Extract Fans 8 NOS
H-O-A switch auto position 8 Volt Free Contact to DDC
Fan Start/Stop command 8 Realy Output
Fan VFD speed control command. 8 0-10 VDC Signal from DDC
Fan VFD speed feedback. 8 0-10 VDC Signal to DDC
Fan VFD trip alarm. 8 Volt Free Contact to DDC
Fan runs status. 8 From Duct differential pressure switch
Chiller - 2 NOS
Common supply temperature. 1
Common return temperature. 1
Compressor status 2
Chiller outlet temperature. 2
BFV command and feedback 2 2 Software Integration
Chiller Command 2
Chiller run status 2
Chiller trip status 2
HOA Status 2
FCU 47 NOS
Monitoring of space temperature
Speed Command Communicable thermostat for FCU
Remote Temperature reset.
P O Box: 8886 Sharjah UAE Tel: +971 6 5981 999 Fax: +971 6 5981 900 Email: sales@gamaengg.com 2 of 4
Water Feature System pumps 2 Nos
Pump start/stop command 2 Relay Output
HOA switches position indication. 2 Volt Free Contact to DDC
Run status of each pump. 2 Volt Free Contact to DDC
Trip alarm indication of individual pump. 2 Volt Free Contact to DDC
Air curtain
Power status 5 Volt Free Contact to DDC
Fault status 5 Volt Free Contact to DDC
Revolving Door
Power status 1 Volt Free Contact to DDC
Fault status 1 Volt Free Contact to DDC
Emergency circuit
Power healthy status 1 Volt Free Contact to DDC
Fault status 1 Volt Free Contact to DDC
AV System
Power healthy status 1 Volt Free Contact to DDC
Fault status 1 Volt Free Contact to DDC
PA/BGM System
Power healthy status 1 Volt Free Contact to DDC
Fault status 1 Volt Free Contact to DDC
MSFD 10 No
Damper open/close status 10 Volt Free Contact to DDC
Lifts
Healthy status. 8 Volt Free Contact to DDC
P O Box: 8886 Sharjah UAE Tel: +971 6 5981 999 Fax: +971 6 5981 900 Email: sales@gamaengg.com 3 of 4
Cabin call alarm 8 Volt Free Contact to DDC
Run status 8 Volt Free Contact to DDC
LV Main Switchgear
ON/OFF status of main incoming breakers. 4 Volt Free Contact to DDC
Trip alarm of main incoming breakers. 4 Volt Free Contact to DDC
CCTV System
All system alarms. 1 Volt Free Contact to DDC
Common fault alarm. 1 Volt Free Contact to DDC
Power ON/OFF status. 1 Volt Free Contact to DDC
PA System
Run status. 1 Volt Free Contact to DDC
System alarm. 1 Volt Free Contact to DDC
Trip alarm indication. 1 Volt Free Contact to DDC
Solar PV system
Healthy status 1 Volt Free Contact to DDC
Fault status 1 Volt Free Contact to DDC
Foam System
Operational status. 1 Volt Free Contact to DDC
System discharged. 1 Volt Free Contact to DDC
Common fault alarm. 1 Volt Free Contact to DDC
Motorized relief damper. 1 Volt Free Contact to DDC