You are on page 1of 4

Type: ESR4−NV3−30

Article No.: 214616


Sales text Safety relay delayed 24VDC

Ordering information
Actuating voltage Uc 24V DC
Dual−channel, Off−delayed,
Description
0.15 – 3 s
Category to EN 954−1 4 (non−delayed) 3 (delayed)
Number of enabling paths to IEC/EN
60204 Stop category
0 2
13062006 1

Approval

General
IEC/EN 60947, VDE 0660,
Standards IEC/EN 60255, UL, CSA, EN
954−1
Lifespan, mechanical Operations × 106 10
Maximum operating frequency
Max. operating frequency Ops/h 3600
Climatic proofing Cold to: EN 60068−2−1, dry
heat to: EN 60068−2−2,

1
temperature change to: EN
60068−2−14, Damp heat to:
EN 60068−2−30
Ambient temperature °C ... 25...+55
Ambient temperature, Storage °C ... 25...+75
Mounting position As required
5 g, frequency: 10 – 55 Hz,
Vibrations (IEC/EN 60068−2−6)
amplitude: 0.35 mm
Degree of protection
Enclosures IP40
Terminals IP 20
Protection against direct contact Finger− and back−of−hand
when actuated from front (IEC 536) proof
Weight kg 0.2
Terminal capacities
1 × (0.14 – 2.5)
Solid core or stranded mm2
2 × (0.14 – 0.75)
1 × (0.25 – 2.5)
Flexible with ferrule mm2
2 × (0.25 – 0.5)
Solid or stranded AWG 18...16
Terminal screw
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.6 × 3.5
Max. tightening torque Nm 0,6
Main conducting paths
Rated impulse withstand voltage Uimp V AC 4000
Overvoltage category/pollution
degree
outside III/3
inside III/2
Rated insulation voltage Ui V AC 300
Rated operational voltage Ue V AC 230
Rated operational current
AC–15
230 V (3600 ops./h) Ie A 4
DC−13
24 V (360 Ops./h) Ie A 5
Max. summation current of all poles
24 V AC/DC devices A 12
Short−circuit protection

2
A
max. fuse 6
gG/gL
Power supply circuit
Actuating voltage 50/60 Hz V AC 24
Actuating voltage Us V DC 24
Voltage tolerance, Pick−up × Ue 0,85...1,1
Power consumption
DC operated W 2,5
Fuse for control circuit supply
24 V PTC resistor
Control circuit
Rated output voltage V DC 24
S12, S22, S31: 25; S34, S35:
Rated current mA
40
Max. resistive load of the cable R 70
Short−circuit current A 2,2
Response time ms 2000
Recovery time ms 3000
Response time with reset monitoring tA1 ms 30
Response time without reset
tA2 ms 700
monitoring
Reset time tR/tR1 ms 25/adjustable
Minimum contact closing time tM ms <200
Recovery time tW ms Approx.500
Synchronous monitoring time tS ms > 100, < 500
Electromagnetic compatibility (EMC)
to EN 50081−1 and EN
Emitted interference
50081−2
Interference immunity EN 50082−2

Dimensions

3
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn
E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net
HPL−C2007G V2.1 © 2007 by Moeller GmbH