PKS™ - TDC 3000® TAB PD 10

CUSTOMER PAGE A50 (A)


RESOURCE MANUAL DATE 5 APR 2007

IOP FIRMWARE REVISIONS REQUIRED FOR PMIO CONNECTION TO


EXPERION

Background For xPM IOPs to be connected to Experion through the PMIO, they
must be at a minimum firmware revision level. Table 1 shows the kits
available to upgrade existing xPM IOPs and which specific boards they
are designed to upgrade.

Table 2 shows which xPM IOPs can be connected to the PMIO and the
minimum firmware revisions required for both R201, R210 and R3xx
releases. Older model IOP's not listed have not been tested and are
not supported by Honeywell with the PMIO.

When looking at the firmware chip, a letter will indicate the current
firmware. When the firmware revision is viewed from a screen, a
number will be displayed. Unlike hardware revisions that follow a fixed
Letter to Number relationship, see "PD 22 Y02 (B)", the firmware Letter
to Number relationship is unique to each type of IOP.

Continued on next page

Honeywell Automation and Control Solutions


TAB PD 10 A50 (A) PAGE 2 DATE 5 APR 2007

IOP FIRMWARE REVISIONS REQUIRED FOR PMIO CONNECTION TO


EXPERION Continued

Action Table 1 shows the kits available to upgrade existing xPM IOPs and
which specific boards they are designed to upgrade. The existing IOP
model will start with either MU or MC. The MU indicates an uncoated
board and the MC indicates coated. Only MC model numbers are
available.

Table 1
Kit Model Description IOP Model IOP # c
MC-ZAIHF3 HLAI IOP PAIH03 51304754-100/150
PAIL01 51303988-300
MC-ZLLAI2 LLAI_8 IOP
PAIL02 51304481-100/150
PAOX01 51303985-200/300
MC-ZAOXF2 AO_8 IOP (R3xx)
PAOX02 51304483-100
51304672-150
MC-ZAOXF3 AO_8 IOP (EC) PAOX03
51309152-175
MC-ZAOYF2 AO_16 IOP PAOY22 80363969-100/150
MC-ZDIYF2 DI IOP, High Density PDIY22 80363972-100c/150
PDIX01 51303997-300
MC-ZDIXF2 DI IOP
PDIX02 51304485-100/150
PDOX01 51303994-300
MC-ZDOXF2 DO IOP
PDOX02 51304487-100c/150
MC-ZDOYF2 DO IOP, High Density PDOY22 80363975-100c/150
MC-ZSTXF3 STIM IOP PSTX03 51304516-200/250
MC-ZDISF2 DISOE IOP PDIS12 51402625-125c/175
MC-ZLLMF2 LLMUX IOP PLAM02 51304362-100/150
MC-ZRHMF1 RHMUX IOP PRHM01 51404109-125/175

Note: c Only some uncoated part numbers are now available until stock is depleted.

Continued on next page

Honeywell Automation and Control Solutions


TAB PD 10 A50 (A) PAGE 3 DATE 5 APR 2007

IOP FIRMWARE REVISIONS REQUIRED FOR PMIO CONNECTION TO


EXPERION Continued

Action, continued Table 2 provides the minimum supported firmware level for the PMIO
in question to be used with Experion. The “FW Chip” column identifies
the part number for the firmware chip on the existing IOP and what is
the minimum revision level that must be identified on the chip for
Experion.

Be aware that the firmware chip normally has just the last four digits of
the part number on the chip along with the revision letter. Example is
the IOP model PAIL02 would have chip 51120575 but would only be
marked 0575 along with the firmware revision letter.

Table 2
FW FW
MODEL FW — Chip d Description
LCN EPKS
PAIL01 6.0 6.00 J- 51120575 LLAI – low level analog input
PAIL02 6.0 6.00 J- 51120575 LLAI – low level analog input
PLAM02 4.1 4.01 F- 51120493 LLMUX – low level multiplexer analog input
PRHM01 6.0 6.00 E- 51120942 RHMUX – remote hardened LLMUX
PAIH03 e 6.1 6.01 G- 51120673 HLAI – high level analog input
PHAI01 1.1 1.01 B- 51121201 HLAIHART – high level AI HART capable
6.0 6.00 STI-MV – smart transmitter interface,
PSTX03 F - 51120841
multivariable
PAOX01 3.4 3.04 D- 51120576 AO_8 – analog output, 8 channel c
PAOX02 3.4 3.04 D- 51120576 AO_8 – analog output, 8 channel c
PAOX03 4.2 4.02 C- 51120674 AO_8 – analog output, 8 channel
PAOY22 1.2 1.02 C- 80364453 AO_16 – analog output, 16 channel
PHAO01 1.1 1.01 B- 51121202 AO16HART – AO 16 channel HART capable
PDIX01 3.3 3.03 C- 51120577 DI – digital input
PDIX02 3.3 3.03 C- 51120577 DI – digital input
PDIY22 1.2 1.02 C- 80364451 DI_24V – digital input, 24 volt
PDIS11 4.4 4.04 F- 51120708 DISOE – digital input sequence of events
PDIS12 4.5 4.05 G- 51120708 DISOE – digital input sequence of events
PDOX01 3.6 3.06 F- 51120578 DO_16 – 16 channel digital output
PDOX02 3.6 3.06 F- 51120578 DO_16 – 16 channel digital output
PDOY22 1.3 1.03 D- 80364452 DO_32 – 32 channel digital output

Note: c For R210 release, Rev. E (3.09/3.9) supports 0.0 ma operation.


d MINIMUM for R201/R210.The R201 CRG showed higher revisions for some
IOPs but further evaluation lowered the revision requirements on some IOPs.
e If the F/W rev is 3.3 (B) or less then the IOP is a PAIH02 and must be replaced
with a PAIH03.

Honeywell Automation and Control Solutions


TAB PD 10 A50 (A) PAGE 4 DATE 5 APR 2007

IOP FIRMWARE REVISIONS REQUIRED FOR PMIO CONNECTION TO


EXPERION Continued

Action Table 3 shows the relationship between the firmware as viewed on a


TPS (LCN) system compared to an EPKS (Experion) station.

When the firmware revision is viewed from a US or GUS on a LCN


system the firmware revision will be in the format of X.Y. Y will be a
single digit hexadecimal character. When viewed from an EPKS
system, the format will be X.YY. Here YY will be a 2 digit decimal
number.

To see the actual firmware revision on a TPS system, go to the HPM


Status Display, select an IOP, and then select Detail Status. If you use
the DATACHNG schematic from PERFMENU, enter
$NMnnBxx.IOMFWREV(y) – where nn is the process network number,
xx is the HPM number, and y is the IOP number. The value displayed
from DATACHNG will be a string so revision 5.4 will be represented as
54. On an Experion Server, open Control Builder, select the IOLIM,
select the IOLINK, and select an I/O file to see all the IOP revisions.

Table 3
TPS EPKS TPS EPKS
1.0 1.00 1.8 1.08
1.1 1.01 1.9 1.09
1.2 1.02 1.A 1.10
1.3 1.03 1.B 1.11
1.4 1.04 1.C 1.12
1.5 1.05 1.D 1.13
1.6 1.06 1.E 1.14
1.7 1.07 1.F 1.15