Professional Documents
Culture Documents
Licensed from the SAE Digital Library Copyright 2011 SAE International
E-mailing, copying and internet posting are prohibited
Downloaded Wednesday, July 20, 2011 1:47:41 PM
SAE TECHNICAL
PAPER SERIES 2004-01-3187
400 Commonwealth Drive, Warrendale, PA 15096-0001 U.S.A. Tel: (724) 776-4841 Fax: (724) 776-5760 Web: www.sae.org
Author:Gilligan-SID:13591-GUID:59413614-129.93.16.3
Licensed to University of Nebraska
Licensed from the SAE Digital Library Copyright 2011 SAE International
E-mailing, copying and internet posting are prohibited
Downloaded Wednesday, July 20, 2011 1:47:41 PM
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise,
without the prior written permission of SAE.
SAE Permissions
400 Commonwealth Drive
Warrendale, PA 15096-0001-USA
Email: permissions@sae.org
Fax: 724-772-4891
Tel: 724-772-4028
ISSN 0148-7191
Copyright © 2004 SAE International
Positions and opinions advanced in this paper are those of the author(s) and not necessarily those of SAE.
The author is solely responsible for the content of the paper. A process is available by which discussions
will be printed with the paper if it is published in SAE Transactions.
Persons wishing to submit papers to be considered for presentation or publication by SAE should send the
manuscript or a 300 word abstract of a proposed manuscript to: Secretary, Engineering Meetings Board, SAE.
Printed in USA
Author:Gilligan-SID:13591-GUID:59413614-129.93.16.3
Licensed to University of Nebraska
Licensed from the SAE Digital Library Copyright 2011 SAE International
E-mailing, copying and internet posting are prohibited
Downloaded Wednesday, July 20, 2011 1:47:41 PM
2004-01-3187
Momentarily paralleling two synchronous generators can λkq = Lkq ⋅ ikq − Lkqq ⋅ iq (10)
be simulated using any of a number of suitable
simulation programs, however, the simulation only The problem formulation is depicted in Figure 1 along
predicts the transient results for a given design. While it with key variables and signal flow causality.
is certainly possible to iterate the design, checking each
iterate via simulation to determine if the design criteria
have been met, it is desirable to have design rules that
id1
can minimize the number of design iterations and limit ω,φ1
vd1
the range of design parameters investigated. This paper Generator #1
iq1
discusses the derivation of an approximate analytical (leading)
solution to paralleling two synchronous generators that vq1
can provide the basis for a design guide.
MATHEMATICAL DERIVATION
Coordinate
In order to investigate the voltage stress imposed on the Transformation
rotating rectifier diodes during out-of-phase paralleling of
two synchronous generators, the following simplified
problem was considered:
vq2
ω,φ1-θ
1) The two generators are initially unloaded with iq2
Generator #2
nominally 1.0 per unit (PU) terminal voltages. (lagging)
vd2
Unequal voltages are considered. id2
q2
λq = Lkqq ⋅ ikq − Lq ⋅ iq (7)
d2
λ f = L f ⋅ i f + Lkdf ⋅ ikd − L fd ⋅ id (8) d1
Author:Gilligan-SID:13591-GUID:59413614-129.93.16.3
Licensed to University of Nebraska
Licensed from the SAE Digital Library Copyright 2011 SAE International
E-mailing, copying and internet posting are prohibited
Downloaded Wednesday, July 20, 2011 1:47:41 PM
λkq1 = 0 (25) *
X qq = ω e ⋅ ( Lq"1 + cos2 θ ⋅ Lq"2 + sin 2 θ ⋅ Ld" 2 ) (38)
and similarly for generator #2:
*
X dq = ω e ⋅ sin θ ⋅ cos θ ⋅ ( Lq"2 − Ld" 2 ) (39)
λ f 2 = L f 2 ⋅ i f 20 (26)
recognizing that,
λkd 2 = Lkdf 2 ⋅ i f 20 (27)
ω e Ldf 1 ⋅ i f 10 = 3 ⋅V10 (40)
λkq 2 = 0 (28)
Using the constitutive relations for the flux linkages, ω e Ldf 2 ⋅ i f 20 = 3 ⋅V20 (41)
equations (6) through (10) and the above constant flux
linkages, it is possible to solve for the following currents:
and further letting
Author:Gilligan-SID:13591-GUID:59413614-129.93.16.3
Licensed to University of Nebraska
Licensed from the SAE Digital Library Copyright 2011 SAE International
E-mailing, copying and internet posting are prohibited
Downloaded Wednesday, July 20, 2011 1:47:41 PM
and
I q1c = ( X dq
*
⋅VA − X dd
*
⋅VB ) det (48)
1
x fl 2
I q1s = ( X dd
*
⋅VA + X dq
*
⋅VB ) det (49) i f 2 )min = i f 20 − ⋅
Nf 1 1 1
⋅ + +
N a 2 xmd 2 x fl 2 xkdl 2
− ( X dq )
2
det = X dd
*
⋅ X qq
* *
(50)
(57)
I d 2c
3 ⋅V10 Ldf
I q1s = = ⋅i (61)
where: ω e ⋅ Lq"1 Lq"1 f 10
Ldf
iq1 = ⋅ i f 10 ⋅ sin ω e t (63)
Lq"1
L ⋅ L − L ⋅ L
i f 1 = i f 10 ⋅ 1 + df 1 kd 1 kdf 1 2kdd 1 ⋅
L f 1 ⋅ Lkd 1 − Lkdf 1
