Chapter 16 Applications of Displacement Ventilation 16.

2 Organizations for Healthy Schools

Better buildings, Better students.

CH16-2 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-3
Chapter 16 Applications of Displacement Ventilation 16.3 Benefits of Displacement Ventilation

• Sustainable Sites – 19 Points Possible


• Water Efficiency – 11 Points Possible
• Energy and Atmosphere – 33 Points Possible
• Materials and Resources – 13 Points Possible
• Indoor Environmental Quality – 19 Points Possible
• Innovation in Design – 6 Points Possible
• Regional Priority – 4 Points Possible

Table 16.1: Summary of LEED 2009 school rating for new construction and major renovations

Occupied
Zone

Mixing Venti
Ventilation
tiilation Displacement Ventilation

CH16-4 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-5
Chapter 16 Applications of Displacement Ventilation 16.3 Benefits of Displacement Ventilation

Maximum Significant Minimal

CH16-6 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-7
Chapter 16 Applications of Displacement Ventilation 16.3 Benefits of Displacement Ventilation

14 New ventilation system (DV)


12 No new ventilation system

10

0
Pollen/pet Asthma Current Any asthma More asthma
allergy ever asthma symptoms symptoms in
‘95 than ’93

CH16-8 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-9
Chapter 16 Applications of Displacement Ventilation 16.3 Benefits of Displacement Ventilation

61.5% Asthma Allergies


85.0% Colds
% Improvement / Reduction in Symptoms

87.3% Flu

72.5% Asthma
100%

67.0% SBS

46.0% Respiratory
20%

47.0% SBS
23.5% Headache
20%

20.0% Respiratory
35.0% SBS

20.0% Headache
35.0% SBS

32.0% SBS

23.6% Asthma

21.4% Asthma

13.5% Asthma
15.0% Colds
20%

20%

0
Increased Outside Air Individual Moisture Pollutant Source Controls 70 Reading
Cont. / Task Air Control 64.4 64.5
61.8
56.3 Math
60
53.3
48.7 47.7 50.6

Score
50

40

30
<2.25 >2.25 & < 3.5 >3.5 & < 4.5 >4.5
Ventilation Rate (I/s person)

Noise

Dirty or opaque windows


Facility aspect

Inoperable windows

Lighting
Temperature

Indoor air quality

0% 20% 40% 60% 80%


Percent dissatisfied

CH16-10 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-11
Chapter 16 Applications of Displacement Ventilation 16.4 Displacement Ventilation in Schools: Typical Application

110

100

90

Average Score
80

70

60

50

40 79
40 45 50 55 60 65
77
Background Noise Level
75

73

71

Temperature (°F)
69

67
65

Classrooms Cafeterias and Kitchens

Laboratories Theaters and Lecture Halls

Gymnasiums Change and Training Rooms

Bathrooms Offices, Commons and Support Areas

CH16-12 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-13
Chapter 16 Applications of Displacement Ventilation 16.4 Displacement Ventilation in Schools: Typical Application

CH16-14 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-15
Chapter 16 Applications of Displacement Ventilation 16.4 Displacement Ventilation in Schools: Typical Application

CH16-16 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-17
Chapter 16 Applications of Displacement Ventilation 16.5 Diffuser Type, Layout and Location

CH16-18 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-19
Chapter 16 Applications of Displacement Ventilation 16.5 Diffuser Type, Layout and Location

CH16-20 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-21
Chapter 16 Applications of Displacement Ventilation 16.5 Diffuser Type, Layout and Location

CLASSROOM

25 ft

Windows

30 ft

CH16-22 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-23
Chapter 16 Applications of Displacement Ventilation 16.5 Diffuser Type, Layout and Location

DR90 DR90

79

77

75

73

71

Temperature (°F)
69

67
65

CH16-24 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-25
Chapter 16 Applications of Displacement Ventilation 16.5 Diffuser Type, Layout and Location

