 30V determined that card and channel for
system Bus voltage.
Load Current Total Load current is the sum of any analogue input
configured as Load current. Otherwise, if Battery
Current is available, the Load current is calculated as
Rectifier Current – Battery Current. Otherwise it is
unavailable.
Battery Current Total Battery current is the sum of any analogue
inputs configured as Battery current. If positive
battery is being charged.
Solar Current Total current produced by the Solar chargers
controlled by EC500.
Sum of Reported The sum of the currents reported by all rectifiers.
Rectifier Currents Where there is no analogue input configuration as
Rectifier current. This will be the same value as
Rectifier current.
Load Power The power being supplied to the load. Load current x
Bus voltage.
System Power Calculated as Bus voltage x Rectifier current if system
operating at Mains supply or DG.
ANALOG INPUTS
The analog inputs (AI) monitor variable dc voltages (bus voltage sense, general purpose analog inputs, current
sensors or temperature sensors).
Generally, the system analog inputs are configured at the factory and do not need to be changed.
The table shows the available number of analog inputs. The actual number of analog inputs
available depends on the number of I/O boards or modules connected.
• Select an analog input. The analog inputs are mapped to specific I/O connectors and are of
three types (voltage/general purpose, current or temperature). See mapping table on page
77.
• Configure the following parameters to suit the application.
To change a setting, select from drop down list or edit the text.
Parameter Setting
Name Type the name of the input or use the default value.
I/O Board Number Select the Analog input number with DCIO board
+ number for respective predefined function.
Analog Input
Number
Shunt Value Select the shunt value with respective mV output
voltage for sensing current.
Configure the following parameters in the Analog Input High Alarms and/or Analog Input Low Alarms tables to
suit the application.
Parameter Setting
Send Trap An SNMP Trap will be sent for this alarm, if Send
Trap is True and the alarm’s severity matches the
setting of the SNMP Trap Level.
SYSTEM STATES
The EC500 monitors the following system states to provide an overview of the DC power system’s operation.
States displayed will depend upon the dc power system model. Some states will only be displayed if there is a
digital input configured for this function.
Name Description
Fan Fail Indicates if any digital input with function set to “Fan
Fail” is active.
Load Fuse Fail Indicates if any digital input with function set to
(DCCB Trip) “DCCB Trip” is active.
Battery Fuse Fail Indicates if any digital input with function set to
“Battery Fuse Fail” is active.
SPD Fail Indicates if any digital input with function set to “SPD
Fail” is active.
DG Running status Indicates if any digital input with function set to “DG
Running status” is active.
DIGITAL INPUTS
The input / output board is fitted with a number of configurable digital inputs (DI) which can monitor external
voltage-free relay contacts or switches.
Configure the following parameters in the Digital Input Alarms table to suit the application.
Parameter Setting
Recognition Period This alarm will activate only after the digital input is
active for this period.
Deactivation The alarm will deactivate only after the digital input
Recognition Period is inactive for this period.
Send Trap An SNMP Trap will be send for this alarm, if send
trap is true and the alarm’s severity matches the
setting of the SNMP trap level.
DIGITAL OUTPUTS
The input / output (I/O) board is fitted with a number of digital outputs (relays) which can control external
equipment or alarm systems.
Digital outputs are operated by a mapping from a digital input alarm, an analog input high or low alarm or a
system alarm.
Parameter Setting
I/O Board Number Select the Analog input number with DCIO board
+ number for respective predefined function.
Analog Input
Number
Active State Select the state of output when the Digital Output is
active
Send Trap An SNMP Trap will be send for this alarm, if send
trap is true and the alarm’s severity matches the
setting of the SNMP trap level.
ENERGY METERING
The Energy Logger records the energy readings for energy meters, cumulative at a specific interval and once in
a full day at midnight. The user can also view per day energy consumption.
DC voltage and current for energy meters are read from respective mapped analogue channels i.e. bus voltage,
battery current, load currents etc. and no additional mapping is required. AC voltage and ac currents are
measured by rectifiers. Solar energy is measured by respective solar chargers.
The EC500 also supports predefined external Modbus based energy meters. Contact Eaton for more details
and availability.
INFORMATION
The following information is available about energy metering.
CONFIGURATION
Set the following parameters.
Load Energy Meter Enable the status of Load Energy Meter Display:
Status Menu>System Config>DC
Config>Load Config
Load Energy Meter Select the load energy meter type, Internal or
Type External.
No of Load Paths Select the number of Load paths as per load strings.
Web:
Load Current Compute the load current with difference of Rectifier Menu>System Config>DC
Computation current and Battery current instead of using load Config>Load Config
shunt.
Battery Shunt Amps Set the battery shunt rating in ampere. Display:
Menu>System Config>DC
Battery Shunt mV Set the battery shunt output voltage proportional to Config>Current
current passing through it. Sensing>Shunt
DATA LOGGING
The EC500 has the following event and data logging functions. All log data can be downloaded as csv file
through web interface or directly to USB drive and can be read using any standard spreadsheet program.
