Professional Documents
Culture Documents
Helix
WM048526
Rev 02
AE
Read this manual before starting any installation, service, or maintenance work
Fuel dispensers contain both electrical components and a hazardous, flammable and potentially
explosive liquid. Failure to follow the below precautions and the Warning and Caution instructions
in this manual may result in serious injury. In addition, it is your responsibility to follow all rules,
codes, regulations, and laws that apply to your location and type of work being performed.
Safety precautions
Make sure that ALL power to the dispenser is turned OFF before opening the cabinet or starting
work. Physically lock, restrict access to, and/or tag the circuit breakers you turn off. In addition,
be sure to trip (close) all emergency valves under the dispenser (if installed) BEFORE you begin.
Make sure that you locate the facility’s emergency shut-off button, and know how to turn OFF
power to the dispenser and submersible pumps (if any) in an emergency.
Never allow a leaking pump to run! Use appropriate measures to clean up any fuel on the forecourt,
and ensure that any leaks or issues that could cause a leak are attended to and repaired immedi-
ately.
Note !
Indicates extra information or tip.
NOTICE!
CAUTION!
DANGER!
Table of Contents
1 Introduction .................................................................................................................................................... 3
1.1 Dispensers Covered ................................................................................................................... 3
1.2 Wayne iGEM™ Computer Software .................................................................................... 4
1.3 Safety precautions ..................................................................................................................... 4
1.4 Bezel .................................................................................................................................................. 7
2 Installation ...................................................................................................................................................... 8
2.1 Helpful Tips .................................................................................................................................... 8
2.1.1 Determining Dispenser Sides A & B ................................................................................................... 8
2.1.2 Determining HI & LO - Product Piping .............................................................................................. 8
2.1.3 Pump Control Wiring at Junction Box .............................................................................................. 8
2.1.4 Dispenser ON/OFF Switch ...................................................................................................................... 8
2.1.5 iX R2 Board Reset Button ....................................................................................................................... 9
2.2 Inspect Equipment ..................................................................................................................... 10
2.3 Island Construction, Dispenser Anchoring, and Piping ............................................. 10
2.4 Emergency Shear Valves ......................................................................................................... 10
2.5 Vapor return piping .................................................................................................................... 12
2.6 Lifting and installing dispenser ............................................................................................. 12
2.7 Electrical wiring ............................................................................................................................ 13
2.7.1 General ........................................................................................................................................................... 13
2.7.2 Dispenser to Wayne Control System interconnection ............................................................... 13
2.7.3 Full service (stand-alone) dispensers ................................................................................................ 14
2.7.4 Multiple dispenser wiring ....................................................................................................................... 15
2.8 Bleeding product lines (remote dispensers) ................................................................... 15
2.9 Calibration of Wayne iMeter™ Piston Fuel Flow Meters ........................................... 15
2.9.1 Bleeding product lines (remote dispensers) ................................................................................... 16
2.9.2 Dispenser purging at startup: new dispensers and/or meters only .................................... 16
2.9.3 During calibration procedure ............................................................................................................... 16
2.9.4 Completing the startup calibration report ...................................................................................... 17
2.9.5 How to determine a successful calibration .................................................................................... 18
2.9.6 Factors that may influence calibration values .............................................................................. 18
3 Startup .............................................................................................................................................................. 19
3.1 Initial checkout ............................................................................................................................. 19
3.2 IR remote control ........................................................................................................................ 20
3.3 iX Pay™ Secure Payment Platform Configuration ....................................................... 21
3.3.1 Initial Configuration Procedure ............................................................................................................ 21
3.4 Set clock function (F 02) ........................................................................................................... 37
3.5 Logical nozzle / hose positions ............................................................................................. 38
3.6 Setting Unit Prices ...................................................................................................................... 40
3.7 Setting Blend Ratios ................................................................................................................... 43
3.8 Setting the Fueling Point ID (FPID) ....................................................................................... 47
3.9 Authorizing the Dispenser ....................................................................................................... 49
3.10 Initial Delivery ............................................................................................................................... 49
Appendices
A Installation Drawings ................................................................................................................................. 71
B Site Interconnection Diagrams .............................................................................................................. 78
C Hydraulic Configurations - Helix 4000 & 5000 Model Dispensers ........................................ 83
D Calibration Setup Report .......................................................................................................................... 88
E U.S. METROLOGICAL AUDIT TRAILS IN US iGEM ............................................................................. 90
F Glossary of Terms and Acronyms ........................................................................................................ 101
1 Introduction
This manual covers general user information on the operation and maintenance of the Helix™
dispenser models outlined in Dispensers Covered3. This manual also includes installation and
footprint drawings that show locations of the product inlets and conduits. Computer function
settings that are necessary for Helix dispenser start-up and operation such as setting prices, blend
ratios, and fueling point ID's are also included. If additional information on function settings and
statistics is required refer to the Helix Dispenser Service Manual (p/n WM048523).