3.0

2.5

2.0

Ventilation Effectiveness
100
90 1.5
80
1.0
70
60 0.5
50
0.0
40
Velocity (ft/min)

30
20
10
0

30

25

20

15

10

5
DR (%)

DLE-H

CH16-26 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-27
Chapter 16 Applications of Displacement Ventilation 16.5 Diffuser Type, Layout and Location

30

25

20

15

10

DR (%)
0

79

77

75

73

71
Temperature (°F)

3.0
69
2.5
67
65 2.0

Ventilation Effectiveness
1.5

1.0

0.5

0.0

80
70
60
50
40
30
Velocity (ft/min)

20
10
0

CH16-28 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-29
Chapter 16 Applications of Displacement Ventilation 16.5 Diffuser Type, Layout and Location

CLASSROOM qoz = (26 People x 75 W) + (3 Computers x 90 W) = 2220 W


ql = 70 m² x 20 W/m² = 1400 W
qex = 27.9 m² x 45 W/m² = 1250 W
7.6 m qT = 4870 W

Windows

9.1 m

CH16-30 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-31
Chapter 16 Applications of Displacement Ventilation 16.6 Displacement Ventilation in Theaters

CH16-32 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-33
Chapter 16 Applications of Displacement Ventilation 16.6 Displacement Ventilation in Theaters

Velocity (ft/min)

100
10
20
30
40
50
60
70
80
90
0
Fresh Air

Fresh Air Temperature (˚F)

65

68

71

74

76

79

82
85
CH16-34 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-35
Chapter 16 Applications of Displacement Ventilation 16.6 Displacement Ventilation in Theaters

100
Neck Region
Feeling of
80 Coolness

Air Velocity, fpm


60

40%
30%
20%
10%
40

Feeling of
20 Warmth

0
-7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5
Temperature Difference, °F

100
Ankle Region

40%
80

30%
Feeling of

Air Velocity, fpm


Coolness

20%
60

10%
40

Feeling of
20 Warmth

0
-7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5
Temperature Difference, °F

CH16-36 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-37
Chapter 16 Applications of Displacement Ventilation 16.6 Displacement Ventilation in Theaters

Elevation View Plan View

Return
Exhaust

Diffusers
Return
Diffusers

5
Middle
4

Height, m
Front
3

1
Back
0
18 19 20 21 22 23 24 25
Temperature, °C

CH16-38 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-39
Chapter 16 Applications of Displacement Ventilation 16.6 Displacement Ventilation in Theaters

4
Front
Height, m

3
Back
2
Middle
1

0
800 900 1000 1100 1200 1300 1400
CO2 concentration, ppm

Vertical Air
Ventilation
Spring Temperature Draft Ratio, %
Effectiveness
Difference, °C
Position 1m 1.7 m 0.1 m 0. 6 m 1.1 m 1.7 m 1.1 m 1.7 m
back, center 1.0 1.2 5 11 11 13 1.8 1.4
back, side 1.6 1.9 12 10 7 8 1.4 1.3
middle, center 0.7 0.9 4 0 12 9 1.6 2.1
front, center 0.6 1.0 13 4 8 8 10.8 5.7
front, side 0.7 1.5 17 9 9 3 8.4 3.5
Maximum 1.9 17 10.8
Minimum 0.6 0 1.3
Average 1.1 9 3.8

CH16-40 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-41
Chapter 16 Applications of Displacement Ventilation 16.6 Displacement Ventilation in Theaters

CH16-42 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-43
Chapter 16 Applications of Displacement Ventilation 16.6 Displacement Ventilation in Theaters

74 °F - 65 °F = 9 °F cooling.