All kind of data log have their own settings. Some logging needs to be enabled, such as
Performance logging and Data logging.
EVENT LOG
The Event Log records every system event / alarm. The EC500 can store up to 10,000 event logs. All types of
alarms i.e. system alarms, analogue alarms, user alarms and smart alarms are logged. Logging of individual
alarms can be disabled under the alarm management section.
Each alarm is logged with its status (Set or Clear), severity and date-time of event.
The 10,000 log store is used in a circular fashion. The oldest logs are over written.
• In Web page go to: Menu>Logs>Erase Logs>. Click on Edit tab and press “Yes Confirm” of
Alarm Logs and press Yes to erase Event Logs.
DATA LOG
The Data log records several system parameters like AC Voltage, Bus Voltage, Load Current, Rectifier Current,
Battery Current, Battery Temperature and Discharge Ah at specified intervals. The rate of Data recording is
settable from Web page. Memory for 10000 Data Log entries is pre-allocated. When this memory is full the
oldest record will be overwritten.
ENERGY LOG
The Energy Log records cumulative and day wise kWh for battery, load, mains energy, diesel generator energy
and load energy. User can view energy logging “Day Wise” and “Month Wise”.
STATUS LOGS
The Status Log records battery status of the system. Memory for 1000 Status Log entries is pre-allocated.
When this memory is full the oldest record will be overwritten.
• To download/save the Log file in web, go to Tab “Export”. The EC500 will export the logs in
excel sheet and save in the download folder.
• To download logs in USB, attach a USB drive to USB connector on front panel, go to Home >
Settings > USB Settings > CopyToExtDrive and select required logs to download. Logs will be
downloaded to USB.
CHANGE LOGS
Any changes to system configuration are logged along with old value, new value, date-time and user. Memory
for 1000 Change Log entries is pre-allocated. When this memory is full the oldest record will be overwritten.
PERFORMANCE LOGS
The Performance Log records the user selected parameters of system. Settings need to be done before starting
the performance log. Controller with SD card provides this option. Refer Controller options on page 11.
Performance data will be logged at user set periodicity and for user set duration.
• To download/save the log file in web, go to Tab “Get Logs” it will export the log in text file,
progress bar will show the progress. After log download completion in download folder of
windows operating system, a pop up window will appear “Logs Download Complete”. Press
OK to complete this process.
SYSTEM CONFIGURATION
OVERVIEW
The EC500 Controller supports a number of functions which are dependent upon availability of specific
hardware in the system. Some critical parameters are also controlled under this section. EC500 configuration
should be set accordingly before commissioning. Most of these configuration settings are not available on
display or Web pages, as these are related to system hardware and should not be changed at run time.
To generate a suitable configuration use the Configuration Tool “Configurator”. This tool generates a
configuration file which can be downloaded to the controller.
For specific requirements, this configuration file can be preloaded in the factory for quick installation &
commissioning.
SYSTEM INFO
The following settings relate to system hardware. These are required for correct operation of the display
screen, web pages, communication and functionalities.
Since system hardware does not change in the field, these settings are not normally editable from Web, SNMP
or Display.
Rectifier Type Select the rectifier type which will be HPR48-ES Configurator:
used in the system. This will result in Main Menu>System
proper communication with rectifier, Config>System Info
rectifier parameters and alarm Web:
reporting. Currently supported Home>System Config>
rectifiers are: System Info
• HPR48-ES (3kW)
• LPR48-ES (1.1kW)
Refer section Rectifiers on page 34 for
more details.
System Type Select whether it is a Single Phase (1P-
N), Three Phase (3P-N) or Phase –
Phase (3P-P) system. Refer section
Rectifiers on page 34 for more details.
DC Interface The EC500 supports following options DCIF 6V3C Shunt
Type depending upon hardware Sensor
requirements:
• DCIF 4V2C Shunt Sensor
• DCIF 6V7C Shunt Sensor
• DCIO 6V3C Shunt Sensor
Refer section DC Interface Boards on
page 8 for more details.
DCIF n Install The EC500 supports up to four DCIF DCIF 1: Installed
status boards. Depending upon the number of DCIF 2: Not Installed
BATTERY CONFIGURATION
Detailed battery parameter settings should be done as given under section Battery and Voltage Control on
page 22.
Home>System Config>
DC Config>Batt. Config
>Batt. Energy Meter
Battery Mid-point Monitoring provides a cost effective method for the early detection of internal battery
faults. The voltage of the two halves of the battery strings are measured and the system controller generates
an alarm signal if voltage imbalance is detected.
A voltage imbalance is an indication that one or more cells have an internal fault. Further investigation can
then isolate the faulty cell(s) and action can be taken to correct the problem and prevent a total battery
failure.
To ensure reliable operation Mid-point Monitoring operates only when the battery is in float mode and after a
configurable lockout period since the last battery discharge, Fast charge, Equalize or Battery Test.
There are two mid-point monitoring Analog inputs on DCIO board (for two battery strings).