The following items are required for the operation and maintenance of Helix dispensers:
• Infrared remote control (IR remote or IRC) - Wayne part number 886446-001
• Printer door - DHW1 key
• Lower bezel door and sliding bezel tray locks - DW2 key
• Hydraulic door key - 3306 key - Wayne part number WM003119
• Any questions concerning installation and operation of the dispenser that are not covered in
this manual should be referred to Wayne Technical Support at +1 800 926 3737.
4 All vehicle traffic and unauthorized persons shall be prevented from coming within 6 m (20 ft)
of the dispensing device.”
WARNING!
ELECTRIC SHOCK HAZARD!
Lockout/Tagout requirements of the U. S. Dept. of Labor, Occupational Safety and Health Admin-
istration (OSHA) may also apply. Refer to Title 29, Part 1910 of the Code of Federal Regulations
(29CFR1910), Control of Hazardous Energy Source (Lockout/Tagout).
Note !
To prevent damage to components located in the hydraulic cabinet, dispenser doors should be
in place during rainy and/or icy weather conditions. Also, check the nozzle boot flipper for freedom
of movement. If ice has formed on the flipper, it should be cleared to prevent unnecessary damage.
Pertinent information and codes are available from the following sources:
Table 1.1: Code Sources
Fiberglass Petroleum Tank and Pipe Institute American Petroleum Institute (API)
1150 South Wilcrest Dr. Suite 101 1220 L Street, N.W.
Houston, TX 77099-4343 Washington, DC 20005-4070
+1(281)568-4100 +1(202) 682-8000
www.fiberglasstankandpipe.com www.api.org
National Fire Protection Association (NFPA) National Assoc. Corrosion Engineers
One Batterymarch Park (NACE)
Quincy, MA 02169-7471 1440 South Creek Dr.
+1(617) 770-3000 Houston, TX 77084-4906
www.nfpa.org +1(281) 2286223 or +1(800)797-6223
www.nace.org
Petroleum Equipment Institute (PEI) National Leak Prevention Association
6514 E. 69th St. (NLPA)
Tulsa, OK 74133-1729 685 Fields Ertel Road
+1(918) 494-9696 Cincinnati, OH 45241
www.pei.org +1(815) 301-2785
www.nlpa-online.org
1.4 Bezel
sales display
VGA display
softkeys
printer door
lock
keypad
printer
unit price
displays
PTS/Grade select
buttons
Figure 1.2: Dispenser Bezel (Example shown is an Helix 4000 fuel dispenser)
2 Installation
Note !
It is recommended to shut down power to all dispenser installation locations at the site prior to
installation instead of shutting down power to each dispenser location individiually as each instal-
lation occurs.
CAT board
ON / OFF
reset button
WARNING!
2 "Listed" means published on a list by a nationally-recognized testing laboratory (NRTL) which is responsible
for product evaluation and is acceptable to the authority having jurisdiction. Underwriter Laboratories, Inc.
(UL) is one example of an NRTL. For more information on NRTL's, see Title 29, Parts 1907 and 1910 of the Code
of Federal Regulations, Safety Testing, or Certification of Certain Worklplace Equipment and Materials.
valve
shear point actuator
lever
top of
concrete
island
trip lever pipe plug
(pull down to for
close valve) bleeding
product
lines
product inlet
Note !
The shear valve must always be at ground plane. The pedestal is considered an extension of the
dispenser, not the island.
Note !
Wayne does not supply the meter inlet pipe nipple or the union shown above.
WARNING!
WARNING!
Explosive or flammable vapors!
2.7.1 General
Wayne recommends employing a qualified electrician for all wiring. A hazardous liquid is being
handled, so it is important to ensure that all wiring is in accordance with the National Electrical
Code (NFPA 70) as well as all federal, state and local regulations. Note: UL requires that all electrical
connections to the dispenser be made with threaded, rigid conduit and properly sealed conductors.
Note: All dispensers and electrical connection boxes must be grounded per NFPA 70.UL
Note !
When data wires are installed, only the two data wires from the Data Distribution Cabinet used
for pump control are to be terminated at the dispenser’s terminal strip. The additional data wires
should not be physically connected to the data terminals on the dispenser’s terminal strip. Instead
they should be properly terminated individually using wire nuts.
WARNING!
Electric Shock Hazard!
A maximum of 12 dispensers (24 fueling points) may be connected to a single PRD7AYO (120) relay;
other relays may have different limitations. All dispensers operating the same pump control relay
must be connected to the same circuit breaker; this may require multiple control relays for a
submersible pump.
Ensure that the submersible pump receives its power from its own separate circuit breaker as il-
lustrated in the Typical Site Wiring Diagram.
Note !
To avoid severe damage to the dispenser, all air and air pockets must be bled from the product
trunk lines before attempting to dispense product
Dispensers have an operation mode setting that establishes the pulser’s calibration mode. This
is set at the factory in the dispenser template (Read Only function F16). The iMeter and the Xflo
meter are calibrated using the same procedure as shown below.
Note !
In the Liter mode, in addition to 20 liters, a 10 liter of 5 liter test measure may be used if required
by the application. However, you should check with your jurisdiction on Weights & Measures tol-
erance requirements.
Note !