CH16-44 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-45
Chapter 16 Applications of Displacement Ventilation 16.6 Displacement Ventilation in Theaters

23 °C to 18 °C = 5 °C cooling

CH16-46 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-47
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

WAITING ROOM

PATIENT ROOM

CH16-48 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-49
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

Couch
Supply Air Supply Air
Diffuser Diffuser
Partition

CH16-50 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-51
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

Occupied
Zone

Mixing Ventilation
Venti
tiilation Displacement Ventilation

CH16-52 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-53
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

tsupply(room#2) 65 °F
tsupply(room#3) 62 °F
qreheat(room#2) 2430 Btu/h
qreheat(room#3) 1701 Btu/h

CH16-54 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-55
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

Similarly,

The narrow range of supply air temperatures combined with the superior energy
recovery potential of displacement ventilation systems allows for the dramatic reheat
savings demonstrated by this example.

CH16-56 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-57
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

CH16-58 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-59
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

Adjust for new supply temperature


The supply temperature should be 5.5 °C less than tsp or 17 °C, whichever is higher.

Calculating the instantaneous reheat requirements for the room:


To warm the supply air from 17 °C to 18.5 °C:

Diffuser

People
Window

Return

PATIENT ROOM

CH16-60 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-61
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

1200 100 DV 2 μm Particles


90 Mixing 2 μm Particles
1000
80 DV 5 μm Particles
2 μm Particle Count

5 μm Particle Count
70 Mixing 5 μm Particles
800
60
600 50
40
400
30
20
200
10
0 0
-5 0 5 10 15 20 25 30
Time (min)

1200 100 DV 2 μm Particles 1200 100 DV 2 μm Particles


90 Mixing 2 μm Particles 90 Mixing 2 μm Particles
1000 1000
80 DV 5 μm Particles 80 DV 5 μm Particles
2 μm Particle Count

5 μm Particle Count

70 Mixing 5 μm Particles

2 μm Particle Count

5 μm Particle Count
800 70 Mixing 5 μm Particles
800
60 60
600 50 600 50
40 40
400 400
30 30
20 20
200 200
10 10
0 0 0 0
-5 0 5 10 15 20 25 30 -5 0 5 10 15 20 25 30
Time (min) Time (min)

CH16-62 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-63
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

R R

CH16-64 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-65
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

R R

1.20 Inlet Concentration


Exhaust Concentration
1.00
Normalized Concentration

Average BZ Concentration
Inlet Concentration - Reference
0.80
Exhaust Concentration - Reference

0.60 Average BZ Concentration - Reference

0.40

0.20

0.00
-1.0 0.0 1.0 2.0 3.0 4.0 5.0
Nominal Time Constant

CH16-66 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-67
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

CH16-68 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-69
Chapter 16 Applications of Displacement Ventilation 16.7 Displacement Ventilation and Health Care

Concentration1 Concentration1
[ppm] [ppm]
10
10

5
5

0
0

CH16-70 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-71
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

CH16-72 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-73
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

18 ft

14 ft

PATIENT ROOM

Corridor
5 ft

7 ft

CH16-74 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-75
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

IP IP

CH16-76 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-77
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

5.5 m

4.5 m

PATIENT ROOM

Corridor
1.5 m

2m

Return

10 in. x 10 in.
24 in. x 24 in. Transfer Grille
Wall Mounted Diffuser with Silencer
PATIENT ROOM

Corridor Exhaust

CH16-78 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-79
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

CH16-80 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-81
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

WAITING ROOM

20 ft

20 ft

Exhaust

250 mm x 250 mm
600 mm x 600 mm Transfer Grille
Wall Mounted Diffuser with Silencer
PATIENT ROOM

Corridor Exhaust

CH16-82 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-83
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

qoz = 3750 + 600 + 1000 = 5350 Btu/h


ql = 3600 Btu/h
qex = 0
qT = 5350 + 3600 = 8950 Btu/h

CH16-84 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-85
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

WAITING ROOM

Exhaust

Exhaust

CH16-86 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-87
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

WAITING ROOM

qoz = 1125 + 170 + 290 = 1585 W


ql = 1050 W
qex = 0
qT = 1585 + 1050 = 2635 W
6m

6m

CH16-88 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-89
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

SI

CH16-90 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-91
Chapter 16 Applications of Displacement Ventilation 16.8 Design Procedure

SI

WAITING ROOM

Exhaust

Exhaust

CH16-92 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-93
Chapter 16 Applications of Displacement Ventilation 16.9 Displacement Ventilation in Industrial Spaces

30.0
0.1 m above floor
27.0
1.7 m above floor
24.0
3.3 m above floor
21.0
Concentration, ppm

18.0
15.0
12.0
9.00
8.00
3.00
.000
.00 10. 20. 30. 40. 50. 60.
Time, min.