Up to 10 additional battery strings can be monitored if additional DCIO input/output boards
are connected. Refer to the System Installation Guide for details on how to connect additional
DCIO input/output boards to the EC500.
Battery strings 1-2 will be connected to DCIO Number 1, DCIO Analog Input number 2-5.
Battery strings 3-4 will be connected to DCIO number 2, DCIO Analog Input numbers 2-5. And
so on, as required up to string 10.
Monitoring
The following information is available about Battery Mid-point Monitoring.
Upper Half String This shows the voltage of Battery string from mid- LCD: Menu>System
point of the string to top of the string. For example, Status>String
if 24 cells consider for 48V Battery bank, then it Monitoring>Mid String
shows the voltage between 13th cells to 24th cell. Voltage.
Lower Half String This shows the voltage of Battery string from ground
point of the string to mid-point of the string. It
shows the voltage between 1st cells to 12th cell.
String Status Calculate the difference between Upper Half String
voltage and Lower Half String voltage, if this Web: Menu>System
difference is less than MPM Threshold Voltage then Status>String Monitoring
status shows OK.
Battery String x When string status is not OK, EC500 generates an Web:
Alarm alarm if “Battery String x Fail” is enabled, x defines Menu>Settings>Alarm
the number of battery string. For example, Battery Management
String number 2 generates an alarm then display will
show “Battery String 2 Fail”.
Configuration
The following parameters are available for configuring Battery Mid-point Monitoring.
Max Strings for Select the number of Battery strings available in Web: Menu>System
MPM system. As per the selection of Strings for MPM, Config>DC Config>String
string parameters are visible in system status monitoring
MPM Volt This setting is used to calculate the final status of LCD:
Threshold Battery string. Each string compares its difference of Menu>Settings>Battery
Upper half voltage and Lower half voltage with this Settings>General
threshold. If difference is beyond this limit then Settings>String Monitoring
status is not OK. Same value is applicable to all
available Battery strings.
MPM Lockout mode more than MPM Lockout period then EC500 Web:
Period will starts the Mid-point operation. Menu>Settings>Battery
Settings
String x Mid Mapping of DCIO voltage channel with Battery Mid- Web: Menu>System
Voltage Channel point sensing signals. For detailed description refer Config>Hardware
the System Installation guide. Mapping>String Monitoring
LOAD CONFIGURATION
EC500 controller provides support for settable individual LVD and Energy metering for each load. It supports
up to 8 Loads. Following settings should be done as part of system configuration.
CURRENT SENSING
The system should be configured for the shunt ratings used in the system. Shunt rating and millivolts full scale
can be configured for each of the selected battery & load current channels. The shunt rating is passed on to
the DCIF card by EC500 and the DCIF scales the measurement as per the settings. These settings are not
intended for channel calibration. All DCIF channels come calibrated from factory. Refer to DCIF specifications
for accuracy.
Battery n Shunt Current rating of respective shunt in 150A, (50 – 5000) Configurator:
current rating Amp. To be defined for individual Main Menu>System
shunt. Setting range is from 50 – Config>DC Config>
5000A. The number battery shunts is Current Sensing
equal to “Number of Battery LVD” set Web:
above. Home>System Config >
Battery n Shunt Shunt millivolt at rated current rating, 50mV, (30 – 50) DC Config>Current
millivolt set above. Number of Load shunts is Sensing
equal to “Number of Load Paths” set
above.
CABINET CONFIGURATION
Items related to cabinet configuration like Temperature sensor, Door sensor and cabinet Fans etc. are
configured as part of System Configuration.
Cabinet Type For enabling fan control, the system Indoor Configurator:
can be defined as Outdoor. Main Menu>System
Config>Cabinet Config
Web:
Home>System Config
>Cabinet Config
Main Menu>System
Config>Cabinet
Config>Fan Config
Fan Sensing Enable or disable the fan sensing. Disable, Enable Main Menu>System
Config>Cabinet
Config>Fan
Config>Fan Sensing
For using system functions, all the required logical channels need to be mapped to respective channels in
hardware. The mapping must match the system wiring and needs to be done carefully.
The first voltage channel on each DCIF shall be wired to Bus Voltage. First channel of first
DCIF shall be mapped to Bus Voltage.
DCIF Current channels are referred as DCIFx_CURR_CHy, where x is DCIF board number (1 -4) and y is current
channel (1- 2 or 1 – 7) depending on particular DCIF board. For DCIF 4V2C Shunt board y varies from 1 – 2, for
DCIF 6V7C Shunt board it varies from 1 – 7 and for DCIO 6V3C Shunt board it varies from 1 – 3.
DCIF Temperature channels are referred as DCIFx_TEMP_CHy, where x is DCIF board number (1 -4) and y is
temperature channel (1- 2 or 1 – 3) depending on particular DCIF board. For DCIF 4V2C Shunt board y varies
from 1 – 2,for DCIF 6V7C Shunt board it varies from 1 – 3 and for DCIO 6V3C Shunt board it varies from 1 - 2.
