You are on page 1of 5

A Minimalistic Approach for Wide-Area

Out-of-Step Identification
G V N YatendraBabu, Nagasekhara Reddy Naguru, and Vaskar Sarkar
Department of Electrical Engineering
Indian Institute of Technology Hyderabad, India
Email: conmp03@iith.ac.in

Abstract—Rotor angle instability (out-of-step or transient in- relay and set of blinders [5] and [6], which can operate in
stability) in the power system is an immediate predicament to real-time without considering the system-wide information. In
the safe operation of the system. The out-of-step condition left [7]–[9], instantaneous angular velocity and acceleration are
untreated may escalate into a widespread outage. Identification of
the out-of-step condition is a necessary precursor to the power used to detect the loss of synchronism. Approaches based on
system operation tools such as controlled islanding to prevent instantaneous measurements may become inferior in detection
system-wide collapse. The controlled islanding needs system-wide when there are outliers in the measurements. Wavelet decom-
consideration for an effective mitigation plan. The conventional position of the speed deviations over three cycles is observed
out-of-step detection is often devised without considering the to determine out-of-step in [10]. In [11] and [12], center-of-
wide-area scenario. A wide-area out-of-step identification ap-
proach based on frequency measurements is evaluated in this inertia (COI) angles are predicted from measurements, which
paper. Most of the times, the out-of-step results disconnection of are used to identify transient instability in the system. Support
equipment or part of the system. Hence, the proposed approach vector classifier is used in [13] and [14] to determine the power
allocates priority to avoid false detection thus preventing un- system transient stability status. In [15], decision tree approach
necessary system separation or disconnection. The methodology is followed to detect loss of synchronism in the system.
proposed is thoroughly verified for accuracy and performance
using the 68-Bus system. Transient instability or out-of-step identification is a prelim-
Index Terms—Out-of-step detection, power system, rotor angle inary step to deploy any counter-measures to an impending
stability, transient stability, wide-area monitoring widespread outage. The counter-measures such as controlled
islanding splits the system into self-sufficient coherent groups
I. I NTRODUCTION [16]. Splitting a healthy system based on an incorrect iden-
tification of the instability is not desirable. In addition, the
Sufficiently large disturbance in the power system can out-of-step condition should be detected as early as possible
introduce excursion in system parameters. The separation of (not too early or not too late) so as to avoid escalation into a
rotor angles between individual or groups of generators is one system-wide outage. Further, the loss of synchronism may be
of the indications of such large disturbances. The separation of experienced at a single generator or between groups of gener-
rotor angles results in loss of synchronism between individual ators, which require consideration of a system-wide measure
or groups of generators. The phenomenon is also known as the to determine out-of-step condition. As the instability evolves
out-of-step condition or transient instability [1]. The transient quickly [1], the intended identification method should not be
instability can be characterized by power swings, rotor angle computationally expensive to be an online application. In this
variations, and fluctuations in voltage and current. paper, a threshold based out-of-step identification method is
Traditionally, the loss of synchronism can be visualized by proposed by considering the factors mentioned above.
time-domain simulation of the power system model [2]. Al-
The rest of the paper is organized as follows. The theoretical
though the time-domain simulation provides accurate results,
background to out-of-step identification is presented in Section
deploying in online application is not feasible because they are
II. In Section III, the proposed methodology is explained.
computationally heavy. Instead of analyzing the time-domain
Simulation studies are performed to provide validation of the
simulation trajectories, the equal-area criterion, which utilizes
proposed method in Section IV. Finally, the paper is concluded
the power-angle relation can be used to identify the existence
in Section V.
of the out-of-step condition in the system [1] and [3]. The basic
equal-area criterion applies to the two-area system. In [4], a
power-time curve is utilized in place of the power-angle curve II. BACKGROUND
to facilitate the equal-area criterion in a multi-machine system. The power delivered by the generator changes when there
The equal-area criterion depends on the instances of the fault is a disturbance or operating state change in the power
inception and clearing, which may not be available in real-time system. The sudden change in the demand causes a momentary
deterministically. Local measurements are used to determine accumulation or deprivation of energy at the generator, which
the out-of-step condition based on the impedance seen by a results in increment or decrement in the generator rotor angle
978-1-5386-6159-8/18/$31.00 © 2018 IEEE and velocity [1]. The loss of synchronism can be determined
60.2

60.15

Frequency (Hz)
60.1

60.05

60

59.95
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Time (sec)

Fig. 2. Oscillatory response of the generator frequency.

