Professional Documents
Culture Documents
System
Abstract-This paper presents the optimal placement of capacitor be placed at candidate buses. It handles the constraints and the
banks in radial distribution system. For the purpose, capacitor objective function separately, and avoids the difficulty to
placement optimized based upon the cost, size and location. In determine the barrier factors. It doesn't require any external
the past research work it has been noticed that the power factor parameter. The proposed method has a guiding search direction
correction improve the stability and efficiency of electrical power which changes continuously as the objective function changes.
delivery. Also, in most of the research work the objective function
is the reduction of power losses and the improvement in voltage Murthy [2] presented a real and reactive combined power
profile. The reduction in power loss and the system voltage loss sensitivity (PLS) index-based approach to determine the
profile further depends upon the size and location of the optimal locations for capacitor placement in the radial
capacitor placement. In this paper the capacitor placement is distribution system (RDS). This approach provides better
optimized based upon the methods for cost, size and location of result as compared with the existing methods of index vector
capacitor bank to be installed in order to compensate for the (IV) and power loss index (PU). Load growth factor is
reactive power demand by the load. For the purpose of capacitor essential for planning and expansion of existing system which
placement in radial distribution system ETAP tool is to be used, is considered in this approach. PLS provides best results in
which will optimize the capacitor placement problem for
terms of power loss and overall cost benefit.
maximum cost saving and is computationally efficient. The
proposed method is to be demonstrated on a standard IEEE-IO Kannan [3] presented an enhanced approach for capacitor
bus radial distribution system. placement in radial distribution feeders to reduce the power
loss and to improve the voltage profile. The optimal capacitor
Keywords-Optimal capacitor placement, power loss, voltage placement method involves two steps, one is to identify the
profile, optimization techniques. optimal candidate bus location for capacitor placement and the
other is to determine the optimal size of the capacitor to be
I. INTRODUCTION
installed at the optimal candidate location. The optimal
Substantial research has been carried out on the solution of location for capacitor placement is decided by a set of rules,
optimal capacitor placement planning in the distribution after that the sizing of the capacitor banks is modelled as an
systems for the purpose of power factor correction, voltage optimization problem.
profile improvement and loss reduction. Especially, industrial
plant with variable load conditions has large inductive loads Tzong Su [4] proposed a relatively new metaheuristic
and its power factor is very poor. These industries benefit most approach for difficult combinational optimization problems.
from capacitor banks. These capacitor banks provide improved This approach is based on population that uses exploration of
power factor, improved voltage profile and minimize the positive feedback and greedy search. By simultaneously
electric utility bills. In most of the cases, the main reason for operating the population of agents, the process stagnation
installation of capacitor banks by consumer is to avoid penalty problem can be effectively prevented. This approach gives an
in the electricity bill. The installations of the capacitor in optimal solution like as the exhaustive search but with little
distribution system need to pay a very sincere effort to optimize computational burden.
the size and location using different methods. Therefore, in past Van Xu [5] proposed a method for deployment of shunt
the researcher has given the different methods to optimize the capacitor banks in a RDS to reduce the power loss and to
capacitor placement problem by which the customer and the provide additional benefits. The net present value (NPV)
power utilities both are get benefitted simultaneously. Reactive criterion is used to determine the cost saving of the capacitor
power compensation devices are discrete in nature in the real placement. Mixed-integer-programming (MIP) model is used
scale system, so optimal capacitor placement is a nonlinear to maximize the NPV of the optimal capacitor placement based
programming problem with integer (discrete) variables. on certain constraints. It uses commercial MIP package
Srinivas Rao [1] presented an approach for OCP in RDS, GUROBI to solve the optimization model. The proposed
which consists of two parts: in the first part loss sensitivity method has been implemented in Macau distribution system.
factors are calculated to determine the optimal candidate This method is computationally efficient and provides a
locations for capacitor placement and in the second part a new considerable positive NPV for optimal capacitor placement.
algorithm which employs Plant Growth Simulation Algorithm M.A.S. Masoum [6] proposed a fuzzy approach for optimal
(PGSA) is used to determine the optimal size of capacitors to capacitor placement in RDS in the presence of harmonic.
23kV 23kV
placement based upon the problem formulation can be Ul Bud 23kV
23kV 23kV 23kV 23kV 23kV Z3kV
"�mmm
obtained considering the size, location and cost of the
installation to benefit the most, subject to the operating
constraints. Therefore, in order to compensate the reactive
power demand of load there are four methods of capacitor
l�:\!VA ��� ���
2 3 LU».p4 L U».pS
installation [11] as follows: 1 IWA 1 IWA Z .