DCIF LVD channels are referred as DCIFx_LVD_CHy, where x is DCIF board number (1 -4) and y is drive (1- 2 or
1 – 5 or 1 - 3) depending on the particular DCIF board.
DCIF PFC inputs are referred as DCIFx_PFC_INy, where x is DCIF board number (1 -4) and y is PFC input (1- 8) of
the particular DCIF board.
DCIF PFC outputs are referred as DCIFx_PFC_OUTy, where x is DCIF board number (1 -4) and y is PFC output
(1- 8) of the particular DCIF board.
PFC IO 16 inputs are referred as PFC16_x_INy, where x is PFC board number (1 - 2) and y is PFC input (1- 16) of
the particular PFC board.
PFC IO 16 outputs are referred as PFC16_x_OUTy, where x is PFC board number (1 - 2) and y is PFC output (1-
16) of the particular PFC board.
LVD relays of DCIF 6V7C are physically mounted on Relay Board or PFC16 IO board.
Refer DC Interface and IO Board details on page 8 and Potential Free Input / Output Board on
page 9
Current Channels 2
Temperature 2
Channels
LVD Drives 2
Current Channels 7
Temperature 3
Channels
LVD Drives 5 Requires additional
relay boards or PFC
IO16 board
Current Channels 3
Temperature 2
Channels
LVD Drives 3
PFC Inputs 8
PFC Outputs 8
PFC Output 16
Mapping>Battery>
Battery n LVD Channel
Web:
Home>System
Config>Hardware
Mapping>Battery>
Battery n LVD Channel
Load MCB Trip Single Load MCB trip using diode string None
Sense is sensed on PFC input. Any available
PFC input can be mapped.
Home>System
Config>Load>Load n
Current Channel
Fan n drive For Fan n drive, required only if Cabinet None Configurator:
is set as Outdoor & Fans are to be used. Main Menu>System
Any available PFC output can be Config>Cabinet>Fan n
mapped, subject to contact rating Relay Channel
required for driving Fan. Web:
Home>System
Config>Cabinet>Fan n
Relay Channel
Fan n Fail Sense For Fan n fail sense PFC input, required None
only if Cabinet is set as Outdoor & Configurator:
individual Fan fail sense is to be used. Main Menu>System
Any available PFC input can be mapped Config>Cabinet>Fan n
Sense Channel
Web:
Home>System
Config>Cabinet>Fan n
Sense Channel
COMMUNICATIONS
COMMUNICATIONS OPTIONS
The EC500 controller provides multiple methods for local and remote communications. A user can
communicate with the controller using 100BaseT Ethernet interface, serial RS485 (Modbus RTU) interface or
GSM modem on RS232 interface. These interfaces provide different level of communication capabilities.
The USB interface is not used for controller communication; it is used for file transfers (to controller) in Host
mode.
ETHERNET COMMUNICATIONS
Ethernet provides the most versatile interface for local or remote communications with the controller.
Refer to:
• Section EC500 Operation Using a PC/Laptop on page 16 for how to connect to Ethernet interface.
• Section System Controller Connector Pin-outs on page 100 for pin outs.
A typical connection diagram is as shown below. Multiple devices can communicate simultaneously over the
Ethernet connection.
PC
Laptop
Ethernet Communication Network
(LAN / WAN)
EC500
NMS Server
The network administrator may assign a unique IP address to each EC500 to be connected to
the TCP/IP network.
Alternatively, use DHCP (Ipv4 or IPv6) to automatically assign an IP address. Network shall
have a DHCP server.
IPv4 address mode is always available in EC500 and IPv6 must be enabled if IPV6 is required.
➢ To configure the EC500 for Static IPv4 Address using the keypad
• Using EC500 Joystick go to: Home Settings System Settings Communication
Settings Ethernet IPv4
• Click on IP Configuration and select Static
• If you are not logged in, a pin screen will be displayed. Enter your pin and press Login.
• Click on IP Address and enter required IPv4 address. Static IP addresses are typically pre-
assigned by network administrators / network planner.
• Similarly enter the pre-assigned Subnet Mask and Gateway Address. If not assigned,
Gateway Address can be left blank.
• Click Apply IP Settings to apply the entered IP settings.
• The Ethernet interface will now start communicating at selected IP address.
➢ To configure EC500 for IPv4 Address allocation from DHCP server using the keypad
• Using EC500 Joystick go to: Home Settings System Settings Communication
Settings Ethernet IPv4
• Click on IP Configuration and select DHCP
• If you are not logged in, a pin screen will be displayed. Enter your pin and press Login.
• Controller will restart and obtain an IP address from DHCP server.
• The Ethernet interface will now start communicating at assigned IP address.
• Assigned IP Address can be viewed from Home Settings System Settings
Communication Settings Ethernet IPv4 IP Address.
Ensure that a DCHP Server is available in the network. Otherwise no IP address will be
assigned to the controller and no communication is possible on Ethernet interface.
