2
...with specific functionality to fit the application
The VLT® AutomationDrive The VLT® HVAC Drive The VLT® AQUA Drive
The VLT® AutomationDrive is a single Setting new standards, the VLT® HVAC As the only dedicated water and
drive concept that controls all opera- Drive integrates seamlessly with HVAC wastewater variable frequency drive
tions from standard induction motors systems. Danfoss’ extensive experi- on the market, the VLT® AQUA Drive
to permanent magnet servo mo- ence in advanced variable frequency offers a wide range of powerful stand-
tors on any machine or production drive technology for HVAC applica- ard and optional features designed
line. The standard versions cover a tions has produced an unmatched specifically for water and wastewater
wide range of functions such as PLC product offering. The VLT® HVAC Drive applications. Pump-specific features
functionality, automatic fine-tuning is suitable for a range of needs, from protect valuable equipment while
of motor control and self-analysis of simple follower operation to intel- providing unparalleled control and
performance. Positioning, synchronis- ligent stand alone control. From “drive flexibility. And with features such as
ing, programmable motion control only” to complete package solutions, sensorless control, Automatic Energy
and even servo performance are also the VLT® HVAC Drive is the economi- Optimisation and Automatic Motor
available. All versions share an identi- cal, flexible and user-friendly answer Adaptation, the VLT® AQUA Drive
cal user interface, so once you’ve to a variety of HVAC applications. provides the lowest overall cost of
operated one, you can use them all. ownership of any drive available.
• VLT® HVAC Intelligent Control with
• Built-in Smart Logic Controller four auto-tuning, multi-input, multi- • Dry pump detection
• Constant torque or variable torque control PIDs • Enhanced sleep mode
operation • Built-in Johnson Controls’ Metasys • Pipe fill mode
• Category 3 Safe Stop N2, Siemens Apogee FLN and Mod- • End-of-curve detection
• Loadsharing and regenerative bus RTU; LonWorks® and BACnet™ • Flow compensation of setpoint
braking capabilities optional
• Real-time clock
Manufactured to the
highest quality standards
VLT® Series drives are UL listed
and made in ISO 9001-2000
certified facilities.
3
Features to meet even the most demanding applications...
To disconnect control signal wires, simply unplug The fieldbus option ready to plug in beneath the Coated control boards are avilable for harsh
the terminal blocks. front panel. It can be turned upside down if you’d environments.
rather have the cable on top.
4
...in a package built for years of reliable operation
Control signals
Specially developed spring-loaded
cage clamps increase reliability and
facilitate easy commissioning and
service.
5
Intelligent heat management
Back-Channel Cooling
The intelligent heat management of
VLT® drives removes 85% of the heat
losses via finned heat sinks, which
transfer the heat to the back channel
cooling air. This back channel is sepa-
rated from the electronics area by
an IP 54 seal. This method of cooling
greatly reduces contamination of the
control electronics area, resulting in
longer life and higher reliability.
Zero clearance,
side-by-side mounting
Up to 10 drives can be placed on a 20-
foot (6-meter) wall, providing 6.3 MW
(at 690 V) or 4.5 MW (at 400 V).
6
Easy start-up, operation and servicing
Smallest in their class of Danfoss’ unmatched reputation for VLT® Series high power drives
Even the F frames (the largest of the service quality and responsiveness carry a number of certifications
VLT® High Power Drives) are among around the world: for maritime use, including those
the smallest in their power range. listed below. Contact Danfoss for
specific model coverage:
Internal components are housed in • Hands-on, factory management
an inverter cabinet, a rectifier cabinet, of service support activities
and – if required – an options cabinet • Local field service organisations
for easy access during commissioning trained and authorised by the
Established in 1864,
and servicing. factory DNV is an independent
• Technical support available 24/7 foundation with
Unparalleled support and service from a single point of contact the objective of safe-
guarding life, property
The Danfoss service organisation is • Parts designed and specified by the and the environment.
present in 120 countries, ready to factory for quick response
respond whenever and wherever you • Flexible coverage plans with fixed
need, around the clock, seven days a prices that reduce overall service
week. costs
7
380 – 500 VAC
D frames
Output Power
Continuous SVLT,N [kVA] 123 147 147 180 180 218 218 274 274 333
Intermittent SVLT,MAX [kVA] 184 162 220 198 270 240 327 301 410 366
Typical Shaft Output [kW] 90 110 110 132 132 160 160 200 200 250