For the U.S. and Canada, acceptance of +/- 3 cu. in. for a 5 gallon measurement and +/- 50 ml for
a 20 liter measurement is only required for newly installed, newly placed in service devices for 30
days. After 30 days, the tolerance is increased to +/- 6 cu. in. for 5 gallons and +/- 100 ml for 20
liters.
Variables in method and environment can account for significant measurement error during
meter calibrations therefore, the procedure below should be followed when calibrating or verifying
any meter to ensure proper calibration.
Note !
Applies to new dispensers only!
Note !
To avoid severe damage to the dispenser, all air and air pockets must be bled from the product
trunk lines before attempting to dispense product.
Note !
The attached Startup report can be used for any meter, however, for Xflo warranty it must be sent
to Wayne along with the dispenser startup forms.
1 UST Temperature: Enter the tank temperature reported from the tank monitor for each fuel
type.
2 Dispenser Serial Number: Enter the dispenser serial number located on the serial plate.
3 Dispenser Model: Enter the complete dispenser model description located on the serial plate.
4 Station Fueling Point: Enter the station fueling point (FP) for the dispenser side under test.
5 Ambient Air Temperature: Enter the air temperature at the time of test.
6 Weather conditions at the dispenser: Circle or enter the conditions that apply when the test is
being conducted.
7 Meter Serial Number: Enter the serial number located on the serial label on the A side of the
meter.
8 Dispenser Side A or B: Circle the dispenser side (A or B) under test.
9 Fuel Type: Enter the fuel type and grade under test.
10 Meter totals: Enter the meter total.
11 Initial Meter Purge Reading (cu in): Enter the can value (in line 6 of SU Report) after filling as
close as possible to 5.000 gallons on the pump display.
12 Verification Value Fast Flow (cu in): Enter the can value (in line 7 of SU Report) after filling as
close as possible to 5.000 gallons on the pump display. If calibration is within +/- 0.1% (+/-1
cubic inch in 5-gallons), skip steps 13 - 18
13 .Lift nozzle.
14 Open calibration door of meter to be calibrated. (Only one door can be opened at a time during
the calibration process.)
15 Display Volume Value at Calibration: Dispense 5 gallons (20 Liters) into the prover can exactly
to the ‘0’ mark on the sight glass and then enter (in line 8 of SU Report) the amount shown on
the volume display. (Note: Write down the entire number).
16 Close the calibration door. (This redefines the calibration factor in the pulser.)
17 Hang up nozzle.
18 Verification Value Fast Flow (cu in): Ensure calibration took successfully within
+/- 0.1% (+/-1 cubic inch in 5-gallons). (Enter in line 9 of SU Report). (Repeat steps 13 - 18 if
outside expected limit.)
19 Verification Value Slow Flow: Ensure the meter remains in calibration at a slow flow rate (enter
in line 10 of SU Report).
20 Seal calibration door.
3 Startup
IRC When F - - is shown on When F 'xx' is shown When xx.xx sub-function is shown
Keys the unit price display on the unit price dis- on the unit price display
play
When in Statistics Mode (S - - or S “xx” on Unit Price Display, the above commands work the same
way.
J15
2 Hold down the #2 softkey when the Temporarily Out of Service screen is displayed. It is displayed
for only 5 seconds. The ‘2’ softkey is the second key to the left of the display. NOTE: If you miss
the screen, reboot and try again.
1 5
# 2 Softkey 6
3 7
4 8
3 Select YES if the dispenser is a Helix dispenser model or has a Compact Payment Terminal
(CPT).
Note !
Since the iX Pay (R2) board automatically resets once every 24 hours at 2:00 A.M., Correct time
entry is essential to avoid resetting during normal business hours.
14 Select YES if the dispenser is using a Contactles Card Reader. Note that a Bill Acceptor and a
Contactless Reader cannot be attached and configured at the same times. These two devices
share the same COM Port. Answering YES to this prompt will enable the Contactless Reader
and the Transparent Mode screen will be displayed.
• Answer NO at the Transparent Mode screen unless instructed to do otherwise for a specific
customer or vendor.
15 Select YES if the dispenser is using a Zebra printer, otherwise, select NO.
16 The printer will print a receipt. Select the value shown on the receipt.
17 Select YES to Remove Receipt Header? prompt. (The most typical selection is NO.)
20 On the keypad, enter the terminal number for the opposite side and then press the ENTER key.
Note !
At this point the configuration data is copied to side B.
22 Test operation of each key on the keypad. Non-numeric keys will show HEX values. See below
for displayed numbers.
Non-numeric keys will show HEX values. See below for displayed numbers.
0x03 0x43
0x02 0x42
0x01 0x41
0x00 0x40
24 The following screen is displayed if YES was selected for the pump test.
26 Test the operation of the card reader. The following screens will be displayed:.
For dispensers that have a secure mag card reader, a description of the LED indicator light on
the Secure Card Reader is listed below:
27 On dispenser side A, when the configuration is complete, select RESET as shown below. The
Diagnostics Complete screen will be displayed, a configuration report* will print, and the system
will automatically reboot. After side A is placed into Operation, the technician needs to perform
only the Diagnostic test on side B and put side B into Operation. A sample configuration report
is shown in Figure X at the end of this section.