Alternatively, the speed- acceleration locus can also be used


to predict the out-of-step condition [9]. The speed and accel-
Fig. 1. Power-angle relationship. erations computed from rotor angles can represent the surplus
accelerating power, which may lead to out-of-step condition.
The generator’s out-of-step condition is predicted when the
by examining the swing curves given by the equation of speed-acceleration locus remains in first and second quarters
motion [1] as expressed below. of the speed-acceleration plane. In other words, the movement
dΔωi of speed-acceleration locus from the second quadrant to the
Mi = ΔPim − ΔPie − Di Δωi (1) first quadrant represents the possible unstable scenario. In
dt
dΔδi this work, the proposed method is compared with the speed-
= ωo Δωi (2) acceleration approach and direct angle comparison.
dt
Where Mi is the inertia constant, Di is the damping constant,
ωo is the synchronous speed, Δδi is the rotor angle, Δωi is III. M ETHODOLOGY
the speed, ΔPim is the mechanical input power, and ΔPie
Generator coherency in the power system is the phe-
is the electrical output power deviations of the ith generator.
nomenon of the generators responding together following a
The active power transfer between two nodes is expressed as
disturbance in the form of electromechanical oscillations. The
follows.
Es Er coherent generator groups are identified using a coherency
Pe = sin(δ) (3) measure or property [16]. For a large disturbance, the in-
X
dividual or groups of generators may separate from each
Where, Es is the sending end voltage, Er is the receiving end other, which is the case of rotor angle instability. In this
voltage, and X is the total reactance between the two nodes. methodology, an attempt is made to identify the out-of-step
On the other hand, the generator can be determined as condition by using the coherency measure.
unstable when the energy gained during accelerating is greater The rotor angle stability basically refers to the ability of
than the energy lost during deceleration. This criterion is generators to regain synchronism after the same is disturbed
known as the equal-area criterion [1]. Graphical illustration by some fault in the system. That is, all the generators
of the equal-area criterion is shown in Fig. 1. The area under should be able to closely converge to a common frequency
the curve between δ0 and δc is the acceleration period (A1), within finite time following a disturbance. Alternatively, the
whereas, the deceleration period (A2) is between δc and δm . angle difference between two generators must vary within a
The instability criterion can be expressed as follows. narrow range and should finally converge to a constant value.
 δc  δm Therefore, the stability status of the system can be monitored
(P m − P e )dδ > (P e − P m )dδ (4) by observing either the frequencies or the angles of generators.
δ0 δc
However, the use of only the latest frequency or angle snapshot
In Fig. 1, the area A1 in the case of fault cleared after rotor may deliver inconclusive result under the oscillatory responses
angle changed from δ0 to δc1 is equal to the corresponding as are illustrated in Fig. 2. The frequency snapshot at t = 1.1
A2, which shows that the machine is not going out-of-step. sec gives the impression as if the system is going to be
The area A1 in the case of rotor angle changed from δ0 to δc2 unstable. The generator frequencies again come very close to
is greater than the corresponding A2. In this case, the energy one another at t = 2.6 sec nullifying the previous impression.
gained during the acceleration is more than the energy lost, It is, therefore, necessary to observe the variations of generator
which increases the rotor angle further. Hence, the machine frequencies or angles for some time duration before drawing
can be determined as unstable. Often, in this analysis, the any inference about stability or coherency. Compared to gen-
system is considered as the generator connected to the infinite erator angles, generator frequencies are easier to observe. This
bus. is because the frequency measurements are readily available
from PMUs. This, in turn, eliminates all the intermediate data Based upon the above conditions, the upper critical value of
processing burdens. In this work, the frequency trajectory of a the FMI is determined through the following equation.
generator is continuously monitored over a fixed-length sliding
time-window. The frequency samples collected through the εucr = μup εpeak . (8)
particular time-window are packed into a frequency trajectory Here, εpeak indicates the maximum observed stable FMI (over
vector. The frequency trajectory vector of length m is a vector all generator pairs and over all the sampling instants). The
of the m frequency measurements including the present sample value of εpeak is obtained by studying several stable cases. In
