2018 China International Conference on Electricity Distribution Tianjin, 17-19 Sep.

2018

Analysis of Arc Model and Its Application in


Single-phase Grounding Fault Simulation in
Distribution Networks
BOWEN LIU1, JINRUI TANG1*, Member, IEEE, XIXIU WU1, JIAQI WANG1, CHEN YANG2

 network[1-4].
Abstract—The single-phase arc grounding fault is the main The single-phase arc grounding fault is the main fault
fault form in medium voltage distribution networks. In this paper, form in medium voltage distribution networks. In most cases,
the Mayr model is used to study the characteristic of single-phase arc model constructed by high-voltage circuit breakers are used
grounding fault current by adjusting the time constant τ and the
to study the fault characteristics in distribution networks [5-6].
dissipated power P, which belongs to the parameters of the Mayr
model. The equivalent sequence network diagram of the phase In this paper, the waveforms of the fault arc current and
A-to-ground fault in the feeder of the resonant ground voltage with different parameters are mainly analyzed when the
distribution system is used to construct the simplified circuit. And single-phase grounding fault of the feeder of the resonant
then the variation law of arc voltage and current waveform under grounding distribution system occurs. Firstly, the parameters in
the change of time constant τ and dissipated power P is analyzed. the simple arc model are debugged, and the actual relationship
The results show that increasing τ within a certain range or
between the arc waveform and the parameters is analyzed and
reducing P can change the arc from the arc extinguishing state to
the continuous arcing state. Comparing with the true measuring obtained. Secondly, the simplified circuit for single-phase
voltage and current, simulation results show that the simplified grounding fault in distribution networks is constructed and the
zero-mode circuit with Mayr arc model for distribution networks Mayr arc model is used in this circuit. Thirdly, the voltage and
can effectively obtain proper and valid voltage and current current waveforms are analyzed under different parameters of
waveforms arc model. The effectiveness of the arc model using in
Index Terms—arc model, dissipated power, fault arc, single-
single-phase grounding fault simulation in distribution
phase grounding fault
networks have been proved by simulation.

I. INTRODUCTION II. SINGLE-PHASE GROUND FAULT OF SIMPLE ARC CIRCUIT

T he establishment of a more practical grounding arc


model can effectively reflect the characteristics of the
actual grounding arc, and can be studied when the distribution
A. Influence of time constants
In order to obtain the basic relationship between arc
voltage and current changes with parameters, we changed the
network appears single-phase grounding faults. In the case of parameters in the simple arc model and the high voltage circuit
grounding faults, transient information such as voltage and breaker arc model.Understand the effect of parameter changes
current of the grounding arc of the fault point is used to find out on arc voltage and current waveform changes.
the characteristics of the zero-sequence current of each feeder
under different grounding arc models to maintain the power
system in the non-effectively grounded distribution

Manuscript received July 15, 2018. This work was supported by the
National Natural Science Foundation of China (Grant No. 51707139).
Bowen Liu, Xixiu Wu and Jiaqi Wang are with Wuhan University of
Technology, and now with the school of automation. (e-mail: 754760622@
qq.com, wuxixiu@163.com. 532851165 @qq.com,).
Jinrui Tang is with Wuhan University of Technology, and now with the
school of automation (Corresponding author, e-mail: tangjinrui001@126.com).
Chen Yang is with Wuhan Electric Power Technical College (e-mail:
627433866@qq.com).

Figure 1 Mayr arc models for a circuit breaker

CICED2018 Paper No. 201805280000363 Page1/7 1865


978-1-5386-6775-0/18/$31.00 ©2018 IEEE
2018 China International Conference on Electricity Distribution Tianjin, 17-19 Sep. 2018

Figure 2 simplified simulation circuit diagram


Take the simple arc model as an example. In the 10kV
fault circuit, the voltage source parameters are 8165V and
50HZ. Since the Mayr arc model is suitable for the simulation Fig. 5 Voltage change waveform of Mayr arc model
of small-current arcs, the arc parameter is τ=0.000344, (τ=0.000458)
P=10000W, and g=1 .e4. In the Mayr model, the waveform distortion of the arc
When other conditions are constant, change the value of τ voltage is more serious and its shape resembles that of a saddle.
and set it to τ = 0.000172, 0.000344, 0.000458. Observe the arc In addition, for each half-wave, the first half-wave arc voltage
voltage and current waveform changes along with the is slightly higher than the second half wave, which is due to the
following three parameters: fact that the temperature of the first half wave arc is slightly
lower than the temperature of the second half wave[7].
It can be seen from the experimental waveform that at τ =
0.000172, the arc model does not play a role at this time. When
τ reaches a certain value, the AC arc voltage waveform exhibits
a distinct nonlinear characteristic. Specifically, the starting arc
voltage is high, and it quickly falls and then maintains at an
approximately constant voltage level.Then an arc extinguishing
voltage lower than the arcing voltage occurs, and it quickly falls
until the current passes zero[8]. As the parameter τ increases, the
peak voltage decreases and the degree of distortion slows.