LUJ.p6
43 7IWA L718IWA O
L1J.llP1 LUJ.p8 LWlP9
.7881WA1.152 IWAO.989IWA l.6S2 IWA
point, which should be taken care of, is that the improvement Year Year Year Year Year
takes place only from point of application towards the source 1 2 3 4 5
of power and not in the opposite direction. Therefore, it is
always advantageous to place the capacitor bank near the load Fig. 3. Bar diagram analysis for OCP cost report
for the load power factor improvement that reduces the losses
in the circuit between the load and the supply feeder and thus Table-III shows that the capacitor placed at different
improves the voltage profile. location provides a significant loss reduction and 151 year cost
benefit and subsequently the accwnulative profit of
B. On the bases ojcost
Rs.6996449 over five year planning period. Though, the cost
The upper limit of power factor improvement depends upon of installation at each node is same but the reactive power
the installation cost & gestation period. Gestation period is demand at candidate node causes the gestation period varied
defined as the period after which the investor completely for different sizes of capacitor placements.
recovers his investment and obtains the first return. From
section II and part D it is observed that the optimal capacitor C. On the bases ojSize
placement depends upon the cost of installation and the In distribution system the loads at each node may vary and
demand charge, therefore, considering the candidate locations the corresponding reactive power demands. In case the
the size of capacitor can be calculated using "(8),". reactive power demand by the load at particular location is
very high then capacitor placement based upon the size will
One example is taken here considering the tariff of the
becomes the ultimate choice.
consumer is Rs.5/- per kVA and the cost of installation is
Rs.20/- at an annual rate of interest of 10%. TABLE IV. : POWER FACTOR OF SWING Bus (Bus I) ON OCP
B 2
.
SIn A.
'1-'1 = = "5 = 0.40
A Capacitor
MW MVAr MVA PF(Lagging)
size(kVAR)
<1>2=23.6°,
00 13.152 5.223 14.151 0.9294
COS<l>2= 0.9165 67 13.071 2.120 13.242 0.9871
Table-IV shows the power factor of swing bus on OCP in As a result of optimal capacitor placement in RDS the
radial distribution system. Here it is shown that for a particular voltage drop in the line impedance will reduce, voltage profile
size of capacitor bank unit we will get optimal power factor will improve (see Fig. 6) and the power factor will also get
with minimal losses and maximum cost saving. Here on improve.
placing capacitor banks of 67 kVAR size improves the power
Comparison of power loss and percentage voltage drop is
factor of swing bus to 0.9871 from 0.9294.
shown in the Table-VI. The minimum and maximum voltages
V. RESULTANDANALYSIS before capacitor installation are 0.8375 p.u (bus 10) and
0.9929 p.u (bus 2), and after capacitor installation are 0.8623
For the test feeder average energy cost is selected to be p.u (bus 10) and 0.9953 p.u respectively.
Rs.2.7/ (kW-hr), capacitor purchase cost Rs.213/ kVAR [11],
installation cost Rs.6000 at each node and capacitor bank
operation cost Rs.6000/ (Bank-year).
105
OCP results in the improvement of power factor of each and
individual node, as a result of this the overall power factor of 100
the swing bus get improved. The power factor before capacitor �
95 +-----""'�-
----- - Compensated
placement and after capacitor placement is shown in Table-V. �
v 90 voltage
OJ:
'"
TABLE V. % POWER FACTOR OF EACH INDIVIDUAL NODE .::::
0 85 +------------"....:-
. - Un
>
Buses
Before capacitor After capacitor 80 compensated
placement pf placement pf voltage
Busl 0.929 0.987 75
Bus2 0.933 0.998 1 2 3 4 5 6 7 8 9 10
Bus3 0.930 0.945 Bus No.