28 Select RESET.
System automatically reboots here. New EPP keypads will come up in the Wait for Install mode
as indicated by the screen below.
29 At this time the system can be placed into OPERATION.
31 Select READY.
32 Press CANCEL.
33 The system is now in Operation mode. Press CANCEL to finish and wait for the online POS
prompt. See Step 34.
Note !
NOTE: To view the iX Pay software version number, select SYS INFO and the screen below will
be displayed. To print a configuration report showing the software version number, go into the
Diagnostic mode and go to the printer test. The software ID will be shown under the Product
Name on the printout.
34 The offline prompt will be displayed until communications are established with the POS. The
default prompt is shown below. Run test sales to verify operation.
Dispenser Side
CAT address
(terminal ID) Battery Mode: logs
Software ID each time
4
NOTE : Software ID
dispenser power is
does not show up on off
config report. Run the SPM mode
diagnostic test to print
version. Erase Reason
Authentication
Type 2 ------ F 02
Press ENTER
Press ENTER ------ Time in HH.MMforma] 2.00
(if time is correct skip to step
8)
Press # Time in HH.MMformat 2.00
Type the current time in 24-hour ------ Entered time in HH.MM for- 2.00
format of HH.MM mat
- Press ENTER
Press NEXT ------ Date in MM.DD format 2.01
(if date is correct skip to step
11)
Press # date in MM.DD format 2.01
Type the current date in the for- ------ entered date in MMDD for- 2.01
mat of MMDD mat
- Press ENTER
Press NEXT ------ year in YYYY format F 02
(if year is correct, skip to
step 14)
Press # year in YYYY format F 02
Type the current year in the for- ------ current year in YYYY format F 02
mat of YYYY
- Press ENTER
Press ENTER ------ F 02
Helix model # be- Dispenser descrip- N=7 N=6 N=5 N=4 N=3 N=2 N=1
gins with tions
H(N/L)11-11 1 Hose X
Non-blender
H(N/L)22-22 2 Hose Y X
Non-Blender
H(N/L)23-21 1 Hose LO BL HI
Blender
H(N/L)23-22 2 Hose LO BL HI
Blender
H(N/L)24-21 1 Hose LO LO-BL MID- HI- HI
Blender BL BL
H(N/L)33-31 3 Hose Z Y X
Non-Blender
H(N/L)34-32 2 Hose LO LO-BL HI-BL HI
Blender
H(W/L)22-22 2 Hose Y X
Non-Blender
H(W/L)23-21 1 Hose LO LO-BL BL HI S
Blender
H(W/L)24-21 1 Hose LO LO-BL MID- HI- HI
Blender BL BL
Helix model # be- Dispenser descrip- N=7 N=6 N=5 N=4 N=3 N=2 N=1
gins with tions
H(W/L)33-31 1 Hose Z Y X
Non-Blender
H(W/L)33-33 3 Hose Y X
Non-Blender
H(W/L)34-32 2 Hose LO LO-BL HI-BL HI
Blender
H(W/L)34-34 4 Hose LO LO-BL BL HI S
Blender
H(W/L)44-42 2 Hose W Z Y X
Non-Blender
H(W/L)44-44 4 Hose W Z Y X
Non-Blender
H(W/L)45-43 3 Hose LO BL HI S2 S1
Blender
1
Type 3 ------ F 03
Press ENTER, ENTER
Press # ------ Existing Credit Price 3.01 Noz 1
Type numbers ________________
ENTER New Credit Price
NEXT
Press # ------ Existing Credit Price 3.02 Noz 2
Type numbers ________________
ENTER New Credit Price
NEXT
Press # ------ Existing Credit Price 3.03 Noz 3
Type numbers ________________
ENTER New Credit Price
NEXT
Press # ------ Existing Credit Price 3.04 Noz 4
Type numbers ________________
ENTER New Credit Price
NEXT
Note !
See table in the Setting Unit Prices section for models and nozzle positions.
SIDE 1
Press ENTER PASS 1
Type the corresponding PASS 2
PASSWORD
Press ENTER
Type the PASSWORD again iGem soft- Date F --
Press ENTER ware version
- Type 18 ------ F 18
- Press ENTER, ENTER
Press # ------ - Existing blend ratio 18.11 Noz 1
Type blend ratio -New blend ratio
Press ENTER
Press NEXT
Press # ------ -Current 2 blend ratio 18.12 Noz 2
Type blend ratio -New blend ratio
Press ENTER
Press NEXT
Press # ------ -Current 3 blend ratio 18.13 Noz 3
Type blend ratio -New blend ratio
Press ENTER
Press NEXT
Note !
The volume display will indicate the value of the blend ratio corresponding to logical nozzle
#1(N=1). If there is no data for this logical nozzle, the number “101” will be displayed.
For reference, the following is a 50% blend ratio setting for a single hose blender, Helix model
B12/3 xxxx. Any unused position has to be set to 101 not 0.