The controller will not communicate on Ethernet until a DHCP server is available or IP configuration is changed
to static.
By default, the controller is configured in Static mode with IP Address 172.16.66.50. This can be used for
starting direct communication with laptop / PC. You will have to set Laptop / PC IP address in static mode with
same subnet mask as the Controller. The controller Ethernet interface supports MDI / MDI-X so regular
Ethernet cable can be used.
M1000 Controller
Laptop
(Set Laptop to static IP)
• If you are not logged in, a pin screen will be displayed. Enter your pin and press Login.
• Click on IP Configuration and select Static
• Click on IP Address and enter required IPv6 address. Static IP addresses are typically pre-
assigned by network administrators / network planner. If an assigned IPv6 address is already
in use, it will be rejected by the controller upon connection to network.
• Click Apply IP Settings to apply the entered IP settings.
• Ethernet interface will now start communicating at selected IPv6 address.
Static IPv6 address is not a common mode of setting and should be used carefully.
➢ To configure EC500 for IPv6 Address allocation from DHCP server using the keypad
• Using EC500 Joystick go to: Home Settings System Settings Communication
Settings Ethernet IPv6 Status
• Enable IPV6 by selecting the check box.
• If you are not logged in, a pin screen will be displayed. Enter your pin and press Login.
• Click on IP Configuration and select DHCP
• The controller will restart and obtain an IP address from DHCP server.
• The Ethernet interface will get IPv6 address from DHCP server and start communicating at
assigned IP address.
• The assigned IP Address can be viewed from Home Settings System Settings
Communication Settings Ethernet IPv6 IP Address.
Or:
• Connect to the EC500 via a web browser (See Ethernet Communications on page 79).
• Go to Home Settings Communication Settings Ethernet MAC
The following methods can be used for communications over the Ethernet interface:
• Set up Ethernet communications and connect the EC500 to the IP network. See Ethernet
Communications on page 79.
• Open a web browser window.
Recommended web browsers: Microsoft Internet Explorer 10 or later, Mozilla Firefox 3.0 or
later, Chrome V63 or later.
Internet Explorer 10/11: Ensure that Compatibility Mode is turned off. Go to Tools >
Compatibility View Settings.
• Type the IP Address of the EC500 into the address bar of the browser.
If HTTPS Access has been enabled and you wish to use secure web communication then type
"https://" before the IP Address.
A MIB file is available for EC500, obtain it from your Eaton representative.
➢ To setup SNMP Communications
• Set up Ethernet Communications (see details on page 79).
• On the web, go to Home Settings Communication Settings SNMP.
• Set the SNMP Access and specific protocol parameters
SNMP Access
Parameter Description Range, Default Where to find:
Value
SNMP Port Port for access by SNMP Manager 161, not settable
SNMP Access Select SNMP protocol for access by SNMPv2c Home> Settings>
Type SNMP Manager SNMPv3 Communication
Settings>SNMP>SNMP
Default: SNMPv3 Type
Read Community Password for read access. Do not public, (string, len Home> Settings>
change the default settings unless 15) Communication
requested by the network Settings>SNMP>SNMP
administrator. Read Community
Privacy Protocol Select one of the two Privacy DES Home> Settings>
protocols. Required if Security model AES Communication
is set to AuthPriv Default: DES Settings>SNMP>SNMPv3
USER>USERx > Privacy
Protocol
For SNMP V3 security, the default user should be disabled or have its rights restricted.
By default SNMP access type is set to SNMPv3. It is recommended to use SNMPv3 for
SNMP access by a NMS Manager else your network may be at security risk.
Default: SNMPv2
Trap Format Select whether a single Trap OID is Group
sued for sending trap or individual OID Individual
is used for sending Trap Default: Individual
Trap Repeat Enable trap repeat if the network is not Enable
reliable Disable
Default: Disable
Trap Repeat Rate Set Trap repeat period, if enabled. 1 – 1440 Minute
Optimize between quality of network
and network load. It should be Default: 10 minute
repeated more often if network is not
reliable, but this increases network
load.
Individual alarm shall be enabled for sending SNMP Traps, by default all alarms are enabled.
Based on SNMP Trap protocol selected, user needs to configure below mentioned different parameters.
Trap Community Set Trap community *****, (string, len 15) Home> Settings>
accepted by respective Communication
Trap receiver. Contact Settings>SNMP>Trap Receiver
your NMS manager for x>Community
correct Trap Community.
Trap Receiver IP Select IP address type of IPv4 Home> Settings>
Address Type the Trap receiver. IPv6 Communication
Default: IPv4 Settings>SNMP>Trap Receiver
x>IP Address Type
Trap Receiver IP Set IP address of the Trap Valid IPv4 or IPv6 Home> Settings>
Address Receiver. Contact your address Communication
NMS manager for correct Settings>SNMP>Trap Receiver
IP address. x>IPv4 or IPv6
Trap Receiver IP Set IP address of the Trap Valid IPv4 or IPv6 Home> Settings>
Address Receiver. Contact your NMS address Communication
manager for correct IP address. Settings>SNMP>Trap Receiver
x>IPv4 or IPv6
For SNMP V3 security, the default user should be disabled or have its rights restricted.