Rated Input Current IL,N [A] 174 208 204 251 251 304 304 381 381 463
Output Current
Nominal Voltage
Continuous (441-500 V) IVLT,N [A] 160 190 190 240 240 302 302 361 361 443
Intermittent (60 sec)* IVLT,MAX [A] 240 209 285 264 360 332 453 397 542 487
460 V
Output Power
Continuous SVLT,N [kVA] 127 151 151 191 191 241 241 288 288 353
Intermittent SVLT,MAX [kVA] 191 167 227 210 287 265 361 316 431 388
Typical Shaft Output [HP] 125 150 150 200 200 250 250 300 300 350
Rated Input Current IL,N [A] 158 185 183 231 231 291 291 348 348 427
Output Current
Continuous (441-500 V) IVLT,N [A] 160 190 190 240 240 302 302 361 361 443
Intermittent (60 sec)* IVLT,MAX [A] 240 209 285 264 360 332 453 397 542 487
500 V
Output Power
Continuous SVLT,N [kVA] 139 165 165 208 208 262 262 313 313 384
Intermittent SVLT,MAX [kVA] 208 181 247 229 312 288 392 344 469 422
Typical Shaft Output [kW] 110 132 132 160 160 200 200 250 250 315
Rated Input Current IL,N [A] 158 185 183 231 231 291 291 348 348 427
Estimated power loss at rated maximum load [W] 2641 3234 2995 3782 3425 4213 3910 5119 4625 5893
Efficiency 0.98 0.98 0.98 0.98 0.98
Output Frequency [Hz] 0-800 0-800 0-800 0-800 0-800
Max. cable cross-section to motor [mm2] 2 x 70 2 x 70 2 x 185 2 x 185 2 x 185
output terminals (per phase) [AWG] 2 x 2/0 2 x 2/0 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. cable cross-section to loadsharing [mm2] 2 x 70 2 x 70 2 x 185 2 x 185 2 x 185
terminals (per -DC/+DC) [AWG] 2 x 2/0 2 x 2/0 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. cable cross-section to brake resistor [mm2] 2 x 70 2 x 70 2 x 185 2 x 185 2 x 185
terminals (per -R/+R) [AWG] 2 x 2/0 2 x 2/0 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. cable cross-section to input mains [mm2] 2 x 70 2 x 70 2 x 185 2 x 185 2 x 185
terminals (per phase) [AWG] 2 x 2/0 2 x 2/0 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. external input line fuses (mains) [A] 300 350 400 500 600
Enclosure Ratings and Weight
IP00/Chassis (D3, D4) [kg]/(lbs) 82 (181) 91 (201) 112 (247) 123 (271) 138 (304)
IP21/NEMA 1 (D1, D2) [kg]/(lbs) 96 (212) 104 (230) 125 (276) 136 (300) 151 (333)
IP54/NEMA 12 (D1, D2) [kg]/(lbs) 96 (212) 104 (230) 125 (276) 136 (300) 151 (333)
8
380 – 500 VAC
E frames
Output Power
Continuous SVLT,N [kVA] 333 416 416 456 456 516 482 554
Intermittent SVLT,MAX [kVA] 499 457 624 501 684 568 722 610
Typical Shaft Output [kW] 250 315 315 355 355 400 400 450
Rated Input Current IL,N [A] 472 590 590 647 647 733 684 787
Output Current
Nominal Voltage
Continuous (441-500 V) IVLT,N [A] 443 540 540 590 590 678 678 730
Intermittent (60 sec)* IVLT,MAX [A] 665 594 810 649 885 746 1017 803
460 V
Output Power
Continuous SVLT,N [kVA] 353 430 430 470 470 540 540 582
Intermittent SVLT,MAX [kVA] 529 473 645 517 705 594 810 640
Typical Shaft Output [HP] 350 450 450 500 500 550/600 550 600
Rated Input Current IL,N [A] 436 531 531 580 580 667 667 718
Output Current
Continuous (441-500 V) IVLT,N [A] 443 540 540 590 590 678 678 730
Intermittent (60 sec)* IVLT,MAX [A] 665 594 810 649 885 746 1017 803
500 V
Output Power
Continuous SVLT,N [kVA] 384 468 468 511 511 587 587 632
Intermittent SVLT,MAX [kVA] 575 514 701 562 766 646 881 695
Typical Shaft Output [kW] 315 355 355 400 400 500 500 530
Rated Input Current IL,N [A] 436 531 531 580 580 667 667 718
Estimated power loss at rated maximum load [W] 5165 6790 6960 7701 7691 8879 8636 9670
Efficiency 0.98 0.98 0.98 0.98
Output Frequency [Hz] 0-600 0-600 0-600 0-600
Max. cable cross-section to motor [mm2] 4 x 240 4 x 240 4 x 240 4 x 240
output terminals (per phase) [AWG] 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. cable cross-section to loadsharing [mm2] 4 x 240 4 x 240 4 x 240 4 x 240
terminals (per -DC/+DC) [AWG] 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. cable cross-section to [mm2] 4 x 240 4 x 240 4 x 240 4 x 240
regeneration terminals (per -DC/+DC) [AWG] 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. cable cross-section to brake [mm2] 2 x 185 2 x 185 2 x 185 2 x 185
resistor terminals (per -R/+R) [AWG] 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. cable cross-section to input [mm2] 4 x 240 4 x 240 4 x 240 4 x 240
mains terminals (per phase) [AWG] 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. external input line fuses (mains) [A] 700 900 900 900
Enclosure Ratings and Weight
IP00/Chassis (E2) [kg]/(lbs) 221 (487) 234 (516) 236 (520) 277 (611)
IP21/NEMA 1 (E1) [kg]/(lbs) 263 (580) 270 (595) 272 (600) 313 (690)
IP54/NEMA 12 (E1) [kg]/(lbs) 263 (580) 270 (595) 272 (600) 313 (690)
9
380 – 500 VAC
F frames
Output Power
Continuous SVLT,N [kVA] 554 610 610 686 686 776 776 873 873 1012 1012 1192
Intermittent SVLT,MAX [kVA] 831 671 915 754 1029 854 1164 960 1309 1113 1517 1311
Typical Shaft Output [kW] 450 500 500 560 560 630 630 710 710 800 800 1000