(64)
Ldf
⋅ (1 − cos ω e t )
Ld"1
ANALYTICAL RESULTS
Author:Gilligan-SID:13591-GUID:59413614-129.93.16.3
Licensed to University of Nebraska
Licensed from the SAE Digital Library Copyright 2011 SAE International
E-mailing, copying and internet posting are prohibited
Downloaded Wednesday, July 20, 2011 1:47:41 PM
Figure 6. Field current minimum & angle Figure 7. Maximum stator current vs. phase mismatch
Several observations can be made about these results: Even though the calculated field currents don’t agree
very well with test data for large values of initial phase
1. The minimum field currents are the same for both mismatch, the absolute minimum calculated field current
generators due to using identical machines. of roughly 6 A agrees reasonably well with the tested
2. The leading generator reaches its field current
minimum first.
3. Peak reverse current occurs near 60° initial phase
mismatch, not 180° as may be expected.
4. The transients are sinusoidal oscillations at the rotor
electrical frequency.
5. The oscillations are undamped since all winding
resistance has been neglected.
6. The value of minimum field current is symmetrical
about 180°.
7. The value of minimum field current at 180° is equal
to that at 0° and both are equal to the initial value
required to produce the initial open circuit voltage.
value of about 7 A. Since the peak electrical over The reason(s) for the poor agreement with test data for
voltage stress on the diodes in the rotating rectifier large phase mismatches goes beyond the simplifications
bridge occurs at minimum field current, the simplified invoked for the sake of mathematical tractability. The
analysis should serve as a design guide to minimize or classical 5-state dq model evolved over the decades to
even eliminate the condition. The value of the closed describe the operation of a wound field synchronous
form solution is that the pertinent generator design machine for steady state operation and during normal
parameters are contained explicitly in the equations and transients. Evidently out-of-phase paralleling at large
can be grouped and/or arranged to derive inequality phase mismatches represents an abnormal transient for
constraints for design purposes. The most logical which the classical dq model is poorly suited to describe.
approach to a design guide would be to determine the Transient FEA with motion would have to be used to
range of generator parameters required to prevent the study the underlying reasons for the inadequacy of the
field current from ever going negative. Once derived, classical 5-state dq equivalent circuit model under such
such a design guide gives the generator designer extreme transient conditions.
significant freedom in realizing a practical design.
CONCLUSION
COMPARISON WITH SIMULATION
A simplified analytical solution to the problem of out-of-
In order to further investigate the degree to which the phase paralleling of two generators was derived.
simplified analytical solution accurately portrays, The solution neglects winding resistances, magnetic
calculated results were compared to simulation results. saturation, and zero sequence components and was
Out-of-phase paralleling transients between a 2-pole shown to reduce to the textbook 3-phase short analysis
75/90 kVA and a 2-pole 90/115 kVA 115 Vac, 400 Hz by zeroing the inductances and terminal voltage for
generator were simulated using the classical 5-state dq generator #2.
model of a wound field synchronous, including
approximate saturation effects based on the no-load Results were calculated for the maximum stator phase
saturation curve. The model was implemented in the currents and both the minimum and maximum field
Saber circuit simulation package and run for a range of currents experienced during the paralleling transient vs.
initial phase mismatches from 0 to 180°, with the 75/90 the initial phase mismatch, with equal terminal voltages.
kVA unit leading. Figure 10 shows the calculated Calculated results were compared with test results for
minimum phase currents and those predicted from out-of-phase paralleling between two 75/90 kVA, 4-pole,
simulation. 115 Vac, 400 Hz. aircraft generators. Calculated results
were also compared with simulation results for out-of-
phase paralleling between a 2-pole 75/90 kVA and a 2-
pole 90/115 kVA unit, both 115 Vac, 400 Hz. aircraft
generators.
REFERENCES NOMENCLATURE
Author:Gilligan-SID:13591-GUID:59413614-129.93.16.3