Side 1 Side 2
Typically, stations sell the low and high grades at zero and 100 percent ratios and may sell the
middle grade at 35 percent or some other intermediate value between 0 and 100. On the above
model, the technician would need to change only sub-functions 18.15 and 18.25 to the inter-
mediate value.
As a reminder, always get the blend ratios from the station owner to avoid any confusion over
which values to use.
Type 5 ------ F 05
Press ENTER
Press ENTER ------ Fuel point address 5.00
for Side 1 in X for-
mat
Type desired FPID ------ New fuel point ad- 5.00
Press ENTER dress for Side 1
Note !
At Startup, the local Authorize switch jumper should be removed as explained in the Disable Stand-
alone Operation section.
After verifying air is bled properly from each trunk line, slowly dispense product through each
dispenser until free of air. Dispense enough product through each hose of each dispenser to
ensure the dispenser and the lines are free of air, before checking the meters.
5 For dispensers equipped with Wayne Vac, verify that the correct vacuum pump motor is running
when dispensing product. Verify by checking that air is being drawn through the vapor return
hole(s) in each nozzle spout. Also, see Testing Procedures manual, p/n 917947.
J6 jumper
Note !
There is no relationship between meter position and hose position. For example, in Table 3-3, po-
sitions N=1 and N=5 are not the high feedstock of a remote series blender used in the example
above.
Meter electronic totalizers are read by entering the Maintenance Mode and accessing the correct
function and associated sub-functions. Perform the following steps using the remote control. Bold
type denote remote control function; italicized type represents dispenser response.
Accessing the Meter Volume Totalizer Sub-function for Side 1:
• Press ENTER
PASS 1 (enter password)
• Press ENTER
PASS 2 (enter password)
• Press ENTER. The unit price display will show F
• Press either UP or DOWN arrow to enter the statistics viewing mode. The unit price display will
show S— (indicating that a number needs to be selected)
• Press 05 to access S05
• Press ENTER. The unit price display will show S05 (indicating that the statistical function has
been accessed)
• Press ENTER to access the sub-functions of S05. The unit price display will show 5.10 (note here
that M=1)
Consecutive pressing of NEXT will allow access to the next sub-function, incrementing the value
of M by (.1). For example, to access S05.20, press NEXT. The unit price display will show 5.20. The
value of the meter volume totals is shown in a format such that the least significant six (6) digits
of the data value appear on the volume display, while higher order non-zero digits of the data
value, if present, appear on the money display. Leading zeros appear as blanks.
Quick Exit
1 Press the CLEAR key until the unit price display window shows S - - .
2 Press ENTER three times. This causes the maintenance mode task to immediately terminate.
The totalizer shows seven digits and reads in whole units (gallons or liters). Fractional amounts
that are left over from a previous sale are stored in the dispenser computer. When the next sale
of the same product ends, if the fractional amounts from the new sale and previous sale(s) com-
bined are one (1) whole unit or greater, the Electro-Mechanical totalizer is adjusted one whole in-
crement; i.e., if five consecutive sales end with a fractional amount of .2, the Electro-Mechanical
totalizer will not account for the fractions until after the fifth sale.
4 Operation
Note !
Any modification, repair, or service to the dispenser not in accordance with the original design
may invalidate compliance with the equipment certifications such as CE Marking, UL, etc. Consult
manufacturer as necessary.
5 Return the nozzle to the nozzle boot. The nozzle boot switch will turn off; the sale will be complete
and ready to pay.
Note !
NFPA 30A requires the dispenser to be “manually activated.” This requires a separate intentional
operation (Push to Start, Cash/Credit selection, or grade selection) after the nozzle is removed
from its hang up position.
Errors are displayed in an alternating 2-page format. Information in the error pages is given below.
HH.MM MM.DD.YY
CC.DD.NN C
Where: Where:
HH = hour MM = month
MM = minute DD = day
CC = error code YY = year
DD = device number C = filling count
NN = logical nozzle number
The complete description of the error codes is given in the Helix Service manual.
Computer errors are read by entering the Maintenance Mode and accessing the correct statistical
function and its sub-functions. Perform the following steps using the remote control. Bold type
denote remote control function; italicized type represents dispenser response.
Accessing the error code Sub-function
1 Press ENTER
2 PASS 1 (enter password)
3 Press ENTER
4 PASS 2 (enter password)
5 Press ENTER. The unit price display will show F
6 Press either UP or DOWN to enter the statistics viewing mode. The unit price display will show
S— indicating that a number needs to be selected.
7 Press 21 to access S21 (error data for Side 1 or A which is the junction box side)
8 Press ENTER. The unit price display will show 21.01, the first and most recent error data for
Side 1. The data will be displayed in the 2-page format described earlier, in an alternating se-
quence, at a 1 second per page rate.
9 Pressing NEXT accesses 21.02 and the display shows information for the second error logged.
By pressing NEXT, the error buffer can be viewed completely.
10 To exit, press CLEAR, then UP or DOWN. The unit price display will show S—.
11 Press ENTER three times to exit to the normal display.
• 2400 MCS - All of the unpaid/stopped indicators will be illuminated on the 2400 MCS console.
