Honeywell Security Facility Information Enter Standby and Alarm Times
Contigency
Factor
Battery & Power Budget Calculator Location: Battery Standby (hours): 24
© 2003-2014 Honeywell International Inc. All Rights Reserved Account #: Alarm Duration (minutes): 5 10%
Apply UL Power Limits? (Required to maintain UL Listing Model:
including UL864) Engineer: Recommended
Commercial Fire Installation 9.6
Date: Battery (AH)
Commercial Burg Installation Recommended Battery Capacity OK for 48-Hr Recharge ###
###
###
SELECTED PANEL MAXIMUM OUTPUT RATINGS ###
Commercial
Select Panel from pulldown list: Power (mA) (mA) (mA) used; mA) Panel
SN
VISTA-32FBPT 128 1000 1700 300 470 1700 1700 1300 2800 34.4
###
###
######
###
Total Standby Total Alarm
Calculated Current Draw 0 40 120 Calculated Bell Draw 0 0 40 120
Standby Budget Alarm Budget
Power Budget 128.0 960.0 1580.0 Bell Power Budget 1700.0
Current 1700.0 1260.0 2680.0
Current OK Current OK Current OK OK Current OK Current OK
External Bell Power Req'd (mA): 0.0 Ext. UL Power Req'd (mA): 0.0
Remove Unused Devices From List ###
Grayed-out device(s) are not supported by selected panel
Unit Selection
Panel Max Output Exceeded if highlighted
Actual
Ohms per Alarm Current Resistance Voltage Drop
12V AUX POWER AND BELL CIRCUIT WIRE RUN DATA
Feet
Units
#16Wire
AWG Stranded1000 ft
Gauge(AWG) Draw (mA) Run Length (twin leads) Voltage At EOL (Percent)
Panel Aux Power Wire Run (twin lead) 5.29 120.00 30 0.32 11.96 0.32 ###
Feet #14 AWG Stranded
Panel Bell 1 Wire Run (twin lead) 3.26 0.00 60 0.39 12.00 0.00 ###
Feet <Select Wire Gauge>
Panel Bell 2 Wire Run (twin lead) 0.00 0 0 0.00 12.00 0.00 ###
Unit Selection
PS24 POWER SUPPLY MODULE, MAXIMUM CAPACITIES ###
Output B
Panel 12V Panel 12V Output A Output A Output B PS24 PC Maximum Total Maximum Total Max. Battery
Alarm
Standby (mA) Alarm (mA) Standby (mA) Alarm (mA) Standby (mA) Board (mA) Standby Output Alarm Output Capacity
(mA)
Using PS24 to back up Control Panel 340 590 570 1700 570 1700 40 610 4180 34.4
###
Total Standby Total Alarm
Equivalent panel load @ 24V 0.0 0.0 0 0 0 0 40 40 40
(converted to 12VDC from 24V full-wave) Standby Budget Alarm Budget
Power Budget 340.0 590.0 570.0 1700.0 570.0 1700.0
Current 570.0 4140.0 34.4
Output Selection
OK 0 Current OK Current OK
Device
24V NOTIFICATION APPLIANCES Enter Which PS24 Standby Load Device Alarm Subtotal A Subtotal A
Enter Device Names & Specifications Quantity Output? (MA) Load (MA) Standby Alarm Subtotal B Standby Subtotal B Alarm
Unit Selection
Total Alarm Actual
Ohms per Current Draw Resistance Voltage Drop
24V BELL CIRCUIT WIRE RUN DATA Units Wire Gauge(AWG) 1000 ft (mA) Run Length (twin leads) Voltage At EOL (Percent)
PS24 Output A Wire Run (twin lead) Feet <Select Wire Gauge> 0.00 0.00 0 0.00 24.00 0.00 ###
PS24 Output B Wire Run (twin lead) Feet <Select Wire Gauge> 0.00 0.00 0 0.00 24.00 0.00 ###