Professional Documents
Culture Documents
This article was published in ASHRAE Journal, September 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org.
Stauffer I Laboratory Building retrofit saved more than $228,000 in FY2009. The retrofit is expected to match or exceed that level annually.
T
he in-house energy group at Stanford University, in Stanford, Calif., conducted a campus-wide study in 2002 to
identify high energy density buildings with significant potential for retrofit savings. Each of the campus buildings was
evaluated by site energy consumption and cost as a function of the building size.
In the process of this analysis, Stan- The Stauffer I Building (Photo 1) is a door air constant volume air-handling
ford identified 12 buildings representing chemical research laboratory with wet units (AHUs) located in the basement
roughly one-third of the total campus and dry laboratories. The building also with intake air louvers that connect to
electrical consumption, which accounted contains support space for researchers ventilation wells adjacent to the build-
for a combined operating cost of $15.3 and administrators with office, confer-
million annually. Stanford selected ence room and other non-laboratory
Stauffer I Laboratory Building as an space. Stauffer I has three stories—two About the Authors
early project due to its small size, high above grade and one below—and was Molly McGuire, P.E., is a mechanical engineer and
Mark Hydeman, P.E., is a principal and founding
energy intensity, and similarity to nearby constructed in 1959 –60. partner at Taylor Engineering, Alameda, Calif.
buildings that also would be candidates, The main building HVAC system Scott Gould is senior energy engineer, Stanford
pending success with the lab retrofit. consists of three central 100% out- University in Stanford, Calif.
fans now operate at part load for most of the year. The exhaust 30,000
fans, although still operating at constant volume to maintain
safe exhaust stack velocities, operate at a reduced speed because 20,000
of the exhaust stack modifications.
10,000
Results: Indoor Environmental Quality
The retrofitted systems provide significantly improved air
0
quality, thermal comfort, and acoustical control compared 40 50 60 70 80
with the original constant volume design. The VAV system OAT (°F)
dynamically controls space airflows, allowing the system
to more precisely address two critical laboratory air quality
health and safety concerns: room pressurization and hood face Steam
airflow. In each space, supply valves track exhaust airflow to 14,000 2005
maintain constant room pressurization as airflows rise and 2006
fall in response to demand. Pressure-independent air valves 12,000 2007
Monthly Steam Energy (Therms)
hood airflow or room air balance is out of range. The system 120,000
also alarms on equipment malfunction or failure.
VAV control of the spaces also provides greatly improved 100,000
thermal comfort. The DDC system provides tighter temperature 80,000
control, and spaces operate at less-than-design airflows for
most of the year, reducing the risk of draft due to high airflows. 60,000
The supply air temperature is reset higher than design cooling 40,000
temperature for much of the year, further reducing the risk of
local discomfort. 20,000
The acoustical environment has been improved, largely due to 0
reduced operating fan speeds and airflows. Fume hoods operate Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
at a fraction of the design airflow rate much of the time. The
acoustical noise in each space was measured under both pre- and Figure 3: Monthly pre- and post-retrofit electricity consumption.