as well as the past m − 1 samples. Thus, the frequency order to prevent false instability detection in unobserved stable
trajectory vector for Generator i (symbolized as Fi ) at the cases, the upward safety factor μup is introduced. The upward
nth time instant is defined as follows. safety factor is a positive number with a value no lower than
  one.
Fi = fi [n], fi [n − 1], ...., fi [n − m + 1] (5)
Real-time application of the proposed transient instability
where, fi [n − k] is the frequency sample collected from identification requires an efficient implementation so as to
Generator i at the (n − k)th time instant. ensure the timely response. As mentioned earlier, the proposed
method uses measurements from PMUs that can send data at
In order to identify the out-of-step status between two gen-
a high reporting rates (i.e., 30 to 120 samples per second for
erators, a frequency mismatch index (FMI) is used. The FMI,
a 60 Hz system). The data received needs to be processed
in essence, indicates the dissimilarity between two generators
before the next data sample arrives at the control center. The
from the point of view of coherency. Different FMIs are
computationally expensive tasks in the proposed methodology
proposed in literature [17] and [18]. Apart from FMIs, there
are the FMI evaluation. It is possible to marginally update an
are also angle-based dissimilarity indices to identify the loss of
FMI value when a new set of data samples arrives. Equation
coherency [19] and [20]. However, for the sake of simplicity,
(6) can be rewritten in the recursive form as is shown below.
the FMI proposed in [17] is used to explain the proposed
 2  2
approach. The other dissimilarity indices can be similarly εi,j [n] = fi [n] − fj [n] − fi [n − m] − fj [n − m]
employed.
+ εi,j [n − 1]. (9)
The FMI between ith and jth generators is determined by
the following equation. The direct use of Equation (6) involves m multiplications, m
subtractions and (m − 1) additions for the calculation of each
m−1
  2 FMI. On the other hand, only 2 multiplications, 3 subtrac-
εi,j [n] = fi [n − k] − fj [n − k] . (6)
tions and 2 additions are required per FMI in the recursive
k=0
calculation. This, in turn, results in significant reduction in
An upper critical value (symbolized as εucr ) is set for the FMI the computational effort for the calculation of FMI values.
to detect instability. The loss of synchronism is affirmed when Furthermore, εi,j = εj,i . Therefore, it is sufficient to calculate
any εi,j exceeds the above mentioned critical value. The speed εi,j s only for j > i. The number of individual FMI values
of instability detection depends upon the upper critical value to be calculated is 0.5ng (ng − 1), where ng is the number of
of the FMI. It is necessary to appropriately tune the length generators.
of the frequency trajectory vector as well as the upper critical
value of the FMI. The length of the frequency trajectory vector IV. C ASE S TUDY
is determined by the following relationship. The alertness of the instability detection scheme employed
is verified through offline simulation studies. In all the
m = Tsw Sf . (7) studies, the PMU data reporting rate is assumed to be 60
samples/second. The length of frequency trajectory vector
Here, Tsw indicates the length of the sliding time-window (in is chosen exactly according to the PMU data reporting rate
seconds) and Sf is the frequency sampling rate (which can be and with respect to the fault duration of four cycles. The
the same as or lower than the PMU data reporting rate [21]). nominal system frequency is taken as 60 Hz. The study is
As per the length of the observation window suggested in [22] carried out on a 68-bus test system. The test system considered
to identify stable and unstable cases, the value of Tsw is taken consists of 16-generators. Each generator is equipped with a
as five times of the maximum possible fault duration time. The power system stabilizer (PSS). The exciters are of the IEEE-
upper critical value (i.e., εucr ) of the FMI is experimentally DC1A type. The generators are represented by means of the
determined by simulating several disturbance events. sub-transient model and loads are represented by means of
The following considerations need to be made while setting the constant impedance model. The mechanical torque input
the upper critical value of the FMI. to each generator is assumed to be constant. The detailed
1) The value of εucr should be as little as possible so that information about lines, generators and loads can be found in
the occurrence of instability can be quickly detected. [23]. The PSS parameters for the test system are designed by
2) The value of εucr should be high enough not to falsely following the procedure presented in [24]. All the disturbances
detect a stable case as an unstable one. are introduced by creating a three-phase bolted fault at the
TABLE I
L IST OF STABLE CASES STUDIED FOR PARAMETER TUNING

