Abstract—The single-phase arc grounding fault is the main The single-phase arc grounding fault is the main fault
fault form in medium voltage distribution networks. In this paper, form in medium voltage distribution networks. In most cases,
the Mayr model is used to study the characteristic of single-phase arc model constructed by high-voltage circuit breakers are used
grounding fault current by adjusting the time constant τ and the
to study the fault characteristics in distribution networks [5-6].
dissipated power P, which belongs to the parameters of the Mayr
model. The equivalent sequence network diagram of the phase In this paper, the waveforms of the fault arc current and
A-to-ground fault in the feeder of the resonant ground voltage with different parameters are mainly analyzed when the
distribution system is used to construct the simplified circuit. And single-phase grounding fault of the feeder of the resonant
then the variation law of arc voltage and current waveform under grounding distribution system occurs. Firstly, the parameters in
the change of time constant τ and dissipated power P is analyzed. the simple arc model are debugged, and the actual relationship
The results show that increasing τ within a certain range or
between the arc waveform and the parameters is analyzed and
reducing P can change the arc from the arc extinguishing state to
the continuous arcing state. Comparing with the true measuring obtained. Secondly, the simplified circuit for single-phase
voltage and current, simulation results show that the simplified grounding fault in distribution networks is constructed and the
zero-mode circuit with Mayr arc model for distribution networks Mayr arc model is used in this circuit. Thirdly, the voltage and
can effectively obtain proper and valid voltage and current current waveforms are analyzed under different parameters of
waveforms arc model. The effectiveness of the arc model using in
Index Terms—arc model, dissipated power, fault arc, single-
single-phase grounding fault simulation in distribution
phase grounding fault
networks have been proved by simulation.
Manuscript received July 15, 2018. This work was supported by the
National Natural Science Foundation of China (Grant No. 51707139).
Bowen Liu, Xixiu Wu and Jiaqi Wang are with Wuhan University of
Technology, and now with the school of automation. (e-mail: 754760622@
qq.com, wuxixiu@163.com. 532851165 @qq.com,).
Jinrui Tang is with Wuhan University of Technology, and now with the
school of automation (Corresponding author, e-mail: tangjinrui001@126.com).
Chen Yang is with Wuhan Electric Power Technical College (e-mail:
627433866@qq.com).
ZS0 If0
3L X0C Ug0
Fig. 13 Current change waveform of Mayr arc model
(P =10000)
Figure 15 Sequence network interconnection for
single-line-to-ground fault
Fig. 14 Current change waveform of Mayr arc model AC Mayr arc model C
(P =15000)
d 2i di
E=3R f 3LX oc 2L +i L +3L L (6)
dt dt
d 2iL di
9R f LXoc 2
+3R f i L +3L L =8167sin 100 t (7)
dt dt