Critical Alarm Delay after which mail will be sent to 1-1440 min,10
Delay user with Critical alarm severity
Major and Above Delay after which mail will be sent to 1-1440 min,10
Alarm Delay user with Major alarm severity
Minor and Above Delay after which mail will be sent to 1-1440 min,10
Alarm Delay user with Minor alarm severity
4. For each Email recipient (up to 6), set the following parameters:
MODBUS COMMUNICATIONS
The Modbus protocol is an industry standard that allows a master station to interrogate devices for its publicly
available data and set supported control and configuration parameters. Modbus is an open protocol and
transmitted over serial lines between devices.
For details of the Modbus registers supported by the EC500, please refer the document
“EC500_Modbus_Register_Details.pdf”.
Modbus supports two serial transmission modes, ASCII and RTU (Remote Terminal Unit). Eaton products
support the RTU mode of operation, which is more prevalent. The EC500 supports RS485, 2 wire interface for
Modbus communications. Serial communication parameters are set to 19200B, 8 data bits, No parity and 1
stop bit.
The response message contains the data read from registers on the slave. The registers occur in order from the
first register requested through each sequential register that follows for the number of register requested.
The Modbus messages on serial connection are not in broadcast format. Devices constructed in such a way
that detect the beginning and end of messages. Framing constructed by measuring gaps of silence on the
communication line. Before each message, there must be a minimum gap of 3.5 characters. O prepare for new
messages, the receiver clears the buffer when gap of 1.5 characters is detected.
The EC500 only employs the Modbus Input Register and Holding Registers. By definition all Input Registers are
read only and Holding Registers are read-write. Depending upon the operation, the device may restrict access
to certain registers to read-only
For detailed description of Parameter Register mapping and Alarm Registers refer document
“AN0157 EC500 Modbus Server”.
COMMUNICATIONS SECURITY
TLS is a protocol for transmitting encrypted data over the Internet. URLs that require a TLS
connection start with https: instead of http. If the network is insecure, Eaton recommends
that you use HTTPS access only.
HTTPS access will be slower than HTTP because of the encryption process.
By default Web access type is set to HTTPS. It is recommended to keep using HTTPS to
avoid any security risk.
The EC500 is shipped with 8 fixed users with different privileges. Customers shall change the default
Username and Passwords. If the passwords for all users are forgotten then the EC500 will not be
accessible from the web. It will continue system control as normal in this condition. Please contact
your Eaton representative in such a case.
Three successive wrong password entries will block the specific user id for 30 seconds. User
must wait for the blocking period to login again. For every successive wrong password entry
the blocking delay will increase by 1 minute. Maximum delay will be 15 minute.
SPECIFICATIONS
EC500 CONTROLLER
INTERFACES
Ethernet
Interface: 10/100baseT, MDI / MDI-X, Auto Negotiation
Connector: RJ-45, front panel
Protocols: IPv4, IPv6, TCP/IP, UDP, SNMPv2c, SNMPv3, http (Web), https
(secure Web), SNTP, SMTP, DHCP Client
Static IP Settings: IP Address, Subnet mask, Gateway address
USB
Connector: USB Type A, front panel
Version: 2.0
Speed: Full Speed (12Mbits/s)
Function: File Transfers from controller
System Communications
Interface: CAN 2.0b
Baud Rate: 250kbps
Connector: RJ-45, rear panel
Number of interfaces: 2, Proprietary
RS-485 Serial
Interface: RS485, 4 wire
Connectors: RJ45, rear panel
Number of interfaces: 2
Protocols: Modbus RTU (Master / Slave), Proprietary
RS-232 Serial
Interface: RS-232 (DTE)
Connectors: DB9F, rear panel
Protocols: Modem interface, Proprietary
External modem options
GSM Modem: Modem Unit HE315xxx
SMS (Text) system status and alarm messages (EC500-V2)
Optional SD Card
Maximum Capacity: 8GB, usable 4GB
Home Screen: System Block Diagram with key system values, latest alarm,
Status and RTC date and time.
Entry
Input: Joystick
(Up / Down / Left / Right / Enter)
Access Security: Read Only,
Write Access with PIN Protection
User interface functions: View system values
View and change alarms
View status messages
Start / Stop control functions
Change operating settings
Audio & LED Indicators
Power On: Green
Critical / Major Alarm: Red
Minor Alarm: Yellow
Audible Alarm Indicator: Enabled/Disabled (default: Enabled)
Language
Language (standard): English
Language options: One additional language supported, available to special request
DC INTERFACE BOARD
DC Interface Units
Number of DC Interface units supported 4, default 1
Types IOB-6V3C
Channels per IOB-6V3C
Voltage: Bus / Load Voltage + 4
Maximum range: +/- 72V
Resolution: 0.01V
Current: 3
Current Sensor Type: Shunt, 50mV
Current Range: Max. + 3000A
Current Resolution: + 0.1A for shunts less than 1000A, + 1A for shunts > 1000A
Temperature: 2
Sensor Type Proprietary, supplied with the system.