Bus4 0.936 0.985
Bus5 0.929 0.998
Bus6 0.981 0.997 Fig. 6. Voltage profile of lO bus system
Bus7 0.992 0.998
Bus8 0.993 0.999 TABLE VI. BRANCH LOSSES AND % VOLTAGE DROP
Bus9 0.991 0.997
BuslO 0.993 0.100 ID Before capacitor placement After capacitor placement
% Voltage % Voltage
Loss (kW) Loss (kW)
drop drop
ZI 46.7 0.71 40.9 0.47
SUMUi\RY OF TOTAL GENERATION . LOADING & DE.\HND Z2 4.0 0.55 3.4 0.23
Z3 177.2 2.40 151.7 1.74
lIW Mnr lIVA �HF
Z4 114.4 1.54 95.6 1.21
s� (S�ing Bu:-�): 1l.152 5.223 14.151 gl.94 Lagging Z5 190.2 3.08 175.9 2.75
Z6 47.8 1.00 44.9 0.93
Total o.m..d : 13.152 5.223 14.151 �.94 I.a;ging
Z7 75.7 1.82 71.2 1.71
- Z8 88.5 3.03 82.4 2.80
Total Motorl..o3d: 12.36& 4.1&6 13.05i 94. I.a;ging
Z9 39.3 2.12 36.5 1.93
Total St.a1icl..o3d: 0.000 0.000 0.000
Total 783.8 702.7
."'tLo!�: O.i&4 l.On
Fig. 4. Summary for total generation, loading and demand without Without Fuzzy
Proposed
capacitor placement compensation Reasonin2 [11
Active power
783.77 702.7 704.883
loss (kW)
% Active power - 10.34 10.065
SllM!.-Li\RY OF TOTAL GENERATION • LOADING & DE.\HND Ul-lu. l,oadj, loss reduction
Reactive power -
lIW lInr MVA �HF 1037 914
loss (kVAR)
S""", (S�i.ngBU!."): 13.0il 2.120 13242 9&.il I.a;ging % Reactive
power loss - 11.86 -
Total o.m..d : 13.0il 2.120 13242 9&.il I.a;ging
reduction
Total Motorl..o3:l : 12.36 8 4.1&6 1l.0;i 94. i2 I.a;ging Total kVAR - 3283 4950
placed
Total Static l..o3:l : 0.000 -2.9&0 2.9&0 0.00 I.a;ging
Annual Profit - 806266 269514
App3r'!IltLo",,;: 0.i03 0.914 (Rs.)
Accumulative - 6996449 5660971
Profit (Rs.)
Fig. 5. Summary for total generation, loading and demand with capacitor
placement
Thus, the overall OCP programme analysis of the system [3] S.M. Kannan, "Optimal capacitor placement and sizing using combined
fuzzy-HPSO method," International Journal of Engineering,Science and
implies that, the optimal capacitor placement result is obtained
Technology,vol. 2,no. 6,pp. 75-84,2010.
for the capacitor size of 67 kVAR, which places 49 capacitor
[4] Tzong Su, "Optimal capacitor placement in distribution systems
banks in lO bus RDS and thus improves the power factor to employing ant colony search algorithm," Taylor and Francis Journal of
0.9871 from 0.9294. There is a real power loss reduction to Electrical Power Components and Systems,vol. 33,pp. 931-946,2005.
702.7kW from 783.8 kW and Reactive power loss reduction to [5] Yan Xu" Zhao Yang Dong, Kit Po Wong, Evan Liu and Benjamin Yue,
914kVAR from 1037kVAR (see Fig. 4 and Fig. 5). The result "Optimal capacitor placement to distribution transformers for power loss
is compared with the existing fuzzy reasoning approach in the reduction in radial distribution systems," IEEE Transactions on Power
Table-VII. Systems,vol. 28,no. 4,pp. 4072-4079 November 2013.
[6] MAS. Masoum, "Fuzzy approach for optimal placement and sizing of
It also reduces the loss by an amount RS.1841546 per year, capacitor banks in the presence of harmonics ", IEEE Transactions in
provides an annual profit of Rs.806266.5 and an accumulative Power Delivery,vo1.19,no. 2, pp. 822-829,2004.
profit of Rs.6996449 for a planning period of 5 years. Thus [7] Diana P. Montoya,Juan M. Ramirez,"Reconfiguration and optimal
capacitor placement for losses reduction ", Transmission and
this method is observed to provide an enhanced cost saving Distribution: Latin America Conference and Exposition (T&D-LA),
over its planning period. sixth IEEE/PES,ppl-6,2012
[8] Sudha Rani, N. Subrahmanyamand M. Sydulu, "Self adaptive harmony
VI. CONCLUSIONS search algorithm for optimal capacitor placement on radial distribution
From the test results it can be observed that the improvement systems," International Conference onEnergy Efficient Technologies for
Sustainability (ICEETS), pp.1330-1335,2013.
in power factor up to unity is not always economical. Also, it
[9] Tzong Su , "A new fuzzy-reasoning approach to optimum capacitor
can be noticed that the power factor correction is the size, allocation for primary distribution systems," IEEE International
location and cost of installation dependent. The optimum Conference on Industrial Technology, pp. 237-241,1996.
value of the capacitor depending upon the any of the criterion [10] Atul, "Economics of power factor correction in radial distribution
chosen does not guarantee that relative parameter in the systems," International Journal of Applied Engineering Research
system configuration under consideration will improve (I JAER),vol.8,no.7,ISSN:0973-4562,pp. 52-56,2013.
simultaneously. [II] ABB Group,Technical papers on power factor correction,Issue 3,2008.