Case id. Faulty line Case id. Faulty line Case id. Faulty line
1 27 - 53 18 34 - 33 35 52 - 55
2 23 - 22 19 34 - 35 36 54 - 53
3 24 - 23 20 36 - 34 37 55 - 54
4 24 - 68 21 36 - 61 38 56 - 55
5 25 - 54 22 37 - 68 39 57 - 56
6 26 - 25 23 38 - 31 40 58 - 57
7 27 - 37 24 38 - 33 41 59 - 58
8 27 - 26 25 43 - 17 42 60 - 57
9 28 - 26 26 44 - 39 43 60 - 59
10 29 - 26 27 44 - 43 44 63 - 58
11 29 - 28 28 45 - 35 45 63 - 62
12 30 - 53 29 45 - 39 46 63 - 64
13 30 - 61 30 45 - 44 47 65 - 62
14 31 - 30 31 46 - 38 48 65 - 64
15 31 - 53 32 47 - 53 49 66 - 56
16 32 - 30 33 49 - 46 50 66 - 65
17 33 - 32 34 52 - 37 51 67 - 66

Fig. 4. Rotor frequency and angle dynamics following the fault at Line 18-50.

Fig. 3. Rotor frequency and angle dynamics following the fault at Line 41-42.

middle of a line. The fault is cleared after four cycles by


tripping the respective line. The εpeak is identified by studying
the stable cases, which are generated by applying the above Fig. 5. Rotor frequency and angle dynamics following the fault at Line 25-54.
mentioned fault scenario to all the lines as listed in Table I.
The maximum observed stable FMI value is found to be 1.764
Hz2 . The FMI upper critical value is conservatively chosen as at Line 25-54, the system remains stable, which is the Case-3.
150%. The rotor frequency and angle dynamics of the Case-1, Case-2,
All the simulations are started from a steady-state that is and Case-3 are plotted in Fig. 3, Fig. 4, and Fig. 5, respectively.
obtained by carrying out load flow analysis with the given Apart from the relation in Equation (6), the relations proposed
generation and load profile in [23]. After saving the trajectories in [11] and [9] are also attempted to identify the out-of-step
of all the quantities, those are resampled (as per the PMU condition. A comparison of times taken by different methods
reporting rate) to identify the time instant at which a method to detect instability following the disturbance is produced in
can detect the transient instability. Two unstable cases and Table II.
one stable case are presented. The first unstable case (Case-1) It can be seen that the methodology proposed always pro-
results because of the fault at Line 41-42. The second unstable vides fastest response than [11]. Although the fastest response
case (Case-2) is caused by the fault at Line 18-50. For the fault is provided by [9], the particular methodology suffers from the
TABLE II [2] S. Zadkhast, J. Jatskevich, and E. Vaahedi, “A multi-decomposition
I NSTABILITY DETECTION TIME COMPARISON approach for accelerated time-domain simulation of transient stability
problems,” IEEE Trans. Power Syst., vol. 30, no. 5, pp. 2301–2311,
Instability detection time (sec) Sept. 2015.
Fault
Status Speed-acceleration Direct angle FMI-based [3] B. Alinezhad and H. K. Karegar, “Out-of-step protection based on equal
at Line
relation [9] comparison [11] criterion area criterion,” IEEE Trans. Power Syst., vol. 32, no. 2, pp. 968–977,
41-42 Unstable 0.9333 3.3833 3.1833 Mar. 2017.
18-50 Unstable 0.6167 2.1000 1.1167 [4] S. Paudyal and R. Gokaraju, “Out-of-step protection for multi-machine
25-54 Stable 0.6500 —– —– power systems using local measurements,” in Proc. IEEE Eindhoven
PowerTech, Jun. 2015, pp. 1–6.
[5] J. Megger and J. M. Gersusa, “Setting and testing of power swing block-
ing and out of step relays considering transient stability conditions,” in
Proc. IET 9th Int. Conf. Developments in Power Syst. Protection, Mar.
2008, pp. 150–155.
[6] D. A. Tziouvaras and D. Hou, “Out-of-step protection fundamentals and
advancements,” in Proc. 57th Annu. Conf. Protective Relay Engineers,
Apr. 2004, pp. 282–307.
[7] K. h. So, J. y. Heo, C. h. Kim, R. K. Aggarwal, and K. b. Song, “Out-
of-step detection algorithm using frequency deviation of voltage,” IET
Gener. Transm. Distrib., vol. 1, no. 1, pp. 119–126, Jan. 2007.
[8] M. R. Salimian and M. R. Aghamohammadi, “Intelligent out of step
predictor for inter area oscillations using speed-acceleration criterion as
a time matching for controlled islanding,” vol. 9, no. 4, pp. 2488–2497,
Jul. 2018.
[9] A. R. Sobbouhi and M. R. Aghamohammadi, “A new algorithm for
predicting out-of-step condition in large-scale power systems using rotor