Range: -20°C to +100°C,±1°C
Resolution < ±1°C
LVD Relays: 3, on board
Resolution: 0.01V
Current: 3
Current Resolution: +/- 0.1A for shunts less than 1000 A, +/- 1A for shunts > 1000A
Temperature: 2
These are maximum software capacities. Full capacity may not be utilizable sue to usage of
common resources and will depend upon hardware installed.
ALARM DESCRIPTIONS
Alarm Description
Mains Fail All three phases R, Y and B are less than 90V or greater than 300V and
communication between EC500 and Rectifiers is not OK. If these two
conditions are found on any complete set of rectifiers per phase for 7 seconds
continuously then “Mains Fail” alarm will be activated.
Phase Fail (R/Y/B) Individual phase is less than 90V or greater than 300V and communication
between EC500 and respective phase rectifiers is not OK. If these two
conditions are found on any complete set of rectifiers per phase for 10
second continuously then “R/Y/B Phase fail” alarm will activated.
Mains High All Rectifiers which are mapped on to different phases are scanned
continuously. If AC voltage range on all rectifiers are found less than 300V
and greater than 270V for 15 seconds continuously then “Mains High” alarm
will activated.
Mains Low All rectifiers which are mapped on to different phases are scanned
continuously. If AC voltage range on all rectifiers are found less than 150V
and greater than 90V for 15 seconds continuously then “Mains Low” alarm
will activate.
Rec Fail EC500 continuously scans the rectifier on different phases if actual rectifier
fail condition is generated from the individual rectifier then Rec Fail alarm will
be activated. This alarm is declared by both rectifier and EC500.
Multi Rec Fail When EC500 receives more than one rectifier fail alarm (“Rec Fail”) from
individual rectifiers then multiple fail alarm will be activated. This alarm is
generated by the EC500, not the rectifier.
Rec Comm. Fail The EC500 continuously communicates with each rectifier. When a rectifier
does not respond to an EC500 request within 60ms then rectifier
communication fail (“Rec Comm. Fail) alarm will be activated. This alarm is
generated by the EC500, not the rectifier.
All Rec Comm. Fail The EC500 continuously communicates with all rectifiers. When EC500
receives “Rec Comm. Fail” alarm from all individual rectifiers then all rectifier
communication fail (“All Rec Comm. Fail”) alarm will be activated. This alarm
is generated by the EC500.
Rec Temperature High If any rectifier has ambient temperature is less than -40°C and greater than
75°C or PFC heat sink temperature is greater than 93°C or DC heat sink
temperature is greater than 115°C, then rectifiers send rectifier temperature
fail (“Rec Temp Fail”) alarm to EC500 and EC500 activates rectifier
temperature high (“Rec Temperature High”).
Rec Over Voltage This alarm is generated in rectifier when below conditions are satisfied:
✓ EC500 gives output voltage command greater than (Set Overvoltage
limit – 1.0V)
✓ When actual output voltage of any rectifier is greater than Set
Overvoltage limit and present average output current of that
rectifier exceeds the previous measured averaged current by 1A.
Rectifiers send this alarm to EC500.
Rack Fan Fail The fan tacho signal is sampled at the rate of 20us and averaged for 65536
samples. If averaged value is less than 0.3V and greater than 2.57V for 13
seconds continuously, then fan fail will be activated. EC500 activates this
after receiving it from rectifier for 17 seconds.
Rec Proc Mode This alarm is generated in the rectifier with a delay of 10ms (one AC cycle)
when input Mains frequency of rectifier less than 44Hz and greater than
66Hz. EC500 receives this and wait for 60 seconds to activate this alarm.
System Overload This alarm is generated when system current (summation of load and all
battery current) exceed the system overload alarm threshold (Normally 105%
of system capacity) for the duration of 10 seconds. This alarm will be latched
if System Overload alarm latch enable is “Set”.
DC Over Voltage This alarm is generated when bus voltage exceed the DC Overvoltage Alarm
Threshold for the duration of 10 seconds.
This alarm will be latched if DC Overvoltage alarm Latch Enable is set.
DC Low Voltage This alarm is generated when Bus voltages becomes lower than the DC
Voltage Low Alarm Threshold and more than 30V for the duration of 5
seconds.
LLVD-n Disconnect The alarm is generated by EC500 when Bus Voltage becomes lower than DC
Under Voltage Alarm Threshold and more than 30V for the duration of 5
seconds. These alarm thresholds can be different value for all n channels.
BLVD Disconnect This alarm is generated by EC500 when Bus voltage becomes lower than
Battery Low Voltage Disconnect (BLVD) Alarm threshold and more than 30V
for the duration of 5 seconds.