Rated Input Current IL,N [A] 779 857 857 964 964 1090 1090 1227 1227 1422 1422 1675
Output Current
Nominal Voltage
Continuous (441-500 V) IVLT,N [A] 730 780 780 890 890 1050 1050 1160 1160 1380 1380 1530
Intermittent (60 sec)* IVLT,MAX [A] 1095 858 1170 979 1335 1155 1575 1276 1740 1518 2070 1683
460 V
Output Power
Continuous SVLT,N [kVA] 582 621 621 709 709 837 837 924 924 1100 1100 1219
Intermittent SVLT,MAX [kVA] 872 684 932 780 1064 920 1255 1017 1386 1209 1649 1341
Typical Shaft Output [HP] 600 650 650 750 750 900 900 1000 1000 1200 1200 1350
Rated Input Current IL,N [A] 711 759 759 867 867 1022 1022 1129 1129 1344 1344 1490
Output Current
Continuous (441-500 V) IVLT,N [A] 730 780 780 890 890 1050 1050 1160 1160 1380 1380 1530
Intermittent (60 sec)* IVLT,MAX [A] 1095 858 1170 979 1335 1155 1575 1276 1740 1518 2070 1683
500 V
Output Power
Continuous SVLT,N [kVA] 632 675 675 771 771 909 909 1005 1005 1195 1195 1325
Intermittent SVLT,MAX [kVA] 948 743 1013 848 1156 1000 1364 1105 1507 1315 1793 1458
Typical Shaft Output [kW] 530 560 560 630 630 710 710 800 800 1000 1000 1100
Rated Input Current IL,N [A] 711 759 759 867 867 1022 1022 1129 1129 1344 1344 1490
Estimated power loss at rated maximum load** [W] 9492 10647 10631 12338 11263 13201 13172 15436 14967 18084 16392 20358
Efficiency 0.98 0.98 0.98 0.98 0.98 0.98
Output Frequency [Hz] 0-600 0-600 0-600 0-600 0-600 0-600
Max. cable cross-section to motor [mm2] 8 x 150 8 x 150 8 x 150 8 x 150 12 x 150 12 x 150
output terminals (per phase) [AWG] 8 x 300 mcm 8 x 300 mcm 8 x 300 mcm 8 x 300 mcm 12 x 300 mcm 12 x 300 mcm
Max. cable cross-section to load- [mm2] 4 x 120 4 x 120 4 x 120 4 x 120 4 x 120 4 x 120
sharing terminals (per -DC/+DC) [AWG] 4 x 250 mcm 4 x 250 mcm 4 x 250 mcm 4 x 250 mcm 4 x 250 mcm 4 x 250 mcm
Max. cable cross-section to regen- [mm2] 2 x 150 2 x 150 2 x 150 2 x 150 2 x 150 2 x 150
eration terminals (per -DC/+DC) [AWG] 2 x 300 mcm 2 x 300 mcm 2 x 300 mcm 2 x 300 mcm 2 x 300 mcm 2 x 300 mcm
Max. cable cross-section to brake [mm2] 4 x 185 4 x 185 4 x 185 4 x 185 6 x 185 6 x 185
resistor terminals (per -R/+R) [AWG] 4 x 350 mcm 4 x 350 mcm 4 x 350 mcm 4 x 350 mcm 6 x 350 mcm 6 x 350 mcm
Max. cable cross-section to input [mm2] 8 x 240 8 x 240 8 x 240 8 x 240 8 x 240 8 x 240
mains terminals (per phase) [AWG] 8 x 500 mcm 8 x 500 mcm 8 x 500 mcm 8 x 500 mcm 8 x 500 mcm 8 x 500 mcm
Max. external input line [A] 2000 2000 2000 2000 2500 2500
fuses (mains)
Enclosure Ratings and Weight
IP21/NEMA 1 [kg]/(lbs) 1004 (2214)† 1004 (2214)† 1004 (2214)† 1004 (2214)† 1246 (2748)† 1246 (2748)†
IP54/NEMA 12 [kg]/(lbs) 1004 (2214)† 1004 (2214)† 1004 (2214)† 1004 (2214)† 1246 (2748)† 1246 (2748)†
10
525 – 690 VAC
D frames 40-100 HP (30-75 kW)
Output Power
Continuous SVLT,N [kVA] 46 53 53 72 72 86 86 108
Intermittent SVLT,MAX [kVA] 73 59 85 80 116 94 129 118
Typical Shaft Output [kW] 30 37 37 45 45 55 55 75
Rated Input Current IL,N [A] 53 60 60 77 77 89 89 110
Output Current
Nominal Voltage
Output Power
Continuous SVLT,N [kVA] 46 54 54 73 73 86 86 108
Intermittent SVLT,MAX [kVA] 73 59 86 80 116 94 128 118
Typical Shaft Output [HP] 40 50 50 60 60 75 75 100
Rated Input Current IL,N [A] 51 58 58 74 74 85 85 106
Output Current
Continuous (551-690 V) IVLT,N [A] 46 54 54 73 73 86 86 108
Intermittent (60 sec)* IVLT,MAX [A] 74 59 86 80 117 95 129 119
690 V
Output Power
Continuous SVLT,N [kVA] 55 65 65 87 87 103 103 129
Intermittent SVLT,MAX [kVA] 88 71 103 96 140 113 154 142
Typical Shaft Output [kW] 37 45 45 55 55 75 75 90
Rated Input Current IL,N [A] 50 58 58 77 77 87 87 109
Estimated power loss at rated maximum load [W] 1355 1458 1459 1717 1721 1913 1913 2262
Efficiency 0.97 0.97 0.97 0.97
Output Frequency [Hz] 0-600 0-600 0-600 0-600
Max. cable cross-section to motor output [mm2] 2 x 70 2 x 70 2 x 70 2 x 70
terminals (per phase) [AWG] 2 x 2/0 2 x 2/0 2 x 2/0 2 x 2/0
Max. cable cross-section to loadsharing [mm2] 2 x 70 2 x 70 2 x 70 2 x 70
terminals (per -DC/+DC) [AWG] 2 x 2/0 2 x 2/0 2 x 2/0 2 x 2/0
Max. cable cross-section to brake resistor [mm2] 2 x 70 2 x 70 2 x 70 2 x 70
terminals (per -R/+R) [AWG] 2 x 2/0 2 x 2/0 2 x 2/0 2 x 2/0
Max. cable cross-section to input mains [mm2] 2 x 70 2 x 70 2 x 70 2 x 70
terminals (per phase) [AWG] 2 x 2/0 2 x 2/0 2 x 2/0 2 x 2/0
Max. external input line fuses (mains) [A] 125 160 200 200
Enclosure Ratings and Weight
IP00/Chassis (D3) [kg]/(lbs) 82 (181) 82 (181) 82 (181) 82 (181)
IP21/NEMA 1 ((D1) [kg]/(lbs) 96 (211) 96 (211) 96 (211) 96 (211)
IP54/NEMA 12 (D1) [kg]/(lbs) 96 (211) 96 (211) 96 (211) 96 (211)
11
525 – 690 VAC
D frames 100-200 HP (75-132 kW)
Output Power
Continuous SVLT,N [kVA] 108 131 131 154 154 191
Intermittent SVLT,MAX [kVA] 161 144 196 170 231 211
Typical Shaft Output [kW] 75 90 90 110 110 132
Rated Input Current IL,N [A] 110 130 130 158 158 198
Output Current
Nominal Voltage
Continuous (551-690 V) IVLT,N [A] 108 131 131 155 155 192
