of Personnel Competence
(CoPC) for Explosive
Atmospheres
Assessment Requirements
IECEx “Unit
Verification” Cert.
❑ Knowledge
❑ Skills
Philosophy of the IECEx CoPC
OD (Operational Documents)
Typical reference documents used, please check applicable unit of competency required
Scope of
Authorisation
List of Units of Competence
Limitation of Scope
Examples of Units of Competence to be
gained
Summary of Prerequisite Units and
Recommended General Competence
Some Units Need Practical Assessment
❑ Unit Ex 002 : zone classification in Gas and in Dust area.
❑ Unit Ex 003 : installation of equipment as ‘d’ enclosure, ‘e’ terminal
box and intrinsic safety barriers by following wiring diagram
❑ Unit Ex 004 : maintenance of installation by doing the preparation,
check and reporting
❑ Unit Ex 005 : repair of a motor
❑ Unit Ex 006 : installation testing by doing the preparation, testing
and reporting
❑ Unit Ex 007 : visual inspections by doing the preparation,
conducting visual inspections and reporting
❑ Unit Ex 008 : detailed inspections by doing the preparation,
conducting detailed inspections and reporting
❑ Unit Ex 009 : installation design by interpreting area classification,
selecting equipment and wiring systems and checking equipment
certification for suitability
❑ Unit Ex 010 : audit inspection by doing all previous practical
assessment
Assessment
SCOPE PREREQUISITES
❑ Safety obligations ❑ This unit would be used in relation
❑ Basic knowledge of persons to any job function that may be
entering a site that has been performed in or associated with
classified hazardous areas. hazardous area
❑ Nature of hazardous areas ❑ Does not require any specific
prerequisites.
❑ Limitations on devices that may be
taken into a hazardous area
❑ OSH responsibilities and
procedures related to hazardous
areas.
❑ Does not include requirements for
ensuring the explosion protection
aspects of plant and machinery.
Unit Ex 000 : Elements for Assessment
SCOPE PREREQUISITES
❑ Covers basic principles of ❑ No minimum level of technical
protection in explosive education applicable
atmospheres of plant and ❑ Shall be assessed in combination
machinery. with, or after gaining other
❑ This unit of competence is based competence required by a given
on various parts of IEC 60079 industry or enterprise for plant or
series. machinery operation or
installations, maintenance or
service functions.
Unit Ex 002 : Perform classification of hazardous areas
SCOPE PREREQUISITES
❑ Covers knowledge and skills to ❑ Degree, diploma or equivalent in a
classify areas where explosive technical subject.
hazards may exist. ❑ Should be carried out by those who
❑ Requires ability to gather and understand the relevance and
analyse data relative to explosion significance of properties of
hazards, determine the extent of flammable materials and those who
risk and establish and document are familiar with the process and
zones the equipment along with safety,
❑ Based on IEC 60079-10-1 and IEC electrical, mechanical and other
60079-10-2 and any other relevant qualified engineering personnel.
standard
Unit Ex 003 : Install explosion-protected equipment and wiring
systems
SCOPE PREREQUISITES
❑ Covers the explosion-protection ❑ Technical education relevant to the
aspects for installing explosion- application, through documents
protected and associated such as College Certificates and
equipment and wiring systems. Vocational qualifications etc.
❑ Requires the ability to match ❑ Minimum 3 years experience in
equipment with that specified for a industrial electrical installation
given location, work safely, and to practice.
installation Standards and ❑ For Responsible Person minimum
complete the necessary installation 3 years experience in Ex industrial
documentation. electrical installation practice.
❑ Assessment is based on IEC ❑ Assessed either concurrently with
60079-14 and any other relevant or after Unit Ex 001
standards.
❑ Installation all types of protection
shall be understood.
Unit Ex 004 : Maintain equipment in explosive atmospheres
SCOPE PREREQUISITES
❑ Covers explosion-protection ❑ Technical education relevant to the
aspects for maintaining explosion- application, through documents
protected and associated such as College Certificates and
equipment and wiring systems Trade Credentials etc.
including plant maintenance. ❑ Minimum 3 years experience in
❑ Ability to develop and manage industrial maintenance practice.
maintenance programs ❑ For Responsible Person minimum
incorporating strategies for 3 years experience in Ex
inspections, repair / overhaul / maintenance practice.
replacement of components and
❑ Assessed either concurrently with
recording of outcomes.
or after Unit Ex 001
❑ Based on IEC 60079-17 and any
other relevant standards
Unit Ex 005 : Overhaul and repair of explosion-protected
equipment
SCOPE PREREQUISITES
❑ Covers the explosion-protection ❑ Technical education relevant to the
aspects of overhauling and application, through documents
repairing explosion-protected such as College Certificates and
equipment Trade Credentials etc.
❑ Operative requires ability to ❑ For Operative minimum 3 years
identify / select authorized experience in the overhaul and
components, follow specifications repair of general electrical,
and complete documentation. electronic and / or mechanical
❑ Responsible Person requires equipment relevant to the scope
ability to establish / document the ❑ For Responsible Person minimum
level of work required, arranging 3 years experience in the servicing
for overhaul/repair to be carried of Ex electrical, electronic and/or
out, verify compliance of mechanical equipment relevant to
overhauled/repaired equipment and the scope of the unit of
complete the documentation. competence being applied
❑ Based on IEC 60079-19 and any
other relevant standards
Unit Ex 006 : Test electrical installations in or associated with
explosive atmospheres
SCOPE PREREQUISITES
❑ Covers testing electrical ❑ Technical education relevant to the
installations for explosive application, through documents
atmospheres. such as College Certificates and
❑ Requires ability to select, prepare Trade Credentials etc.
and use appropriate testing ❑ Minimum 3 years experience in
devices, work safely and to industrial electrical installation
Standards and to interpret and practice.
record test results. ❑ Assessed either concurrently with
❑ Based on IEC 60079-14 and any or after Unit Ex 001
other relevant standards that may
apply.