Press Clear until the console display is totally blank. Press Pump Start. At this point all un-
paid/stopped indicators will go out and fuel flow may resume.
• Wayne Plus - All fueling point numbers will be shown in reverse index (light fueling point numbers
on a dark background) on the Wayne Plus. Press 0, Pump #, and Pump Start. At this point all
operational fueling points will be shown in normal format (dark fueling point numbers on a
light background) and fuel flow may resume.
• Nucleus - All fueling point numbers will be shown with the STOP sign. Press the ALL START key.
At this point all the fueling points will show the gas pump icon and all or each can be authorized.
Note !
All nozzles must be hung up before performing the following procedure.
The dispenser may be placed in stand-alone operation - not operated by a control system. To set
the dispenser in stand-alone, the correct function and its corresponding sub-function must be
accessed. Next, the filling mode is changed to its new setting and the data is saved. To access the
desired sub-function, the following steps must be performed using the remote control. Bold type
denote remote control function and italicized type represents dispenser response. NOTE: See ad-
ditional requirements for standalone operation in Appendix C.
Accessing the filling mode Sub-function
1 Press ENTER
2 PASS 1 (enter password)
3 Press ENTER
4 PASS 2 (enter password)
5 Press ENTER. The unit price display will show F— , indicating that it needs a function number
to proceed)
6 Press 01 to access F01
7 Press ENTER. The unit price display will show F01, indicating that the function has been accessed)
8 Press ENTER to access the sub-functions of F01. The unit price display will show 1.01 and the
volume display will show a 1 indicating that the dispenser is in serial filling or that the dispenser
is being controlled by the site controller via serial link.
9 Press UP to increment the value of function 1.02 by unity, followed by ENTER, or press # and
type 2 followed by ENTER (here 2 means that the filling mode is Stand-alone Mode, dispenser
not supervised by site controller).
Saving the new setting
1 Press ENTER. The price display will show “– – – – – –“, the volume display will be blank and the
unit price display will show the last sub-function accessed.
2 Press 00 (to access F00)
3 Press ENTER. The unit price should now display F00, the price display will show “– – – – – –“ and
the volume and the volume display will be blank.
5 Maintenance
Note !
To prevent damage to components located in the hydraulic cabinet, dispenser doors should be
in place during rainy and/or icy conditions.
Note !
Never re-install a broken break-away valve.
NFPA code requires that a Listed emergency breakaway device designed to retain liquid on both
sides of the break-away point, must be installed on each hose dispensing Class liquids; these devices
must be installed and maintained per the manufacturer's instructions. Refer to your state and local
coderequirements that apply to your installation.
Note !
On dispensers equipped with the hose retractor option, the hose clamp must be mounted upstream
of the break-away device to avoid damage to the dispenser in the event of a drive-off.
The combined hose, break-away, and whip maximum lengths are listed in the following table:
14 ft
(4.27 m)
Non-vapor 3/4 in 10 ft 10 ft
(.016m) (3.05 m) (3.05 m)
Non-vapor 5/8 in 14 ft 14 ft
(.019 m) (4.27 m) (4.27 m)
The strainer is located inside the casting and held in place by the filter. Place a suitable container
below the filter/strainer casting to catch product and sediment. Remove the filter and gently pull
the strainer out of the filter/strainer casting. Clean strainer screen of any debris. Re-install strainer
and a new filter.
To install the new filter, first apply a thin coat of oil to the gasket and hand turn until the gasket
contacts the base. Then tighten one half turn. Open the emergency shear valve, turn the sub-
mersible circuit breaker ON, and check for leaks.
In new installations it may be necessary to change the filter frequently in the first few days of op-
eration in order to ensure proper operation.
If the underground installation is new it may be necessary to clean the strainer screen two or
three times the first few days of operation to remove debris and pipe dope. After this, occasional
cleaning of the strainer is all that should be required. The fuel filter should be changed whenever
the strainer is cleaned.
Note !
Replacement fuel filter should be UL-recongnized. The recommended gasoline and ethanol fuel
filters are rated at 10 micron.
NOTICE!
Turn power off!
Note !
Do not use pressurized water (even from a garden hose) to wash or rinse off a dispenser. Under
no circumstance should power washers be used to clean a dispenser. This can force water into
the electronic head and cause damage to the electronic components in the dispenser rendering
it inoperative.
Do not use all-purpose cleaners.
Do not use gasoline or other petroleum based products to clean the dispenser.
Periodic waxing of the dispenser surfaces is essential to maintain the original finish and inhibit
corrosion. Painted surfaces should be waxed with an automotive wax or polish.
Note !
It is important to wipe down the dispenser with a clean cloth and clean water after every cleaning.
Periodic waxing of the dispenser surfaces is essential to maintain the original finish and inhibit
corrosion. Stainless steel surfaces should be polished with a non-abrasive silicone wax.
Note !
No chlorine-based cleaners can be used on the stainless stell, especially if the dispenser is located
in a marine environment.
paper holders
print head -
green lever
feed button
tab on paper
Indicators for
holder both
Power and
sides
Status
3 Insert new paper roll so that the paper feeds from the top of the roll into the printer. Paper
feeds from the top of the roll. Pull outward on tabs at bottom of hoder. Align and engage paper
core with holder.