speed-acceleration,” Int. Trans. Elec. Energy Syst., vol. 26, no. 3, pp.
486–508, 2016.
[10] E. A. Frimpong, P. Y. Okyere, and J. A. Asumadu, “Generator out-of-
step prediction using wavelet analysis,” in Proc. 4th IEEE Int. Symp.
Power Electron. Distrib. Gener. Syst., Jul. 2013, pp. 1–4.
[11] J. C. Cepeda, J. L. Rueda, D. G. Colome, and D. E. Echeverria, “Real-
time transient stability assessment based on centre-of-inertia estimation
Fig. 6. The speed-acceleration locus of Generator 11 between 1.5 seconds from phasor measurement unit records,” IET Gener. Transm. Distrib.,
and 3.5 seconds following the fault at Line 25-54. vol. 8, no. 8, pp. 1363–1376, Aug. 2014.
[12] F. G. Velez, V. A. Centeno, and A. G. Phadke, “Multiple swing
transient stability assessment with phasor measurements,” in Proc. IEEE
Manchester PowerTech, Jun. 2017, pp. 1–6.
problem of false instability detection. To demonstrate the false [13] L. S. Moulin, A. P. A. da Silva, M. A. El-Sharkawi, and R. J. Marks,
identification, the Case-3 is considered, which is a stable case “Support vector machines for transient stability analysis of large-scale
as shown in Fig. 5. The angle comparison and FMI-based power systems,” IEEE Trans. Power Syst., vol. 19, no. 2, pp. 818–825,
May 2004.
approach are not detected any out-of-step condition in the [14] M. Rashidi and E. Farjah, “LEs based framework for transient instability
Case-3. However, the speed-acceleration criterion identified prediction and mitigation using pmu data,” IET Gener. Transm. Distrib.,
an out-of-step condition in the Case-3, which is incorrect. vol. 10, no. 14, pp. 3431–3440, Oct. 2016.
[15] T. Amraee and S. Ranjbar, “Transient instability prediction using de-
For illustration, the speed-acceleration curve of Generator 11 cision tree technique,” IEEE Trans. Power Syst., vol. 28, no. 3, pp.
between 1.5 seconds and 3.5 seconds following the fault at 3028–3037, Aug. 2013.
Line 25-54 (Case-3) is plotted in Fig. 6, which satisfies the [16] G. Rogers, Power System Oscillations. Norwell, MA: Kluwer Academic
Publishers, 2000.
out-of-step condition. [17] H. A. Alsafih and R. Dunn, “Determination of coherent clusters in a
multi-machine power system based on wide-area signal measurements,”
V. C ONCLUSION in Proc. IEEE PES General Meeting, Jul. 2010, pp. 1–8.
[18] M. Jonsson, M. Begovic, and J. Daalder, “A new method suitable for
In this work, the coherency measure is extended for de- real-time generator coherency determination,” IEEE Trans. Power Syst.,
tection of rotor angle instability following a disturbance dur- vol. 19, no. 3, pp. 1473–1482, Aug. 2004.
ing the real system operation. The out-of-step condition is [19] J. Wei and K. Deepa, “A multi-flock approach to rapid dynamic genera-
tor coherency identification,” in Proc. IEEE PES General Meeting, Jul.
identified through a frequency mismatch index by observing 2013, pp. 1–5.
generator frequencies in real-time. The frequency mismatch [20] M. R. Aghamohammadi and S. M. Tabandeh, “Online coherency iden-
index is continuously evaluated over a moving time window. tification based on correlation characteristics of generator rotor angles,”
in Proc. IEEE Int. Conf. on Power and Energy (PECON), Dec. 2012,
The loss of synchronism between two generators (thus, the pp. 499–504.
inception of rotor angle instability) is indicated by the crossing [21] A. G. Phadke and J. S. Thorp, Synchronized Phasor Measurements and
of a threshold by the FMI. The respective critical FMI value their Applications. New york, NY: Springer, 2008.
[22] “IEEE recommended practice for industrial and commercial power
can be set experimentally by observing the FMI range over systems analysis (brown book),” IEEE Std 399-1997, pp. 1–488, Aug.
several stable cases. Case studies confirm the effectiveness of 1998.
the proposed method in terms of detection time and accuracy. [23] B. Pal and B. Chaudhuri, Robust Control in Power Systems. New york,
NY: Springer, 2005.
[24] R. A. Jabr, B. C. Pal, N. Martins, and J. C. R. Ferraz, “Robust and
R EFERENCES coordinated tuning of power system stabiliser gains using sequential
[1] P. Kundur, Power System Stability and Control. New York, NY: linear programming,” IET Gener. Transm. Distrib., vol. 4, no. 8, pp.
McGraw-Hill, Inc., 1994. 893–904, Aug. 2010.

You might also like