Intermittent (60 sec)* IVLT,MAX [A] 162 144 197 171 233 211
575 V
Output Power
Continuous SVLT,N [kVA] 108 130 130 154 154 191
Intermittent SVLT,MAX [kVA] 161 144 196 170 232 210
Typical Shaft Output [HP] 100 125 125 150 150 200
Rated Input Current IL,N [A] 106 124 124 151 151 189
Output Current
Continuous (551-690 V) IVLT,N [A] 108 131 131 155 155 192
Intermittent (60 sec)* IVLT,MAX [A] 162 144 197 171 233 211
690 V
Output Power
Continuous SVLT,N [kVA] 129 157 157 185 185 229
Intermittent SVLT,MAX [kVA] 194 172 235 204 278 252
Typical Shaft Output [kW] 90 110 110 132 132 160
Rated Input Current IL,N [A] 109 128 128 155 155 197
Estimated power loss at rated maximum load [W] 2264 2662 2664 3114 2953 3612
Efficiency 0.98 0.98 0.98
Output Frequency [Hz] 0-600 0-600 0-600
Max. cable cross-section to motor output [mm2] 2 x 70 2 x 70 2 x 70
terminals (per phase) [AWG] 2 x 2/0 2 x 2/0 2 x 2/0
Max. cable cross-section to loadsharing [mm2] 2 x 70 2 x 70 2 x 70
terminals (per -DC/+DC) [AWG] 2 x 2/0 2 x 2/0 2 x 2/0
Max. cable cross-section to brake resistor [mm2] 2 x 70 2 x 70 2 x 70
terminals (per -R/+R) [AWG] 2 x 2/0 2 x 2/0 2 x 2/0
Max. cable cross-section to input mains [mm2] 2 x 70 2 x 70 2 x 70
terminals (per phase) [AWG] 2 x 2/0 2 x 2/0 2 x 2/0
Max. external input line fuses (mains) [A] 250 315 350
Enclosure Ratings and Weight
IP00/Chassis (D3) [kg]/(lbs) 82 (181) 82 (181) 91 (201)
IP21/NEMA 1 (D1) [kg]/(lbs) 96 (211) 96 (211) 104 (230)
IP54/NEMA 12 (D1) [kg]/(lbs) 96 (211) 96 (211) 104 (230)
12
525 – 690 VAC
D frames 200-400 HP (132-315 kW)
VLT® AutomationDrive P160 T7 P160 T7 P200 T7 P200 T7 P250 T7 P250 T7 P315 T7 P315 T7
Output Power
Continuous SVLT,N [kVA] 191 241 241 289 289 343 343 398
Intermittent SVLT,MAX [kVA] 287 265 362 318 433 377 514 438
Typical Shaft Output [kW] 132 160 160 200 200 250 250 315
Rated Input Current IL,N [A] 198 245 245 299 299 355 355 408
Output Current
Nominal Voltage
Continuous (551-690 V) IVLT,N [A] 192 242 242 290 290 344 344 400
Intermittent (60 sec)* IVLT,MAX [A] 288 266 363 319 435 378 516 440
575 V
Output Power
Continuous SVLT,N [kVA] 191 241 241 289 289 343 343 398
Intermittent SVLT,MAX [kVA] 287 265 362 318 433 377 514 438
Typical Shaft Output [HP] 200 250 250 300 300 350 350 400
Rated Input Current IL,N [A] 189 234 234 286 286 339 339 390
Output Current
Continuous (551-690 V) IVLT,N [A] 192 242 242 290 290 344 344 400
Intermittent (60 sec)* IVLT,MAX [A] 288 266 363 319 435 378 516 440
690 V
Output Power
Continuous SVLT,N [kVA] 229 289 289 347 347 411 411 478
Intermittent SVLT,MAX [kVA] 344 318 434 381 520 452 617 526
Typical Shaft Output [kW] 160 200 200 250 250 315 315 400
Rated Input Current IL,N [A] 197 240 240 296 296 352 352 400
Estimated power loss at rated maximum load [W] 3451 4292 4275 5156 4875 5821 5185 6149
Efficiency 0.98 0.98 0.98 0.98
Output Frequency [Hz] 0-600 0-600 0-600 0-500
Max. cable cross-section to motor [mm2] 2 x 185 2 x 185 2 x 185 2 x 185
output terminals (per phase) [AWG] 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. cable cross-section to loadsharing [mm2] 2 x 185 2 x 185 2 x 185 2 x 185
terminals (per -DC/+DC) [AWG] 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. cable cross-section to brake [mm2] 2 x 185 2 x 185 2 x 185 2 x 185
resistor terminals (per -R/+R) [AWG] 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. cable cross-section to input [mm2] 2 x 185 2 x 185 2 x 185 2 x 185
mains terminals (per phase) [AWG] 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. external input line fuses (mains) [A] 350 400 500 550
Enclosure Ratings and Weight
IP00/Chassis (D4) [kg]/(lbs) 112 (247) 123 (271) 138 (304) 151 (334)
IP21/NEMA 1 (D2) [kg]/(lbs) 125 (277) 136 (301) 151 (334) 165 (364)
IP54/NEMA 12 (D2) [kg]/(lbs) 125 (277) 136 (301) 151 (334) 165 (364)
13
525 – 690 VAC
E frames
Output Power
Continuous SVLT,N [kVA] 376 448 409 498 498 568 568 600
Intermittent SVLT,MAX [kVA] 564 493 613 548 747 625 852 660
Typical Shaft Output [kW] 300 355 315 400 400 450 450 500
Rated Input Current IL,N [A] 381 453 413 504 504 574 574 607
Output Current
Nominal Voltage
Continuous (551-690 V) IVLT,N [A] 380 450 410 500 500 570 570 630
Intermittent (60 sec)* IVLT,MAX [A] 570 495 615 550 750 627 855 693
575 V
Output Power
Continuous SVLT,N [kVA] 378 448 408 498 498 568 568 627
Intermittent SVLT,MAX [kVA] 568 493 612 548 747 624 852 690
Typical Shaft Output [HP] 400 450 400 500 500 600 600 650
Rated Input Current IL,N [A] 366 434 395 482 482 549 549 607
Output Current
Continuous (551-690 V) IVLT,N [A] 380 450 410 500 500 570 570 630
Intermittent (60 sec)* IVLT,MAX [A] 570 495 615 550 750 627 855 693
690 V
Output Power
Continuous SVLT,N [kVA] 454 538 490 598 598 681 681 753
Intermittent SVLT,MAX [kVA] 681 592 735 657 896 749 1022 828
Typical Shaft Output [kW] 355 450 400 500 500 560 560 630
