Professional Documents
Culture Documents
Romania
1
sensitivity approach. In section IV it is presented the test nature –combination of continuous and discrete dynamics – as
power network and two cases that were analyzed. Section V a set of differential algebraic (DA) equations [4]:
shows the results obtained using the proposed methodology.
Finally, in section VI, some conclusions that provide a x f x, y (1)
valuable contribution to the understanding of the dynamic
voltage stability assessment of a power system are pointed out. ° g x , y s x, y 0
0 ® (2)
II. APPLIED SOFTWARE °̄ g x , y s x, y ! 0
can also be evaluated using a Taylor series expansion of the IV. ELECTRIC POWER SYSTEM
system flows (7). The expansion for I x and I y can be In Fig. 1 it is shown the Electric Power Network that will
expressed as [15]: be used in this study. The simulations were carried out
considering the network data presented in [10], [16]. The
w I x x0 , t operating point assumed in this study corresponds to a
'x t 'x0 higher order terms (12)
w x0 1600 MW and 850 MVAr load level.
w I y x0 , t N2 N3 N5
'y t ' x0 higher order terms (13)
w x0 N1 ~~
~ G2
Neglecting the higher order terms and taken into account
(7): G1
L2
w x t
'x t | 'x0 (14) L1
w x0 N4
p.u.
Fig. 2. Voltage in busbar N4 trajectory sensitivities.
2.95
p.u.
2.70
0.90
2.65
0.85
2.60
0.80 s
0 50 100 150 200 250 300 350 400 450
FIELD CURRENT : G1 WITHOUT SC Unité : p.u.
0.75
FIELD CURRENT : G1 WITH 0,1 % SC Unité : p.u.
FIELD CURRENT : G1 WITH 2,5 % SC Unité : p.u.
0.70 FIELD CURRENT : G1 WITH 5 % SC Unité : p.u.
FIELD CURRENT : G1 WITH 10 % SC Unité : p.u.
0.65
Fig. 5. Field current of generator G1
0.60
B. Case II
0.55
0.50
3.1
3.0
2.9
2.8
2.7
Fig. 6. Voltage in busbar N4 trajectory sensitivities.
N4 for different values of load shedding. FIELD CURRENT : G1 WITH 30 % LOAD SHEDDING Unité : p.u.
FIELD CURRENT : G1 WITH 20 % LOAD SHEDDING Unité : p.u.
FIELD CURRENT : G1 WITH 10 % LOAD SHEDDING Unité : p.u.
FIELD CURRENT : G1 WITH 7,5 % LOAD SHEDDING. Unité : p.u.
p.u.
FIELD CURRENT : G1 WITH 2,5 % LOAD SHEDDING. Unité : p.u.
FIELD CURRENT : G1 WITHOUT LOAD SHEDDING. Unité : p.u.
0.90
VI. CONCLUSIONS
0.80
This paper presents a study of the dynamic voltage stability
of an electric power system using trajectory sensitivity
0.75 analysis. Trajectory sensitivities were effectively obtained as a
sub-product of simulating the nominal time-domain trajectory.
0.70
These sensitivities offer a way of ranking the relative
s
0 50 100 150 200 250 influence of system parameters.
VOLTAGE BUSBAR: N4 WITH 30% LOAD SHEDDING Unité : p.u.
VOLTAGE BUSBAR: N4 WITH 20% LOAD SHEDDING Unité : p.u.
VOLTAGE BUSBAR: N4 WITH 10% LOAD SHEDDING Unité : p.u.
In case I, the trajectory sensitivity analysis indicates that
VOLTAGE BUSBAR: N4 WITH 7,5% LOAD SHEDDING Unité : p.u.
VOLTAGE BUSBAR: N4 WITH 2,5% LOAD SHEDDING Unité : p.u.
there is a collapse situation for the series compensation of
VOLTAGE BUSBAR: N4 WITHOUT LOAD SHEDDING Unité : p.u.
0.1%. For the other values of the series compensation the
Fig. 7. Voltage variation in busbar N4. system remains stable. For the series compensation of 2.5%
Fig. 8 presents the field current of generator G1 trajectory and 5% the sensitivity values are higher than in the situation
sensitivities for different values of load shedding produced by of 10% of series compensation. This situation corresponds to
the post processing unit. the most stable scenario. The same conclusion can be drawn
from observation of figure 3 where it is shown that the
variation of the voltage on the busbar N4 for 10% of series
compensation is the most stable. In case II, trajectory
sensitivity analysis proves that when the load shedding is
2.5% and 7.5% the system voltage collapses. However, only
using a load shedding of 30% (lower value of sensitivity) it is
possible to restore the system stability closer to the initial
voltage level.
From the obtained results it was proved that the developed
technique is feasible and provides a deeper insight into the
influence of parameters on system performance. The solutions
obtained are in accordance with the results calculated using
the time domain simulation program. The accurate modeling
of the OXL is an important factor in the simulation of voltage
instability. The trajectory sensitivities of the system variables
to different parameters can be used successfully to avoid the
power system instability. Due to the output information
Fig. 8. Field current of generator G1 trajectory sensitivities. supplied by the proposed approach it is possible to implement
6