Professional Documents
Culture Documents
Authorized licensed use limited to: Universidad de chile. Downloaded on July 07,2020 at 15:59:02 UTC from IEEE Xplore. Restrictions apply.
2
Authorized licensed use limited to: Universidad de chile. Downloaded on July 07,2020 at 15:59:02 UTC from IEEE Xplore. Restrictions apply.
3
It can be seen when the fault resistance is equal to zero, the ( Z S 0 A + 0.5 Z 0 L )Z ST
Z 0 A = ( p − 0.5 ) p Z 0 L + (18)
measured impedance at the relaying point is equal to the Z S 0 A + 0.5 Z 0 L + Z ST
impedance of the line section between relaying and fault
Z ST
points. The power system conditions only affect the measured C11 = (19)
impedance in the presence of fault resistance. Z S 1 A + 0.5 Z 1L + Z ST
When a STATCOM is introduced to a power system, the Z ST
C00 = (20)
above equations would vary. This variation not only depends Z S 0 A + 0.5 Z 0 L + Z ST
on the STATCOM parameters, but also to its installation
( 0.5 Z 1L + Z 1SB )( 1 − EST ) + Z ST ( 1 − h e − jδ )
location. Therefore, the modified equations are presented for Kδ =
three installation points, i.e. relaying point, mid-point, and ( Z 1SA + 0.5 Z 1L )(( p − 0.5 ) Z 1 L h e − jδ + Z 1B EST ) (21)
remote end. In the following sub-section, STATCOM is + Z ST ( Z 1B + ( Z 1SA + P Z 1 L )h e − jδ )
represented by its source voltage, EST, and its natural coupling − ( 0.5 Z 1 L + Z 1SB ) + ( Z 1SA + 0.5 Z 1L )h e − jδ
reactance, ZST.
+ ( Z 1SA + Z 1L + Z 1SB )EST
A. STATCOM at the Near End K'δ = (22)
( Z 1SA + 0.5 Z 1 L )(( p − 0.5 ) Z 1L h e − jδ + Z 1B EST )
In this case STATCOM is not present in the fault loop. + Z ST ( Z 1 B + ( Z 1SA + P Z 1L )h e − jδ )
Here, some of the above equations are modified as below:
Z Z Z A = p Z1L
Z 1 A = p Z 1L + S 1 A ST (11)
Z S 1 A + Z ST ⎡( p − 0.5 )Z 1L ( Z Σ + 3 R f )K'δ + ⎤
⎢ ⎥ (23)
Z S 0 A Z ST ⎢⎣2C1 ( 1 − C11 ) + C0 ( 1 − C00 )( 1 + 3 K 0 L ) + 3 R f ⎥⎦
Z0 A = p Z0 L + (12) +
Z S 0 A + Z ST ( Z Σ + 3 R f )Kδ + 2C1C11 + C0 C00 ( 1 + 3 K 0 L )
− Z 1SA ( h e − jδ − EST ) + Z ST ( 1 − h e − jδ ) It can be seen that in this case the measured impedance at the
Kδ =
Z 1SA ( p Z 1L h e − jδ + Z 1B EST ) (13) relaying point is affected by STATCOM parameters, even in
the absence of the fault resistance.
+ Z ST ( Z 1B + ( Z 1SA + P Z 1 L )h e − jδ )
It can be seen that in the absence of fault resistance, the C. STATCOM at the Remote End
measured impedance is equal to the actual impedance to the In this case STATCOM is installed at the remote bus of the
fault point. transmission line. Therefore, STATCOM is not present in the
fault loop. Here, the equations should be modified as:
B. STATCOM at the Mid-Point
Z Z
In this case STATCOM is not present in the fault loop Z 1B = ( 1 − p )Z 1L + S 1B ST (24)
Z S 1B + Z ST
when the fault occurs on the line section between the relaying
point and the mid-point. On the other hand, when the fault Z S 0 B Z ST
Z 0 B = ( 1 − p )Z 1L + (25)
occurs at the line section between the mid-point and the Z S 0 B + Z ST
remote end, STATCOM is included in the fault loop. In the Z 1SB ( 1 − EST ) + Z ST ( 1 − h e − jδ )
former case, some of the mentioned equations should be Kδ =
Z 1SB (( 1 − p ) Z 1L + Z 1 A EST ) (26)
modified as follow: − jδ
( 0.5 Z 1L + Z S 1 B )Z ST + Z ST (( 1 − p ) Z 1L + Z 1SB + Z 1 A h e )
Z 1B = ( 0.5 − p ) p Z 1L + (14)
0.5 Z 1L + Z S 1B + Z ST It can be seen that in this case when the fault resistance is
equal to the zero, the measured impedance is equal to the
( 0.5 Z 0 L + Z S 0 B )Z ST
Z 0 B = ( 0.5 − p ) p Z 0 L + (15) impedance of the line section which is located between the
0.5 Z 0 L + Z S 0 B + Z ST relaying and fault points.
( 0.5 Z 1L + Z 1SB )( 1 − EST ) + Z ST ( 1 − h e − jδ )
Kδ =
( 0.5 Z 1L + Z 1SB )(( 0.5 − p ) Z 1L + Z 1 A EST ) (16) IV. EFFECTS OF STATCOM ON DISTANCE RELAY TRIPPING
− jδ CHARACTERISTIC
+ Z ST (( 1 − p )Z 1 L + Z 1SB + Z 1 A h e )
The impacts of the installation of a STATCOM on a
It can be seen that in this case also the measured impedance in
transmission line have been tested for a practical system. A
the absence of the fault resistance does not deviate from its
400 kV Iranian transmission line with a length of 300 km has
actual value.