Rated Input Current IL,N [A] 366 434 395 482 482 549 549 607
Estimated power loss at rated maximum load [W] 5383 6449 5818 7249 7671 8727 8715 9673
Efficiency 0.98 0.98 0.98 0.98
Output Frequency [Hz] 0-500 0-500 0-500 0-500
Max. cable cross-section to motor out- [mm2] 4 x 240 4 x 240 4 x 240 4 x 240
put terminals (per phase) [AWG] 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. cable cross-section to loadsharing [mm2] 4 x 240 4 x 240 4 x 240 4 x 240
terminals (per -DC/+DC) [AWG] 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. cable cross-section to regeneration [mm2] 4 x 240 4 x 240 4 x 240 4 x 240
terminals (per -DC/+DC) [AWG] 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. cable cross-section to brake resis- [mm2] 2 x 185 2 x 185 2 x 185 2 x 185
tor terminals (per -R/+R) [AWG] 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm 2 x 350 mcm
Max. cable cross-section to input mains [mm2] 4 x 240 4 x 240 4 x 240 4 x 240
terminals (per phase) [AWG] 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. external input line fuses (mains) [A] 700 700 900 900
Enclosure Ratings and Weight
IP00/Chassis (E2) [kg]/(lbs) 221 (487) 221 (487) 236 (520) 277 (611)
IP21/NEMA 1 (E1) [kg]/(lbs) 263 (580) 263 (580) 272 (600) 313 (690)
IP54/NEMA 12 (E1) [kg]/(lbs) 263 (580) 263 (580) 272 (600) 313 (690)
14
525 – 690 VAC
F frames
Frame Size
F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
P710 P800 P900 P1M0 P1M2
VLT® HVAC Drive T7 T7 T7 T7 T7
VLT® Type
Output Power
Continuous SVLT,N [kVA] 628 727 727 847 847 941 941 1056 1056 1255
Intermittent SVLT,MAX [kVA] 942 800 1090 932 1270 1035 1412 1161 1583 1380
Typical Shaft Output [kW] 500 560 560 670 670 750 750 850 850 1000
Rated Input Current IL,N [A] 642 743 743 866 866 962 962 1079 1079 1282
Output Current
Nominal Voltage
Continuous (551-690 V) IVLT,N [A] 630 730 730 850 850 945 945 1060 1060 1260
Intermittent (60 sec)* IVLT,MAX [A] 945 803 1095 935 1275 1040 1418 1166 1590 1386
575 V
Output Power
Continuous SVLT,N [kVA] 627 727 727 847 847 941 941 1056 1056 1255
Intermittent SVLT,MAX [kVA] 941 800 1091 931 1270 1035 1412 1161 1584 1380
Typical Shaft Output [HP] 650 750 750 950 950 1050 1050 1150 1150 1350
Rated Input Current IL,N [A] 613 711 711 828 828 920 920 1032 1032 1227
Output Current
Continuous (551-690 V) IVLT,N [A] 630 730 730 850 850 945 945 1060 1060 1260
Intermittent (60 sec)* IVLT,MAX [A] 945 803 1095 935 1275 1040 1418 1166 1590 1386
690 V
Output Power
Continuous SVLT,N [kVA] 753 872 872 1016 1016 1129 1129 1267 1267 1506
Intermittent SVLT,MAX [kVA] 1129 960 1309 1117 1524 1242 1694 1394 1900 1656
Typical Shaft Output [kW] 630 710 710 800 800 900 900 1000 1000 1200
Rated Input Current IL,N [A] 613 711 711 828 828 920 920 1032 1032 1227
Estimated power loss at rated maximum load** [W] 9674 11315 10965 12903 12890 14533 14457 16375 15899 19207
Efficiency 0.98 0.98 0.98 0.98 0.98
Output Frequency [Hz] 0-500 0-500 0-500 0-500 0-500
Max. cable cross-section to motor output [mm2] 8 x 150 8 x 150 8 x 150 12 x 150 12 x 150
terminals (per phase) [AWG] 8 x 300 mcm 8 x 300 mcm 8 x 300 mcm 12 x 300 mcm 12 x 300 mcm
Max. cable cross-section to loadsharing [mm2] 4 x 120 4 x 120 4 x 120 4 x 120 4 x 120
terminals (per -DC/+DC) [AWG] 4 x 250 mcm 4 x 250 mcm 4 x 250 mcm 4 x 250 mcm 4 x 250 mcm
Max. cable cross-section to regeneration [mm2] 2 x 150 2 x 150 2 x 150 2 x 150 2 x 150
terminals (per -DC/+DC) [AWG] 2 x 300 mcm 2 x 300 mcm 2 x 300 mcm 2 x 300 mcm 2 x 300 mcm
Max. cable cross-section to brake resistor [mm2] 4 x 185 4 x 185 4 x 185 6 x 185 6 x 185
terminals (per -R/+R) [AWG] 4 x 350 mcm 4 x 350 mcm 4 x 350 mcm 6 x 350 mcm 6 x 350 mcm
Max. cable cross-section to input mains [mm2] 8 x 240 8 x 240 8 x 240 8 x 240 8 x 240
terminals (per phase) [AWG] 8 x 500 mcm 8 x 500 mcm 8 x 500 mcm 8 x 500 mcm 8 x 500 mcm
Max. external input line fuses (mains) [A] 2000 2000 2000 2000 2000
Enclosure Ratings and Weight
IP21/NEMA 1 [kg]/(lbs) 1004 (2214)† 1004 (2214)† 1004 (2214)† 1246 (2748)† 1246 (2748)†
IP54/NEMA 12 [kg]/(lbs) 1004 (2214)† 1004 (2214)† 1004 (2214)† 1246 (2748)† 1246 (2748)†
15
VLT® High Power Drive Special Conditions
60
40 35
20
0 30
0 10 20 30 40 50 60 0 500 1000 1500 2000 2500 3000
Max. Ambient Temperature [°C] Altitude [metres above sea level]*
95
100
80 90
Iout [%]
Iout [%]
60
40 85
20
0 80
0 10 20 30 40 50 60 0 500 1000 1500 2000 2500 3000
Max. Ambient Temperature [°C] Altitude [metres above sea level]*
As shown above, when the ambient temperature is 55° C, * 690 V drives are limited to 6560’ (2000 m) above sea level
high overload drives can provide 90% of their rated output based on PELV requirements.
current, and normal overload drives can provide 85% of
their rated output current.
For derating options related to carrier frequency, see the VLT® HVAC Drive, VLT® AQUA Drive
or VLT® AutomationDrive design guide.