25.0
3.3 m above floor
22.5
1.7 m above floor
20.0
0.1 m above floor
17.5
Concentration, ppm

15.0
12.5
10.0
7.50
5.00
2.50
.000
.00 10. 20. 30. 40. 50. 60.
Time, min.

CH16-94 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-95
Chapter 16 Applications of Displacement Ventilation 16.9 Displacement Ventilation in Industrial Spaces

Height,
Height, m
m Mast
Mast AA Height,
Height, m
m Mast
Mast BB

25
25 25
25
Height, m Mast A Height, m Mast B
Local
Local air
air change
change index
index Local
Local air
air change
change index
index
20
20 20
20 25 25
Air
Air Temperature
Temperature Air
Air Temperature
Temperature
15
15 15
15 20 20

10
10 10
10 15 15

55 55 10 10
Supply
Supply Supply
Supply
Air
Air Temp
Temp Air
Air Temp
Temp
00 00 5 5
14
14 15
15 16
16 17
17 18
18 19
19 20
20 21
21 14
14 15
15 16
16 17
17 18
18 19
19 20
20 21
21
Temperature,
Temperature, °C
°C Temperature,
Temperature, °C
°C 0 0
0 2 4 6 8 10 12 14 16 0 2 4 6 8 10 12 14 16
00 11 22 33 44 00 11 22 33 44 Concentration of chromium compounds, μg/m Concentration of chromium compounds, μg/m
Local
Local Air
Air Change
Change Index
Index Local
Local Air
Air Change
Change Index
Index
0 0.2 0.4 0.6 0.8 1 0 0.2 0.4 0.6 0.8 1
Total concentration of particles, mg/m Total concentration of particles, mg/m

Cr(VI) Cr(III) Particles Cr(VI) Cr(III) Particles

CH16-96 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-97
Chapter 16 Applications of Displacement Ventilation 16.9 Displacement Ventilation in Industrial Spaces

Cooling Heating

Approx. 3 m

Approx. 3 m

Cooling Heating

CH16-98 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-99
Chapter 16 Applications of Displacement Ventilation 16.9 Displacement Ventilation in Industrial Spaces

Section View Plan View

Section View Plan View

Section View

CH16-100 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-101
Chapter 16 Applications of Displacement Ventilation 16.9 Displacement Ventilation in Industrial Spaces

qoz = (35 people × 375 Btu/h) + (33880 + 64390 + 31050 + 38180 + 30436 +
56610 Btu/h) = 267671 Btu/h
ql = 7920 ft² × 10.234 Btu/h/ft² = 81053 Btu/h
qex = (2670 ft² × .045 Btu/h/ft² °F × 18 °F) + (7920 ft² × .031 Btu/h/ft² °F × 18 °F)
= 6582 Btu/h
qT = 355306 Btu/h

CH16-102 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-103
Chapter 16 Applications of Displacement Ventilation 16.9 Displacement Ventilation in Industrial Spaces

Placed 10 ft Above Ground - Cooling


Unit Size Total Static
Face Vel, Air Flow,
(Face Pressure, in. Pressure, in. SPL, dBA
fpm cfm
Area) w.g. w.g.
75 870 0.156 0.115 45
14 100 1160 0.281 0.208 52
(11.6 ft2) 125 1450 0.445 0.330 59
150 1740 0.645 0.480 64
100 1470 0.214 0.171 53
18 125 1838 0.329 0.262 58
(14.7 ft2) 150 2205 0.467 0.370 62
175 2573 0.628 0.496 66
150 3090 0.249 0.198 56
25 175 3605 0.339 0.269 60
(20.6 ft2) 200 4120 0.441 0.350 64
225 4635 0.557 0.442 67