Unit Ex 007 : Perform visual and close inspection of electrical
installations in or associated with explosive atmospheres
SCOPE PREREQUISITES
❑ Covers evaluating the ❑ Technical education relevant to the
completeness of verification application, through documents
dossier and compliance of the such as College Certificates and
explosion-protected aspects of the Trade Credentials etc
electrical installations. ❑ For Operative a minimum 3 years
❑ Requires ability to work safely in a experience in industrial electrical
hazardous area, evaluate a installation practice.
verification dossier, identify ❑ For Responsible Person a
explosion-protected equipment minimum 3 years experience in Ex
with their certification and electrical installation practice
specified location, inspect an relevant to the scope of the unit of
installation for compliance and competence being applied for
report and act on inspection taking into account the scope
results. limitations.
❑ Based on IEC 60079-14 and IEC ❑ Assessed either concurrently with
60079-17 and any other relevant or after Unit Ex 001
standards that may apply.
Unit Ex 008 : Perform detailed inspection of electrical
installations in or associated with explosive atmospheres
SCOPE PREREQUISITES
❑ Covers explosion-protection ❑ Technical education relevant to the
aspects of conducting initial, application, through documents
periodic and sample audit such as College Certificates and
inspections of explosion-protected Trade Credentials etc.
equipment and installations. ❑ For an operative a minimum 3
❑ Requires the ability to audit a years experience in general
verification dossier, work safely in electrical installation practice.
a hazardous area, inspect against ❑ For a responsible person a
Standards and report and act on minimum 3 years experience in
inspection results. Hazardous Area installation
❑ Based on IEC 60079-14 and IEC practice.
60079-17 and any other relevant ❑ Assessed either concurrently with
standards that may apply. or after Unit Ex 001
Unit Ex 009 : Design electrical installations in or associated
with explosive atmospheres
SCOPE PREREQUISITES
❑ Covers the explosion-protection ❑ Technical education relevant to the
aspects of designing electrical application, through documents
power, control and instrumentation such as Degree, Diploma and
systems and installations. College Certificates etc
❑ Requires ability to establish design ❑ Minimum 3 years experience in
briefs and to pursue economical general electrical installation
and effective explosion-protection design or supervised Hazardous
design solutions. Area installation design.
❑ Based on IEC 60079-14 and any ❑ Assessed either concurrently with
other relevant standards that may or after Unit Ex 001
apply.
Unit Ex 010 : Perform audit inspection of electrical
installations in or associated with explosive atmospheres
SCOPE PREREQUISITES
❑ Covers the explosion-protection ❑ Technical education relevant to the
aspects of conducting an audit of application, through documents
an electrical installation. such as Degree, Diploma, College
❑ Requires the ability to verify Certificates, Trade Credentials
whether an installation complies etcetera.
with the relevant hazardous area ❑ Minimum 3 years experience in
Standards for that installation and general electrical installation or
includes the verification of design inspection practice,
and certification documentation ❑ Minimum of 2 years experience in
(verification dossier), maintenance, Hazardous Area electrical
overhaul and repair, work safety, installation inspection practice.
inspection against Standards and
❑ Assessed either concurrently with
reporting of audit results.
or after Units Ex 002, Ex 008 and Ex
❑ Based on IEC 60079-14 and IEC 009.
60079-17 and any other relevant
standards that may apply.
Summary of essential knowledge and associated skills for each
Unit of Competence
Summary of essential knowledge and associated skills for each
Unit of Competence
Summary of essential knowledge and associated skills for each
Unit of Competence
Summary of essential knowledge and associated skills for each
Unit of Competence
APPLICATION CHECKLIST DESCRIPTION
❑ All pages of the application form completed (including payment information and selected schedule)
❑ Valid e-mail address included
❑ Valid telephone number included
❑ Resume with details of work experience associated with Hazardous Areas and Non-Hazardous Areas.
Please provide details of employer(s) or client(s) for verification.
❑ Letter of Current Employment
❑ Copy of Degree / Diploma / Certificate
❑ Copy of training records related to Hazardous Areas
❑ Copy of Government issue Identification Document eg Mykad, International Passport etc. Please cross,
with the word -IECEX COPC-
❑ Current Passport size portrait photograph, in colour and with a white background in electronic .jpg
format 150 X 200 pixels. Please send it to : ask.pci@sirim.my (Subject : Applicant Name)
❑ Evidence of assessment fee payment transaction eg. Cheque, payment slip etc
❑ Copy of completed application documents for your records
NOTE :
All documentation such as resume, certificates, identification document etc to be reviewed / endorsed / certified by current
employer, notary public or commissioner of oaths (pesuruhjaya sumpah)
CERTIFICATION PROCESS
Inquiry • Quotation
Application + • Complete
supporting
Payment documents
Documents • Education,
Qualification,
validation Experience, Training
< 2 weeks
• Acceptance of
Exam application
notification
> 1 month • Exam schedule
Assessment
2 ~ 3 weeks
Independent
Review &
CER
Online
Certificate
Example of
CoPC
(New Entrant)
Ex05
IECEx Scheme
for Certification
of Personnel
Competence for
Explosive
Atmospheres
Example of
CoPC
(Experienced)
Ex05
IECEx Scheme
for Certification
of Personnel
Competence for
Explosive
Atmospheres
Example of IECEx CoPC ID Card
United Nations Endorsement of IECEx
Full Text
http://www.unece.org/press/pr2011/11trade_p03e.htm