16
VLT® High Power Drive Dimensions
74 420
(2.9) 765 m3/hr (16.5)
(450 CFM)
Min. 225 (8.9)
Air Space Outlet
170 m3/hr
(100 CFM)
1166
1209 (45.9)
981 (47.6)
(38.6)
Air Space Inlet
Min. 225 (8.9)
310
(12.2)
163 380
(6.4) (15.0)
417
(16.4) Optional pedestal 176F1827 available
for stand-alone floor mount installations
(adds 200 mm/7.9” to height)
D2 frame (floor or wall mount)
420
72 765 m3/hr (16.5)
(2.8) (450 CFM)
Min. 225 (8.9)
Air Space Outlet
170 m3/hr
(100 CFM)
1362 1589
(53.6) 1547
(62.6) (60.9)
Air Space Inlet
Min. 225 (8.9)
423
(16.6)
157 380
(6.2) (15.0)
417
(16.4) Optional pedestal 176F1827 available
for stand-alone floor mount installations
(adds 200 mm/7.9” to height)
Drives shown with optional disconnect switch
17
VLT® High Power Drive Dimensions
408
66 765 m3/hr 255 m3/hr (16.1)
(2.6) (450 CFM) (150 CFM)
Min. 225 (8.9)
Air Space Outlet
1046
(41.2) 997
818 (39.3)
(32.2)
147
Air Space Inlet
Min. 225 (8.9)
(5.8)
157
(6.2) 375
(14.8)
417
(16.4)
1327
(52.2)
1280
1099 (50.4)
(43.3)
161
Air Space Inlet
(6.3)
Min. 225 (8.9)
151 375
(5.9) (14.8)
417
(16.4) Drives shown with optional
disconnect switch
18
VLT® High Power Drive Dimensions
1444 m3/hr
(850 CFM) 600
72 (23.6)
(2.8)
Min. 225 (8.9)
Air Space Outlet
340 m3/hr
(200 CFM)
2000
(78.7)
1551
(61.1)
164
(6.5)
727
(28.6)
494
(19.4)
538
(21.2)
E2 frame (cabinet mount)
1547
(60.9)
1320
(52.0)
269
(10.6)
Air Space Inlet
Min. 225 (8.9)
157 498
(6.2) (19.6)
539
(21.2)
Drives shown with optional
disconnect switch
19
VLT® High Power Drive Dimensions
607
(23.9)
1400
(55.1) IP 21/NEMA 1
2100 m3/hr
IP 54/NEMA 12
1575 m3/hr
(927 CFM)
2280
(89.8)
2205
(86.8)
1497
(58.9)
2956 m3/hr
(1740 CFM)
607
(23.9)
1804
(71.0) IP 21/NEMA 1
2100 m3/hr
(1236 CFM)
Min. 200 (7.9)
Air Space Outlet
IP 54/NEMA 12
1575 m3/hr
(927 CFM)
2280
(89.8)
2205
(86.8)
1497
(58.9)
3941 m3/hr
(2320 CFM)
20
VLT® High Power Drive Dimensions
607
(23.9)
1997
(78.6) IP 21/NEMA 1
1444 m3/hr
IP 54/NEMA 12
2100 m3/hr
(1236 CFM)
2280
(89.3)
2205
(86.8)
1497
(58.9)
2956 m3/hr
(1740 CFM)
607
(23.9)
2401
(94.5) IP 21/NEMA 1
2800 m3/hr
(1648 CFM)
Min. 200 (7.9)
Air Space Outlet
IP 54/NEMA 12
2100 m3/hr
(1236 CFM)
2280
(89.8)
2205
(86.8)
1497
(58.9)
3941 m3/hr
(2320 CFM)
21
VLT® High Power Drive Options
Available on Frames
Typecode Position
D3/
4 D4/E2
Mains Shielding
Lexan® shielding mounted in front of incoming power terminals and input plate to protect from
accidental contact when the enclosure door is open.
D1/
4 D2/E1
4 F
22
VLT® High Power Drive Options
Available on Frames
Typecode Position
RFI Filters
VLT® Series drives feature integrated Class A2 RFI filters as standard. If additional levels of RFI/EMC
protection are required, they can be obtained using optional Class A1 RFI filters, which provide
suppression of radio frequency interference and electromagnetic radiation in accordance with EN 55011.
On F-frame drives, the Class A1 RFI filter requires the addition of the options cabinet.
Marine use RFI filters are also available. D/E/
F3/F4 5
NAMUR Terminals
NAMUR is an international association of automation technology users in the process industries,
primarily chemical and pharmaceutical industries in Germany. Selection of this option provides
standardised terminal connection and associated functionality as defined by NAMUR NE37.
Requires the selection of the MCB 113 Extended Relay option in typecode block 16.
F 5
23
VLT® High Power Drive Options
Available on Frames
Typecode Position
6 D/E/F
Regeneration Terminals
Allow connection of regeneration units to the DC bus on the capacitor bank side of the DC-link reactors
for regenerative braking. The F-frame regeneration terminals are sized for approximately ½ the power
rating of the drive. Consult the factory for regeration power limits based on the specific drive size and
voltage.
6 E/F
6 F3/F4
Loadsharing Terminals
These terminals connect to the DC-bus on the rectifier side of the DC-link reactor and allow for the
sharing of DC bus power between multiple drives. The F-frame loadsharing terminals are sized for
approximately 1/3 the power rating of the drive. Consult the factory for loadsharing limits based on the
specific drive size and voltage.
9 D/E/F
24
VLT® High Power Drive Options
Available on Frames
Typecode Position
Fuses
Fuses are highly recommended for fast-acting current overload protection of the variable frequency
drive. Fuse protection will limit drive damage and minimize service time in the event of a failure.
D/E/
F 9
Disconnect
A door-mounted handle allows for the manual operation of a power disconnect switch to enable and dis-
able power to the drive, increasing safety during servicing. The disconnect is interlocked with the cabinet
doors to prevent them from being opened while power is still applied.
D/E/
F3/F4 9
Circuit Breakers
A circuit breaker can be remotely tripped but must be manually reset. Circuit breakers are interlocked
with the cabinet doors to prevent them from being opened while power is still applied. When a circuit
breaker is ordered as an option, fuses are also included for fast-acting current overload protection of the
variable frequency drive.
F3/F4 9
Contactors
An electrically controlled contactor switch allows for the remote enabling and disabling of power to the
drive. An auxiliary contact on the contactor is monitored by the Pilz Safety if the IEC Emergency Stop
option is ordered.
F3/F4 9
25
VLT® High Power Drive Options
Available on Frames
Typecode Position
10 F
11 F
26
VLT® High Power Drive Options
Available on Frames
Typecode Position
External Temperature Monitoring
Designed for monitoring temperatures of external system components, such as the motor windings
and/or bearings. Includes eight universal input modules plus two dedicated thermistor input modules.
All ten modules are integrated into the drive’s safe-stop circuit and can be monitored via a fieldbus
network (requires the purchase of a separate module/bus coupler).
Additional features:
• One universal output, configurable for analog voltage or analogue current
• Two output relays (N.O.) F 11
• Dual-line LC display and LED dignostics
• Sensor lead wire break, short-circuit, and incorrect polarity detection
• Interface setup software
27
VLT® High Power Drive Options
Fieldbus
Typecode Position
28
VLT® High Power Drive Options
Applications
Typecode Position
MCB 101 General purpose I/O
Offers an extended number of control inputs and outputs:
• Incremental encoders
• SinCos encoders with Hyperface®
• Power supply for encoders 14
• EIA-422 interface
14
29
VLT® High Power Drive Options
Applications
Typecode Position
14 • 3 analogue inputs
• 3 analogue outputs
• Back-up power for Real-Time Clock
• Connection and monitoring of PTC sensors according to DIN 44081 and DIN 44082
14 • Capable of monitoring up to six thermistors in series
• Alarm logging, sensor leads short-circuit detection, and sensor leads break detection
• Integrated with the drive’s safe-stop function in accordance with Category 3 EN 954-1
• ATEX certified
30
VLT® High Power Drive Options
Applications
Typecode Position
MCO 305 Programmable Motion Controller
Provides synchronization (electronic shaft) capabilities, positioning and electronic cam control.