This alarm also triggers the battery contactors for battery LVD operation with
no delay.
Batt Bank Dischg. This alarm is generated when any battery current becomes lower than the
Battery Discharge Current Threshold (1%) in percentage of Battery Capacity
and Bus Voltage also becomes lower than Battery Discharge Voltage Alarm
Threshold (52V) for the duration of 15 seconds.
MBD (Mains ON Batt This alarm is generated when Battery Bank Discharge Alarm present and
Dischg.) Mains Fail alarm is not present or in other words if at-least one phase is OK
for duration of 120 seconds.
Temp Comp CBL Fail Temperature Compensation Cable Fail alarm is generated when Battery
Temperature becomes less than -25°C for the duration of 10 seconds.
Batt n Reverse This alarm is generated when the Battery Voltage becomes lower than
-20V for the duration of 10 seconds.
Batt n Fuse Fail This alarm is generated when any of the below mentioned condition is
present for the duration of 10 seconds:
1. Bus Voltage is more than the addition value of Battery Voltage and
Battery Fuse Fail Alarm Threshold.
2. Bus Voltage is less than the subtraction value of Battery Voltage and
Battery Fuse Fail Alarm Threshold.
Batt n Not Present This alarm is generated when Bus Voltage is less than 20V for the duration of
10 seconds.
Rack Temp1 Low This alarm is generated when Rack Temperature 1 becomes lower than Rack
Temperature 1 Low Alarm Threshold for the duration of 10 seconds.
Rack Temp2 Low This alarm is generated when Rack Temperature 2 becomes lower than Rack
Temperature 2 Low Alarm Threshold for the duration of 10 seconds.
Rack Temp1 High This alarm is generated when Rack Temperature 1 exceeds than Rack
Temperature 1 High Alarm Threshold for the duration of 10 seconds.
Rack Temp2 High This alarm generates when Rack Temperature 2 exceeds than Rack
Temperature 2 High Alarm Threshold for the duration of 10 seconds.
Rack Fan Fail This alarm is generated when the Fan Fail Alarm is continuously detected for
10 seconds, provided Fan is in running condition.
DCIF Comm. Fail This alarm is generated when no communication packet from DCIF is received
by EC500 for continuously 5 seconds. This alarm clear all the parameters
related to DCIF.
S-Chg. Comm. Fail Solar charger communication fail is generated whenever any solar charger
does not respond to EC500 request for communication for the duration of 15
seconds.
RTC Fail When the Real Time Clock’s second does not change for the duration of 10
seconds then RTC fail alarm is declared.
CONNECTOR PIN-OUTS
SYSTEM CONTROLLER CONNECTOR PIN-OUTS
3 Tx
4 -
5 -
6 Tx
7 -
8 -
USB USB USB Serial Interface 1 VCC (+5V dc), max 100mA
Type A
2 Data -
3 Data +
3 -
5 -
6 -
7 0V, Reference
3 -
5 -
6 -
7 0V, Reference
5 -
6 Tx- (Out)
7 0V, Reference
3 Tx+ (Out)
5 -
6 Tx- (Out)
7 0V, Reference
3 -
4 CTS
6 RTS
8 RxD (In)
9 -
5 -
6 -
7 0V, Reference
X2, Upper DB9F Relay drives for Potential Free 1 +15V DC, protected power output
outputs.
2 Relay Drive 2
Use a 1:1 cable for connecting
to PFC 8 IO Board 3 Relay Drive 4
4 Relay Drive 6
5 Relay Drive 8
6 Relay Drive 1
7 Relay Drive 3
8 Relay Drive 5
9 Relay Drive 7
X2, Lower DB9M Potential Free inputs. Use a 1 0V, Common for PFC input
1:1 cable for connecting to PFC (Protected)
8 IO Board
2 PFC IN 2
3 PFC IN 4
4 PFC IN 6
5 PFC IN 8
6 PFC IN 1
7 PFC IN 3
8 PFC IN 5
9 PFC IN 7
5 Isolated 5V
6 -
7 0V, Reference
3 TX1+
6 TX1-
7 0V, Reference
3 TX2+
4 ISOGND_EXT
6 TX2-
7 0V, Reference
3 Contactor3+
4 Common1
5 -
6 -
3 Battery Voltage – 2
4 Battery Voltage – 3
2 Battery Voltage – 4
3 Battery Voltage – 5
4 Battery Voltage – 6
TB1 24-Pin Male, PFC Output 1,3,5 1st Relay – Pole, NC, NO
6,5 0V – D3 Input
8,7 0V – D4 Input
10,9 0V – D5 Input
12,11 0V – D6 Input
14,13 0V – D7 Input
16,15 0V – D8 Input
3 3.3V Protected
4 Temperature – 2 Input
4 Current Input 3-
5 Current Input 2+
6 Current Input 2-
7 Current Input 1+
8 Current Input 1-
SUPPORT
For product information and a complete listing of sales offices, visit Eaton’s website at: dcpower.eaton.com, or
email dcinfo@eaton.com