Figure 5.5: Push green lever forward and raise print head
7 The printer will automatically advance and cut the paper. The green status light will be on.
1 Black AC Hot
2
3 Black Pump Control 1 LO
4 Black Pump Control 2 HI
5 Black Pump Control 3 Open
6 Black Pump Control4 Single
7 Black Neutral
8 Black AC Neutral
9 Orange CAT TX / RX +
10 Orange CAT TX / RX -
11 White Current Loop 1 +
12 White Current Loop 2 -
NC Orange Wayne Trac TX / RX +
NC Orange Wayne TracTX / RX -
option NC Blue Side A Intercom Speaker +
option NC White Side A Intercom Speaker -
option NC Blue Side A Call Button +
option NC Blue Side A Call Button -
option NC Brown Side B Intercom Speaker +
option NC White Side B Intercom Speaker -
option NC Brown Side B Call Button +
option NC Brown Side B Call Button -
Backroom Installation
Below are graphical layouts of the available hydraulic configurations for the different Helix H-Style
dispenser models. The graphics can be interpreted as follows, using the H(W/L)44-44 model as
an example.
Single-Sided: H(W/L)22-220
Single-Sided: H(N/L)22-220
Single-Sided: H(W/L)33-330
Vista Equivalent: 389
Vista Equivalent: 390
Single-Sided: H(W/L)33-310
Vista Equivalent: 390/U
Single-Sided: H(W/L)44-440
Vista Equivalent: 490
Single-Sided: H(N/L)33-310
Vista Equivalent: 390/U Narrow
Single-Sided: H(W/L)44-420
Vista Equivalent: 490/U
Single-Sided: H(N/L)25-210
Vista Equivalent: 585
Single-Sided: H(N/L)23-210
Vista Equivalent: 580
2X-21: 2-PRODUCT WIEDE BLENDER
(3-5 Grades)
Single-Sided: H(N/L)24-210
Vista Equivalent: 595/U
Single-Sided: H(N/L)34-320
Vista Equivalent: 595 Narrow
WM048526
Line 8- Record volume displayed while filling to zero mark on the prover can in Calibration mode
Line 9- Verify calibration: Meter under test must calibrate within +/- 0.1% (+/- 1 cubic inch in 5 gallons)
Line 10- Verification Value Slow - Conduct test on nozzle first latch or approx. 1 GPM
Rev 02
05/2013
D Calibration Setup Report
The following diagrams illustrate the Audit Trails contained in the US iGEM. Arrows between the
pictures show which key is used on the remote control to navigate between the screens. The first
diagram shows the upper level screens and subsequent diagrams illustrate the details contained
in each log and how to navigate down into those logs.
Note !
Dislays shown in these instructions are from previous model displays, however, the iGEM process
and data shown on displays in the audit trails process shown here have not changed.
UPPER LEVEL
The upper level of the metrological audit trail is shown below. Pressing CLEAR advances to the next event log.
iGEM currently contains the following event logs: Blend Ratio changes, Unit of Measure/Meter Type changes, Pulse
Output Resolution changes, ATC changes, Product Pressurization changes, and Program changes. As indicated
below, the information will be shown on the sales/volume and unit price displays.
Sale/Vol
display
CLEAR CLEAR
Unit Price displays
CLEAR
CLEAR CLEAR
CLEAR
CLEAR CLEAR
CLEAR
Last Sales Display
BLEND RATIOS
The audit trail event log for blend ratios is shown below. Pressing ENTER when at the upper level takes you into the
specific blend ratio changes for each product. The blend ratio event log is not displayed on non-blending dispens-
ers. The event counter has a capacity of 1000 ) 1-1000. Details of the last 10 changes to each product are logged.
CLEAR
ENTER
NEXT NEXT
“Pr 4” = product 4 Last 10 blend ratio changes for PR 5 Last 10 blend ratio changes for PR 6
toggle
“nonE” = No changes
“bC 10 blend ration change record 10
MEASURE/METER TYPE
This log tracks the unit of measure as well as the type of meter for which the iGEM is configured. The event coun-
ter has a capacity of 1000 (1-1000). Details of the last 10 changes are logged.
CLEAR CLEAR
ENTER
“US GAL” = Currently set to US Gallons
“Unit” = Unit of measure change record 1
toggle
toggle
NEXT
“nonE” = No Changes
“UC 10” = Unit of measure change record 10
The pulse output configuration change event log is shown below. The log tracks changes to pulse output configu-
ration programming. The event counter has a capacity of 1000 (1-1000). Details of the last 10 changes are logged.
CLEAR CLEAR
toggle
toggle
“nonE” = No Changes
“UC 10” = Unit of measure change record 10
The audit trail to track Automatic Temperature Compensation configuration changes is shown below. The event
counter has a capacity of 1000 (1-1000). Details of the last 20 changes are logged. Refer to the next page for
details of the individual meter configurations.