• 7 digital inputs
• 2 analogue outputs 16
• 4 SPDT relays
• Meets NAMUR recommendations
• Galvanic isolation capability
31
VLT® High Power Drive Accessories
Power Filtration
• Trouble-free operation 2300 2185 30.5 774 15.4 390 19.3 490 Floor 130B2395
0
630 598 17.2 436 10.5 265 16.4 415 Floor 130B2280
−500
765 726 28.9 734 17.6 446 20.5 520 Floor 130B2421
−1000
0 5 10 15 20 25 30 35 40
1350 1282 29.6 750 18 455 19.9 503 Floor 130B2422
20
10 182 173 18.3 463 24.1 610 17.4 440 Floor 130B2400
280 266 18.3 463 24.1 610 17.4 440 Floor 130B2401
Iu [A]
400 380 22.5 571 30.4 770 21.7 550 Floor 130B2402
380–500 V
−10
−20
500 475 11.9 300 26.4 670 19.3 490 Floor 130B2277
0 5 10 15 20 25 30 35 40
Time [ms] 750 712 23.8 602 30.4 770 21.7 550 Floor 130B2278
910 864 23.8 602 30.4 770 21.7 550 Floor 130B2405
NEMA Type 1 (IP20) Enclosure
0
45 42 11.3 285 6.7 170 10.3 260 Wall 130B2424
−500
75 71 11.3 285 6.7 170 10.3 260 Wall 130B2425
−1000
0 5 10 15 20 25 30 35 40 115 109 11.3 285 6.7 170 10.3 260 Wall 130B2426
20
165 157 20.6 522 26.4 670 19.7 500 Floor 130B2427
525–690 V
10
260 247 20.6 522 25.2 640 19.7 500 Floor 130B2428
310 294 20.6 522 26.4 670 19.7 500 Floor 130B2429
Iu [A]
−10
430 408 20.6 522 26.4 670 19.7 500 Floor 130B2238
−20
530 503 23.8 602 30.4 770 21.7 550 Floor 130B2239
0 5 10 15 20 25 30 35 40
Time [ms] 630 598 20.6 522 26.4 670 19.7 500 Floor 130B2274
Voltage and current with dU/dt filter 765 726 33.8 856 45.3 1150 33.9 860 Floor 130B2430
1350 1282 33.8 856 45.3 1150 33.9 860 Floor 130B2431
32
VLT® High Power Drive Accessories
Power Filtration
motor 480 456 25.6 650 23.7 600 24.9 630 Floor 130B2288
• Reduced semiconductor losses in the 660 627 29.3 742 24.5 620 24.7 626 Floor 130B2289
drive when using longer motor cables
750 712 27 684 34.7 880 26.2 664 Floor 130B2290
• Less EMI on unshielded motor cables
• Reduced voltage peaks 880 836 35.2 893 30 760 28.4 720 Floor 130B2291
Chassis (IP00) Enclosure
• Reduced electrical discharges in the 1200 1140 36.3 920 29.2 740 26.1 661 Floor 130B2292
motor, prolonging bearing life
• Prevent flashover in motor windings 45 42.5 14.9 378 12.3 310 14.6 370 Floor 130B2323
76 72 17.4 440 14.2 360 16.2 410 Floor 130B2324
115 109 18.9 480 17 430 17 430 Floor 130B2325
165 157 21.4 542 18.9 480 19.3 490 Floor 130B2326
260 247 19.5 493 21.7 550 21.3 540 Floor 130B2327
525–690 V
0
940 893 36.6 928 44.9 1140 22.1 560 Floor 130B2339
−500
1320 1250 38.2 968 33.5 850 29.2 740 Floor 130B2340
−1000
0 5 10 15 20 25 30 35 40
20 180 171 30.8 782 37.1 940 25.6 650 Floor 130B2311
10 260 247 30.8 782 37.1 940 25.6 650 Floor 130B2312
410 390 30.8 782 37.1 940 25.6 650 Floor 130B2313
Iu [A]
380–500 V
−10
480 456 29.3 742 41.4 1050 30 760 Floor 130B2314
−20
660 627 45.4 1152 50.8 1290 31.5 800 Floor 130B2315
0 5 10 15 20 25 30 35 40
Time [ms] 750 712 43.9 1115 50.8 1290 31.5 800 Floor 130B2316
NEMA Type 1 (IP20) Enclosure
Voltage and current without sine wave filter 880 836 45.4 1152 50.8 1290 31.5 800 Floor 130B2317
1200 1140 45.4 1152 50.8 1290 31.5 800 Floor 130B2318
1000
500
45 42.5 20.6 522 26.4 670 19.7 500 Floor 130B2343
Vuv [V]
0
76 72 20.6 522 26.4 670 19.7 500 Floor 130B2344
−500
115 109 20.6 522 25.2 640 19.7 500 Floor 130B2345
−1000
0 5 10 15 20 25 30 35 40 165 157 30.8 782 35.9 910 25.6 650 Floor 130B2346
260 247 30.8 782 37.1 940 25.6 650 Floor 130B2347
525–690 V
20
10
303 287 45.4 1152 50.8 1290 31.5 800 Floor 130B2348
430 408 45.4 1152 50.8 1290 31.5 800 Floor 130B2270
Iu [A]
−10
530 503 45.4 1152 50.8 1290 31.5 800 Floor 130B2271
−20
660 627 45.4 1152 50.8 1290 31.2 790 Floor 130B2381
0 5 10 15 20 25 30 35 40
Time [ms]
765 726 45.4 1152 50.8 1290 31.5 800 Floor 130B2382
Voltage and current with sine wave filter 940 893 45.4 1152 50.8 1290 31.5 800 Floor 130B2383
1320 1250 51.6 1310 51.3 1302 33.9 860 Floor 130B2384
33
VLT® High Power Drive Accessories
Harmonic Filtration
34
VLT® High Power Drive Accessories
Harmonic Filtration
* Above 460V, derating of the active filter power for the harmonic mitigation will occur
35
VLT® High Power Drive Accessories
36
VLT® High Power Drive Accessories
PC Software
VLT® MCT-10 Basic (available free of charge from the Danfoss web site) allows access
to a finite number of drives with limited functionality. The Advanced edition, offering
a higher level of functionality, is available from your Danfoss sales partner.
