and control
Sepam range
Sepam 100 RT
contents page
presentation 2
connection 4
characteristics 6
installation 7
ordering information 8
reset
sepam 100
S01 RT
2
parameter setting Access to and identification of
microswitches SA-1 and SA-2.
The parameters of the 2 "alarm" inputs
made be set so as to make them "tripping"
inputs.
"Alarm" inputs In1 and In2 may be set
individually as "tripping" inputs. SA-2
The choice is made via two microswitches SA-1
that are accessible on the left-hand side of
Sepam 100 RT.
Access to the microswitches is closed off
by a removable plastic cover.
The plastic cover should be replaced after
the setting has been made. Parameter setting
"Alarm" position.
Move the microswitch tab to the left.
"Tripping" position
Move the microswitch tab to the right.
S
SA - 2 1
R In2
13
In3
S
1
R In3
14
In4
S "tripping"
1 inputs
R In4
15
In5
S 1
R In5
21
1
reset out
20
1
1 A
8
O1
reset PB 7
6 tripping
O2 outputs
5
4
1A O3
1 3
+
aux. on
sup. 2 1 B
- 4
3 power
O6 on
2
1 output
3
connection
4 17
3 16
1A 8 2 – 15
O1 0 A 21
7 tripping 20 reset 1 + 14
O2 6 19 A 13
5 annunciation 18 12
O3 4 17
220-240VAC
inhibit 11
3 closing 16 inputs
10
2 15
220-240VAC
– aux In5
1 14 9
+ supply In4
220-250VDC
100-127VAC
13 8
In3
100-127VAC
12 P
In2 7
11 In1 1B
6
48-125VDC
10
220-250VDC
common
9 B 5
8 4 4
05
48-125VDC
7
24-30VDC
alarm 2 3 3
6 output
O6 2 2
5
24-30VDC
1B 4 1 1
4
3 04 3
power on alarm 1 B A
2 2 output
output
1 1
Terminal identification
earthing terminal Each terminal is identified by 3 characters.
1 A 4
4
-C +C SEPAM 100 RT
Example of input wiring
remote reset 0 A 21
(transformer protection) reset
0 A 20
0 A 15 In 5
thermostat (tripping) 0 A 14 In 4
buchholz (tripping) 0 A 13 In 3
thermostat (alarm) 0 A 12 In 2
buchholz (alarm) 0 A 11 In 1
0 A 10 Com
1 A 1
+
1 A 2 power
-
Sepam 100 RT 03 01 02
M
TRIP
CLOSE
–C
5
characteristics
electrical characteristics
logic inputs
24/30 Vdc 48/127 Vdc 220/250 Vdc
power consumption 10 mA 5 mA 4 mA
typical filtering time 5 ms
logic outputs (relays)
breaking capacity (1) 24/30 Vdc 48 Vdc 127 Vdc 220/250 Vdc
contact O1 7A 4A 0.7 A 0.3 A
contacts O2 to O5 3.4 A 2A 0.3 A 0.15 A
making capacity 8A
permissible steady state current 8A
number of operations under full load 10 000
response time typical 15 ms
(inputs to outputs) max. 25 ms
power supply
range typical maxi inrush current
consumption consumption
24/30 Vdc ± 20% 2.5 W 6,5 W < 10 A during 10 ms
48/127 Vdc ± 20% 3.5 W 7.5 W < 10 A during 10 ms
220/250 Vdc - 20%, + 10% 4W 9W < 10 A during 10 ms
environmental characteristics
climatic
operation IEC 68-2 -10°C to +70°C
storage IEC 68-2 -25°C to +70°C
damp heat IEC 68-2 95% to 40°C
mechanical
degree of protection IEC 529 IP 51 on front
vibrations IEC -255-21-1 class I
shocks IEC 255-21-2 class I
seismic tests IEC 255-21-3 class I
fire NFC 20455 glow wire
dielectric
power frequency IEC 255-4(1) 2 kV - 1 min.
1.2/50 µs impulse wave resistance IEC 255-4 5 kV
electromagnetic
radiation IEC 255-22-3 class x 30 V/m
electrostatic discharge IEC 255-22-2 class III
damped 1 MHz wave IEC 255-22-1 class III
5 ns fast transients IEC 255-22-4 class IV
(1)
published in 1976 and amended in 1979.
“ ” marking on our product guarantees their conformity to European directives.
6
installation
A
86 max
20 175
88 84 max
e = 3 mm max
7
Ordering information
quantity: ...................................................................................................
auxiliary power supply: 24 to 30 Vdc .............................................................
48 to 125 Vdc ...........................................................
220 to 250 Vdc .........................................................