CLEAR CLEAR
toggle
toggle
ENTER
“tCON = ATC was enabled
NEXT
The details of each ATC configuration change are shown below. This log shows the ATC probes and fuel tupe
assigned to each possible meter in the dispenser.
toggle
NEXT
ENTER
NEXT
NEXT
NEXT
NEXT
NEXT
The Product Pressurization change log tracks the changes made to the product pressurization change function,
f21.07. The details of the last ten changes are kept, as well as a counter for the total number of changes are kept
as well as a counter for the total number of changes to this function setting (1-1000).
CLEAR CLEAR
toggle
toggle
NEXT
The Program Change log tracks details of the last ten programs that were loaded onto the iGem board. A counter
also tracks the total number of program loads (1-1000).
CLEAR
CLEAR
toggle
toggle
NEXT
The meter totals display is shown below. Volume totals for each meter associated with this fueling point are dis-
played. Meters not assigned to this fueling point will display 0.000.
CLEAR CLEAR
NEXT
NEXT
The display of metrological function data setttings are shown below. This is shown at the end of the audit trail dis-
play and allows a “read only” view of the actual data values currently assigned to the functions/sub-functions in
iGem (see iGem programming manual for values).
CLEAR CLEAR
ENTER
NEXT
ENTER
Sub-function
- data for F17
NEXT
NEXT
ENTER
Sub-function data for F19
NEXT
NEXT
ENTER
Sub-function data for F22
NEXT
Table F.1:
TERM DEFINITION
TERM DEFINITION
TERM DEFINITION
Intrinsic Safe Barrier (ISB) barrier inside the dispenser - the area below the
barrier is free from hazardous electrical sparks
island-oriented when the nozzle is located on the left or right sides
of the dispenser, as opposed to front or back sides
jitter unwanted electrical pulses or interference (as in jitter
pulses)
jumper small wire or connector used to join together to pins
in a connector or on a circuit board
junction box a metal box located near the bottom of the dispenser
lane oriented when the nozzle is located on the front or back sides
of the dispenser as opposed to th left or right sides
LEE lower electronic enclosure
low hose the fuel hose is connected near the middle of the
dispenesr, as opposed to high at the top
LT low temperature
LTS lift-to-start (to activate dispenser)
meter dispenser component that measures the
net volume the amount or volume of fuel after temperature
compensation
nozzle device at the end of the hose that is inserted into the
vehicle (or container) when dispenseing product
nozzle boot the holder (on the dispenser) of the nozzle when it is
not in use
outlet location at a meter, valve, or casting where the fuel
exits
outlet casting a metal or aluminum type mold where the hose is
connected to the dispenser
P/N part number
payment terminal (PT) as in payment terminal on the dispenser where a
payment is made by credit card
pedestal platform or base that the dispenser sits on (also re-
ferred to as 'island' in some areas)
pipe dope sealant used on the threads of a pipe; pipe sealant
POS Point of Sale
TERM DEFINITION
prime to pour fuel into the pump to clear out the air in order
to start the pump properly
product tube fuel tube; the tube that contains the fuel or that fuel
moves through
PTS push-to-start (to activate dispenser)
pulser device that generates signals
purge clearing the fuel lines of air
relay an electrical component used in the dispenser
remote (pump) the pump for the dispenser is located in the under-
ground tank; not inside the dispenser
residual something left over or remaining (as in residue)
retainer clip (pin) used to secure or hold a tube in place
retractor pulls hose back into place after use
sales/volume display shows the total sale amount and the volume dis-
pensed
satellite (dispenser) a small dispenser connected to and controlled by
another dispenser that is referred to the master
servTerm a software application also known as the Service
Terminal program
shear valve see emergency valve
sight glass a glass cylinder used for visually measuring volume
of fuel
Small-style a short (small) type of dispenser
softkey as in buttons or keys on a keypad
solenoid valve electro-mechanically operated valve
SPM secure payment module
stand-alone mode dispenser is not connected to or communicating with
the POS
Std standard
strainer device that captures small unwanted particles in the
gasoline or diesel fuel
submersible pump that is located in the underground tank
TERM DEFINITION
suction (pump) the pump for the dispenser is located inside the dis-
penser
torque rotating force applied to tighten; amount of force
used to tighten a screw or pipe
Torx™ a brand name of a type of screw
TOT totalizer -
totalizer (TOT) device on the dispenser that counts and displays the
total volume units
TRAC Transponder-activated CAT
triple bump tube a tube having three raised areas on the end
unit price display (UPD) shows the fuel price per gallon or per litre
universal joint a type of coupling
UPD Unit Price Display
UPS Un-interruptible Power Supply
vacuum air has been removed (as in a vacuum line)
valance cosmetic panels around the top of the dispenser
vapor recovery system that claims fuel vapors, minimizing exposure
to the customer and environment
WIP Wayne Integrated Pulser; a type of meter manufac-
tured by Wayne
Xflo a type of meter manufactured by Wayne
Copyright notice
© 2012 Wayne, A GE Energy Business. The contents of this manual may not be copied in whole
or in part without the express written consent of Wayne.
Wayne reserves the right to make revisions to this manual without prior notice.