With VLT® MCT 31, you can determine whether harmonics will be an issue in your
installation, and if so, what strategies will be most cost-effective in addessing the
problem.
37
Ordering Typecode for D and E Frames
[1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18]
FC – – – – – – – – – X – X – SXX X – – – – – – –
38
Ordering Typecode for F Frames
[1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18]
FC – – – – – – G – C – – – – SXXX – – – – – – –
[1] Application 380-480/500V only (T4 or T5 in position [3]): [11] Auxiliary 24V Supply & External
102 VLT® HVAC Drive H4 RFI filter, Class A1 Temperature Monitoring
202 VLT® AQUA Drive HF RCM with Class A1 RFI filter X No option
302 VLT® AutomationDrive HH IRM with Class A1 RFI filter H 5 A, 24 V power supply (customer use)
HK* NAMUR terminals with Class A1 RFI filter J External temperature monitoring
[2] Power Size
RCM with NAMUR terminals and Class A1 5 A, 24 V power supply (customer use) &
P450 HM* G
RFI filter external temperature monitoring
P500
IRM with NAMUR terminals with Class A1
P560 HP* [12] LCP Language
RFI filter
P630 Standard language package including
P670 [6] Braking & Safety X English, German, French, Spanish, Danish,
P710 See ratings data on pages 8-15 X No brake IGBT Italian and Finnish
P750 for power ratings B Brake IGBT mounted Consult Danfoss for other language options
P800 T Safe Stop (FC 102/202 only; std. on 302)
[13] Fieldbus
P850 Brake IGBT plus Safe Stop
U AX No fieldbus option
P900 (FC 102/202 only; safe stop std. on 302)
A0 MCA 101 Profibus DP V1
P1M0 R Regeneration terminals
A4 MCA 104 DeviceNet
P1M2 Requires contactor (E, F, G or H in typecode block [9]);
includes safe stop for FC 102 and FC 202: A6 MCA 105 CANopen (FC 302 only)
[3] AC Line Voltage AG MCA 108 LonWorks (FC 102 only)
IEC Emergency stop pushbutton
T4 3Ø 380/480 VAC (no FC 302) M AJ MCA 109 BACnet (FC 102 only)
(with Pilz safety relay)
T5 3Ø 380/500 VAC (FC 302 only) IEC Emergency stop pushbutton with brake AN MCA 121 Ethernet I/P
N
T7 3Ø 525/690 VAC IGBT and brake terminals
[14] Application
IEC Emergency stop pushbutton with BX No application option
[4] Enclosure P
regeneration terminals
E21 IP21/NEMA 1 BK MCB 101 general purpose I/O
E54 IP54/NEMA 12 [9] Mains Input BR MCB 102 encoder input
IP21/NEMA 1 with cabinet light & IEC F1 & F2 frames: BU MCB 103 resolver input
L2X
230 V power outlet X No option BP MCB 105 relay expansion
IP54/NEMA 12 with cabinet light & IEC 7 Fuses BZ MCB 108 safety PLC interface
L5X
230 V power outlet A Fuses & loadsharing terminals MCB 109 analogue I/O & real-time clock
B0
IP21/NEMA 1 with cabinet light & NAM D Load sharing terminals backup
L2A
115 V power outlet F3 & F4 frames: B2 MCB 112 PTC thermistor
IP54/NEMA 12 with cabinet light & NAM 3 Mains disconnect & fuses BY MCO 101 extended cascade control
L5A
115 V power outlet
5 Mains disconnect, fuses & loadsharing
H21 IP21 with space heater and thermostat [15] Motion Control
E Mains disconnect, contactor & fuses
CX No motion control option
H54 IP54 with space heater and thermostat F Mains circuit breaker, contactor & fuses
IP21/NEMA1 with space heater, thermostat, MCO 305/350/351 motion control,
R2X Mains disconnect, contactor, load sharing C4 synchronising and/or positioning
light & IEC 230 V outlet G
terminals & fuses (For FC 302 only)
IP54/NEMA12 with space heater, Mains circuit breaker, contactor, load
R5X H C5 MCO 102 advanced cascade control
thermostat, light & IEC 230 V outlet sharing terminals & fuses
IP21/NEMA1 with space heater, thermostat, J Mains circuit breaker & fuses [16] Extended Relay
R2A
light, & NAM 115 V outlet
Mains circuit breaker, load sharing X No option
IP54/NEMA12 with space heater, K
R5A terminals & fuses R MCB 113 extended relay (FC 302 only)
thermostat, light, & NAM 115 V outlet
[10] Power Terminals & Motor Starters [17] Motion Software
[5] RFI Filter, Terminal & Monitoring Options X No option No motion software
F1 & F2 frames: E 30 A, fuse-protected power terminals Note: C4 option in [15] selected with
H2 RFI filter, Class A2 (standard) XX
30 A, fuse-protected power terminals no motion software in [17] will require
NAMUR terminals and F programming by qualified individual
HJ* & 2.5-4 A manual motor starter
Class A2 RFI filter MCO 350 synchronising control software
30 A, fuse-protected power terminals 10
F3 & F4 frames: G (must select C4 in position [15])
& 4-6.3 A manual motor starter
H2 RFI filter, Class A2 (standard) MCO 351 positioning control software
30A, fuse-protected power terminals 11
HE RCM with Class A2 RFI filter H (must select C4 in position [15])
& 6.3-10 A manual motor starter
HG IRM with Class A2 RFI filter 30 A, fuse-protected power terminals
J [18] Control Power Backup Input
& 10-16 A manual motor starter
HJ* NAMUR terminals and Class A2 RFI filter DX No DC input installed
K Two 2.5-4 A manual motor starters
D0 MCB107 24 VDC backup input
RCM with NAMUR terminals and Class A2 L Two 4-6.3 A manual motor starters
HL*
RFI filter
M Two 6.3-10 A manual motor starters
IRM with NAMUR terminals and Class A2 N Two 10-16 A manual motor starters
HN*
RFI filter High power VLT® Series variable
frequency drives can be configured
*MCB112 PTC Thermistor card (B2 in typecode position [14]) and MCB 113 Extended Relay Card
(R in typecode position [16]) required for NAMUR terminals – FC 302 only.
online at www.danfoss.com
39
What VLT® is all about
Danfoss Drives is the world leader among dedicated drives providers
– and still gaining market share.
Danfoss AS, Årenga 2, 1340 SKUI, Tlf. 67 17 72 00 Fax, 67 13 68 50, www.danfoss.no • drives@danfoss.no