Fig. 3 Voltage change waveform of Mayr arc model


(τ=0.000172)

Fig. 6 Current change waveform of Mayr arc model


(τ=0.000172)
It can be seen from the experimental waveform that the
current of the arc model is 0 at τ=0.000172.When τ reaches a
certain value, the current waveform resembles a sine wave.
However, the change is slow at the current zero crossing, with
Fig. 4 Voltage change waveform of Mayr arc model obvious "zero rest" characteristics. As the parameter τ increases,
(τ=0.000344) the arc current waveform peaks unchanged[9].
However, the characteristics of slow changes at zero
crossings gradually weakened and the phenomenon of “zero
rest” weakened.

CICED2018 Paper No. 201805280000363 Page2/7 1866


2018 China International Conference on Electricity Distribution Tianjin, 17-19 Sep. 2018

Fig. 7 Current change waveform of Mayr arc model


(τ=0.000344)
Fig. 10 Voltage change waveform of Mayr arc model
(P =10000)

Fig. 8 Current change waveform of Mayr arc model


(τ=0.000172)
B. Dissipation power effect
Let's look at other conditions to maintain the same arc Fig. 11 Voltage change waveform of Mayr arc model
parameter τ = 0.000344, change the value of P, set it to 5000, (P =15000)
10000, 15000.

Fig. 12 Current change waveform of Mayr arc model


(P =5000)
Fig. 9 Voltage change waveform of Mayr arc model For the arc current at P=15000, the current of the arc model is
(P =5000) 0. When P decreases to a certain value, the current waveform is
similar to a sine wave, but it changes slowly at the current
From the experimental waveform, it can be seen that when
zero-crossing, with a clear “zero-off” characteristic.
P=15000, the arc model does not play a role at this time and is
With the increase of parameter P, the peak value of the arc
in the arc extinguishing state. When P reaches a certain value,
current waveform is basically unchanged; there is a
the AC arc voltage waveform exhibits a distinct nonlinear
zero-shutdown phenomenon, and the phenomenon of zero rest
characteristic. As the parameter P increases, the basic
increases in a certain range.
waveform does not change, and the voltage peak becomes
larger.

CICED2018 Paper No. 201805280000363 Page3/7 1867


2018 China International Conference on Electricity Distribution Tianjin, 17-19 Sep. 2018

ES ZS1 ZT1 If1

X1C Ug1 If/3

ZS2 ZT2 If2


3R f
X2C Ug2

ZS0 If0

3L X0C Ug0
Fig. 13 Current change waveform of Mayr arc model
(P =10000)
Figure 15 Sequence network interconnection for
single-line-to-ground fault

On the basis of this figure, X1C、X2C 、ZS0、ZS1、ZS2、


ZT1、ZT2, etc. are simplified through circuit analysis, and the
smaller value is ignored. The resulting simulation circuit
diagram is as follows:
L

Fig. 14 Current change waveform of Mayr arc model AC Mayr arc model C
(P =15000)

III. SINGLE-PHASE GROUND FAULT OF RESONANT NETWORK


A. Circuit introduction Figure 16 simplified simulation circuit diagram
In the resonant grounding distribution system, a B. Parametric analysis
single-phase (A-phase) ground fault occurs on the feeder. A The parameters in the literature "Analysis of the dynamic
corresponding sequence network diagram is formed based on adjustment characteristics of the zero-sequence current with the
the symmetrical component method, as shown in the figure. compensation of the distribution line of the distribution
X0C 、 X1C and X2C are the zero-sequence, network" are calculated, and the corresponding values are
positive-sequence, and negative-sequence capacitive brought into the simulation circuit. The specific parameters are:
reactances of the distribution line, ZT1 and ZT2 are the positive R=3, L=0.8934H, C =0.0357F.
and negative sequence equivalent impedances of the The Mayr model is actually suitable for small current
transformer, ZS0 、 ZS1 and ZS2 are the system-side zero circuits, and theoretical analysis should lead to better waveform
sequences, respectively. Equivalent impedance of positive and results. But actually adjusting the arc parameter τ= 0.0344, P =
negative and negative sequences, ES is the system-side 10000W, = 1.e4. The simulation waveform is as follows.
generator equivalent potential (only the positive sequence Through the above arc voltage and current waveforms, it
component), L is the inductance of the arc suppression coil, and can be found that at this time the state of the arc is extinction,
the current is always zero, and the arc does not produce any
R f is the ground fault resistance at the fault point[10].
effect.