CH16-104 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-105
Chapter 16 Applications of Displacement Ventilation 16.9 Displacement Ventilation in Industrial Spaces

82.00

79.60

77.20

Temperature (°F) 74.80

72.40

70.00

1.67

1.33

1.00

0.67
Velocity (ft/s)

0.33

0.00

1.67

1.33

1.00
Draft Temperature (˚F)

0.67

0.33

0.00

CH16-106 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-107
Chapter 16 Applications of Displacement Ventilation 16.9 Displacement Ventilation in Industrial Spaces

qoz = (35 people × 110 W) + (16590W + 8920 W + 11190 + 9100 W + 18870 +


9930 W) = 78450 W
ql = 734m² × 32.284 W/m2 = 23696 W
qex = (249 m2 × 0.256 W/m2K × 10 K) + (734 m2 × 0.176 W/m2K × 10 K) = 1929 W
qT = 104075 W

CH16-108 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-109
Chapter 16 Applications of Displacement Ventilation References

AHRI (2008). AHRI standard 885-2008: Procedure for estimating occupied space
sound levels in the application of air terminals and air outlets. Arlington,
VA: Air-Conditioning, Heating, and Refrigeration Institute.

ASHRAE (2002). Standard 129-1997 (R2002)—Measuring air-change effectiveness.


Atlanta, GA: American Society for Heating, Refrigerating and Air
Conditioning Engineers.

ASHRAE (2007). Standard 62.1-2007—Ventilation for acceptable indoor air


quality. Atlanta, GA: American Society for Heating, Refrigerating and Air
Conditioning Engineers.

ASHRAE (2008). Standard 170-2008—Ventilation of health care facilities. Atlanta,


GA: American Society for Heating, Refrigerating and Air Conditioning
Engineers.

ASHRAE (2009a). ASHRAE handbook—Fundamentals. Atlanta, GA: American


Society for Heating, Refrigerating and Air Conditioning Engineers.

ASHRAE (2009b). ASHRAE research project-1373—Air distribution effectiveness


with stratified air distribution systems. Atlanta, GA: American Society for
Heating, Refrigerating and Air Conditioning Engineers.

ASHRAE (2010a). Addendum G to Standard 170-2008—Ventilation of health care


facilities. Atlanta, GA: American Society of Heating Refrigeration and Air-
Conditioning Engineers.

ASHRAE (2010b). Standard 55-2010—Thermal environmental conditions for


human occupancy. Atlanta, GA: American Society for Heating,
Refrigerating and Air Conditioning Engineers.

Bakó-Biró, Z., Kochhar, N., Clements-Croome, D.J., Awbi, H.B., & Williams, M.
(2007). Ventilation rates in schools and learning performance. Proceedings
from Clima 2007 WellBeing Indoors. Helsinki.

Berube-Dufour, M., Derome, D., & Zmeureanu, R. (2008). In situ assessment of the
air distribution in a room with a displacement ventilation system at the
Auberge Saint-Antoine (field study report). Sustainable Buildings &
Communities, Natural Resources Canada.

Breum, N. O., Helbo, F., & Laustsen, O. (1989). Dilution versus displacement
ventilation—An intervention study. Annuals of Occupational Hygiene, 33
(3), 321-329.

CH16-110 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-111
Chapter 16 Applications of Displacement Ventilation References

CH16-112 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-113
Chapter 16 Applications of Displacement Ventilation References

CH16-114 © Copyright Price Industries Limited 2011. Errata reprint 2016. © Copyright Price Industries Limited 2011. Errata reprint 2016.
CH16-115
END OF CHAPTER 16

APPLICATIONS OF
DISPLACEMENT VENTILATION

Take the chapter quiz to earn


6.0 PDH CREDITS
START

Visit www.priceindustries.com for the latest updates.