been used for this study. The structure of this line is
When the fault is located at the line section between the
mentioned in [8]. By utilizing the Electro-Magnetic Transient
mid-point and the remote end, STATCOM is present in the
Program (EMTP) [9] various sequence impedances of the line
fault loop and therefore, influences the measured impedance.
are evaluated according to its physical dimensions. The
Here, the mentioned equations should be modified as:
calculated impedances and the other parameters of the system
( Z + 0.5 Z 1L )Z ST
Z 1 A = ( p − 0.5 ) p Z 1L + S 1 A (17) are as follow:
Z S 1 A + 0.5 Z 1L + Z ST R1L = 0.01133 Ω/km
X1L = 0.3037 Ω/km
3
Authorized licensed use limited to: Universidad de chile. Downloaded on July 07,2020 at 15:59:02 UTC from IEEE Xplore. Restrictions apply.
4
R0L = 0.1535 Ω/km STATCOM is also shown in the dotted form for comparison.
X0L = 1.1478 Ω/km It can be seen that even when STATCOM is not active, i.e.
Z1SA = 8 ∠ 85º Ω its current is zero; it slightly affects the measured impedance
Z0SA = 12 ∠ 75º Ω at the relaying point. The measured resistance decreases
Z1SB = 16 ∠ 85º Ω slightly as well as the measured reactance. Here the decrease
Z0SB = 24 ∠ 85º Ω in the resistance is more considerable.
h = 0.96 Fig. 6 shows the effect of the variation of IST on the
δ = 16º measured impedance at the relaying point. Here IST takes the
In the absence of STATCOM, Fig. 4 shows the measured values of 1.0, 0.5, 0.0, –0.5, and –1.0.
impedance at the relaying point when fault resistance varies 100
from 0 to 200 ohms and the fault point varies from the
90
relaying point to the remote end of the transmission line. ( -1.0 )
80 ( 0.0 )
( 1.0 )
100
70
Reactance, X (Ohms)
90
60
80
50
70
40
Reactance, X (Ohms)
60
30
50
20
40
10
30
0
0 50 100 150 200 250 300 350
20
Resistance, R (Ohms)
10
Fig. 6. Variation of tripping characteristic with STATCOM at relaying point
0
0 50 100 150 200 250 300 350 It can be seen that as STATCOM current varies from the
Resistance, R (Ohms)
Fig. 4. Distance relay tripping characteristic without STATCOM lagging to the leading mode, the measured reactance is
increased while the measured resistance variation is not
Normally a STATCOM controls its connecting point considerable, slight decreasing. In the case of the low fault
voltage according to its controlling strategy. Therefore, resistance, the measured impedance is almost unchanged.
STATCOM parameters vary when the loading conditions of
B. STATCOM at the Mid-Point
the power system are changed. But in this study the
operational conditions of the power system are assumed to be Fig. 7 shows the tripping characteristic when IST is equal to
constant and it is assumed these conditions are achieved by zero, i.e. STATCOM is not active.
the different STATCOM operational parameters. Here 140
value while the leading current is shown by the negative value. 100
Reactance, X (Ohms)
100 40
90
20
80
70 0
0 50 100 150 200 250 300 350
Reactance, X (Ohms)
Resistance, R (Ohms)
60
Fig. 7. Tripping characteristic with STATCOM at the mid-point
50
Authorized licensed use limited to: Universidad de chile. Downloaded on July 07,2020 at 15:59:02 UTC from IEEE Xplore. Restrictions apply.
5
100
( 0.5 ) It can be seen that even when STATCOM is not active, it
Reactance, X (Ohms)
60
mode. On the other hand, the measured reactance varies
50
greatly when STATCOM changes its operation mode. As it
40
can be seen in Fig. 8 the variation of the measured reactance is
not uniform along the transmission line in the lower and upper 30
increases. When the operating mode of STATCOM is Fig. 10. Variation of tripping characteristic with STATCOM at remote end
changed from the lagging to the leading mode, in the upper
part, the measured impedance in case of the low fault It can be seen that as the operational mode of STATCOM
resistance increases, while for the high magnitudes of the fault varies from the lagging to the leading mode, the measured
resistance the measured reactance decreases considerably, and reactance decreases, while the measured resistance variation is
for the medium values of the fault resistance the measured not considerable and increases slightly. In the case of low
reactance is exposed to the lowest variation. In the upper part, fault resistance, the measured impedance is almost unchanged.
unlike the lower part, when the fault resistance is zero, the Comparing this case with the case of the STATCOM presence
measured impedance is not equal to the actual impedance of at the relaying point, it can be seen that the variation of the
the line section located between the fault and relaying points. measured impedance has an opposite pattern in these cases.
80 5
70
(Ohms)
60
Authorized licensed use limited to: Universidad de chile. Downloaded on July 07,2020 at 15:59:02 UTC from IEEE Xplore. Restrictions apply.
6
Authorized licensed use limited to: Universidad de chile. Downloaded on July 07,2020 at 15:59:02 UTC from IEEE Xplore. Restrictions apply.