CICED2018 Paper No. 201805280000363 Page4/7 1868


2018 China International Conference on Electricity Distribution Tianjin, 17-19 Sep. 2018

voltage waveform of the high voltage arc is severely distorted,


and its shape is similar to a "saddle" shape. In addition, for
each half wave, the first half wave voltage is slightly higher
than the second half wave. The current waveform is similar to
a sine wave, but it changes slowly at current zero crossings,
with a distinct "zero break" characteristic.

Fig. 17 Voltage change waveform of Mayr arc model


(τ=0.0344 P =10000)

Fig. 19 Voltage change waveform of Mayr arc model


(τ=0.01275 P =5000)

Fig. 18 Current change waveform of Mayr arc model


(τ=0.0344 P =10000)

At this time, the parameters τ and P are subjected to


multiple values. According to the law obtained in the simple
arc model, the voltage peak decreases as the parameter Fig. 20 Current change waveform of Mayr arc model
increases, and the degree of distortion becomes slower. With (τ=0.01275 P =5000)
the increase of the parameters, the peak value of the arc
current waveform is basically unchanged and there is a In contrast, the low-voltage arc is significantly different,
zero-shutdown phenomenon. So the parameters should be the shape of the low-voltage arc voltage is similar to that of the
within a certain range, and to obtain the correct result by wave, and the amplitude of the vibration gradually becomes
increasing τ to reducing P. larger, and then suddenly becomes smaller, repeating this
Continue to debug the parameters to get the result. The arc situation. The arc current is also similar to a wave shape,
parameters are as shown in the figure below: τ= 0.01275, P = fluctuating up and down in a small range, generating large
5000W, = 1.e4. fluctuations when the arc is generated, and then recovering,
From this arc voltage and current waveform, it can be seen repeating this situation.
that under this parameter, the arc is arc-fired once in several Continue to adjust the parameters as shown below: τ=
cycles, and then the arc is extinguished, and the arc is 0.0255, P = 5000W, = 1.e4.
repeated for a while, compared with other papers that study From the above results the arc voltage current waveform,
the variation of the high-voltage arc waveform. As a result, the arc is equivalent to a metallic ground. In real life, it is
the arc waveform is suitable for the case of a small current common for trunks to stand on a single-phase line and the
circuit, and the obtained waveform is complicated, and the trunk is directly burnt to produce a metallic ground. The

CICED2018 Paper No. 201805280000363 Page5/7 1869


2018 China International Conference on Electricity Distribution Tianjin, 17-19 Sep. 2018

current and voltage waveforms are close to a sine wave at this


time.

Fig. 24 Current change waveform of Mayr arc model


Fig. 21 Voltage change waveform of Mayr arc model (τ=0.0225 P =7000)
(τ=0.0255 P =5000)

IV. FORMULA DERIVATION


The derivation of the circuit is performed under the
assumption that the parameters are known, and it is hoped that
the calculation formula for arc voltage and current can be
derived successfully:
1 dg 1  u  i 
=  -1 (1)
g dt  m  Ploss 
di
U c =U L =3L L (2)
dt
dI
3R f  Ic +IL  +3L  L =E (3)
dt
Fig. 22 Current change waveform of Mayr arc model
di L
(τ=0.0225 P =5000) d(3L  ) 2
i=i c +i L =X oc  dt +i =3LX  d i L +i (4)
L oc L
dt dt 2
Then the magnitude of the dissipated power P is changed.
Study the effect of parameter P on continuous arcing. E=3R f i (5)
Solved by the above formula:

 d 2i  di
E=3R f  3LX oc 2L +i L  +3L L (6)
 dt  dt
d 2iL di
9R f LXoc 2
+3R f i L +3L L =8167sin 100 t  (7)
dt dt

Since the change of the arc resistance is a transient change,


we study the transient formula in the whole circuit into the
analysis, and hope to get the relationship between the arc
voltage and the transient change of the current. As can be seen
from the above equation, the arc resistance is a non-linear
Fig. 23 Voltage change waveform of Mayr arc model resistance element that varies with voltage and current. The
(τ=0.0255 P =7000) formula is first-order differential equations.

