Specification Sheet Contract Req. P.O. By Checked Approved Customer: Project: APDR Plant Area: Unit: 1 Tag No. PT-100C GENERAL 2 Service Presion salida nueva torre lavadora de g 3 Minimum Normal Maximum Design Unit PROCESS 4 Pressure 0 8 20 psig CONDITIONS 5 Process Temperature 80 120 C 6 Ambient Temperature 5 25 C 7 Manufacturer Rosemount, Inc. 8 Model No. 3051TG2A2B21AWR3D4M4DOC1Q4Q8V5HR7Z1 9 Pressure Transmitter Type Gage Pressure TRANSMITTER 10 Calibrated Span 0 to 20 psig 11 Adjustable Range 0 to 150 psi 12 Output Signal De 4 a 20 mA con señal digital basada en el protocolo HART 13 Body Rating 14 Process Flange Type NPT 1/2-14 15 Drain / Vent 16 Process Flange NPT 1/2-14 17 Adapters BODY 18 Wetted O-Ring 19 Housing Polyurethane-covered Aluminum 1/2-14 NPT 20 Bolts 21 Mounting Brackets 22 Conduit Entry Size Polyurethane-covered Aluminum 1/2-14 NPT 23 Isolating Diaphragm 316L SST 316L SST ELEMENT 24 Fill Fluid Silicona 25 Cert/Approval Type 26 Display LCD Display with Local Operator Interface OPTIONS 27 Zero and Span Adjust Analog Zero and Span 28 Transient Protection 29 Custom Configuration Configuración del software personalizada 30 Manufacturer 31 Model No. MANIFOLD 32 Manifold Style 33 Manifold Type 34 35 NOTES 36 37 38 This report is provided according to the terms and conditions of the Instrument Toolkit™ End-Use Customer License Agreement. Toolkit Version: 3.0 (Build217D) Printed: 8/4/2020