CICED2018 Paper No. 201805280000363 Page6/7 1870


2018 China International Conference on Electricity Distribution Tianjin, 17-19 Sep. 2018

Trying to solve this second-order non-homogeneous REFERENCES


differential equation, the general solution and special solution [1] Nagy I. Elkalashy, Matti Lehtonen, Hatem A. Darwish, et al. Modeling
are more complicated. And the arc resistance and the and Experimental verification of high impedance arcing fault in medium
differential equation are coupled. voltage networks[J]. IEEE Transactions on Dielectrics and Electrical
Insulation, 2007, 14(2): 375-383.
It is difficult to find the corresponding solution if the first [2] Toshiya Ohtaka, Viktor Kertesz, Rene Peter Paul Smeets. Novel
differential equation of the resistance is brought in. So here we black-box arc model validated by high-voltage circuit breaker testing[J].
only choose to use simulation to illustrate the arc model. But it IEEE Transactions on Power Delivery, 2018, 33(4): 1835-1844.
is not difficult to see that the parameters τ and P have a great [3] Schavemaker P. H. Vander Sluis L. An Improved Mayr-Type Arc Model
Based on Current-Zero Measurements[J]. IEEE Transactions on Power
influence on the arc model, and their changes directly affect the Delivery, 2000, 15(2): 580-584.
arc voltage and current waveform[11]. [4] LIU Junyong, GAO Hongjun, MA Zhao, et al. Review and prospect of
From these two formulas, the related tool can be used to active distribution system planning[J]. Journal of Modern Power
derive the relevant curve change law. Further research will be Systems and Clean Energy, 2015, 3(4): 457-467.
[5] LI Feng, XU Bingyin, YAN Tingchun. Modeling and simulation of arcs
conducted later. We put the above formula into the MATLAB. for cable fault location in ARM mode[J]. Automation of Electric Power
Draw the waveform of the arc voltage and current as a function Systems, 2014, 38(11): 104-108.
of time in MATLAB. From this we can infer the correctness of [6] XU Ye, GUO Moufa, CHEN Bin, et al. Modeling and simulation
the model. Through the two methods of simulation and formula analysis of arc in distribution network[J]. Power System Protection and
Control, 2015, 43(7): 57-64.
analysis, the law of parameter change and waveform change is [7] HU Zuo, LI Xinran, LI Peiqiang. Method of fault line location and its
obtained at the same time. implementation[J]. High Voltage Engineering, 2007, 33(1): 41-44.
So next, our research direction is to combine the [8] LIU Jian, ZHANG Xiaoqing, LI Pinde, et al. A novel approach treating
simulation rules and formulas involved in this article to further single-phase ground fault in distribution system[J]. Power System
Technology, 2016, 40(11): 3586-3590.
explore and study the arc voltage and current formula. [9] TANG Jinrui, YIN Xianggen, ZHANG Zhe, et al. Survey of fault
On the theoretical level, it is necessary to solve the location technology for distribution networks[J]. Electric Power
problem of why the waveform changes in this way, and Automation Equipment, 2013, 33(5): 7-13.
calculate the value of the arc voltage and current at each [10] Yuanchao Wang,Zhihan Yang,Zongxi Xie. Research of load leveling
strategy for electric arc furnace in iron and steel enterprises[C]. Abstracts
moment. This will be the key issue for future research. of International Conference on Mechanics, Materials and Structural
Engineering. 2016.
V. CONCLUSION [11] Mokhtari H,Hejri M.A new three phase time-domain model for electric
arc furnaces using MATLAB. Asia Pacific Transmission and
Different from the traditional high-voltage circuit breaker Distribution Conference and Exhibition. 2002.
arc model, this paper puts the Mayr arc model into the
single-phase ground fault model of the distribution network. Jinrui Tang (M’2017) , received his Ph.D. degree in electrical engineering from
Some useful conclusions are drawn as follows: Huazhong University of Science and Technology, Wuhan, China, in 2014.
Currently, he is an associate professor of the department of electrical
(1) In the single-phase grounding arc fault of the engineering in the School of Automation, Wuhan University of Technology.
distribution network, the arcing and arc-extinguishing of the arc His research focuses on protection and control of electric distribution network.
has certain randomness. Each cycle will not produce the arc
phenomenon, arc parameters directly affects the frequency of
arcing. This is different from the circuit breaker obviously.
(2) In the single-phase ground fault of the distribution
network, the time constant τ and the dissipated power P have a
great influence on the arc model. Within a certain range, proper
adjustment of the arc parameters τ and P enables the arc to
switch between arc extinguishing, periodic arcing, and
continuous arcing. Specifically, to increase the parameter τ,
decreasing the parameter P enables the arc to develop in the
direction of continuous arcing. And as the parameter τ increases,
the voltage peak decreases, the degree of distortion becomes
slower, and the current peak decreases. As the parameter P
increases, the voltage peak increases and the peak value of the
arc current waveform remains substantially unchanged.
However, to obtain the values of the parameters τ and P at the
critical point of arcing and extinction, further research is
needed.