Professional Documents
Culture Documents
Out-of-Step Identification
G V N YatendraBabu, Nagasekhara Reddy Naguru, and Vaskar Sarkar
Department of Electrical Engineering
Indian Institute of Technology Hyderabad, India
Email: conmp03@iith.ac.in
Abstract—Rotor angle instability (out-of-step or transient in- relay and set of blinders [5] and [6], which can operate in
stability) in the power system is an immediate predicament to real-time without considering the system-wide information. In
the safe operation of the system. The out-of-step condition left [7]–[9], instantaneous angular velocity and acceleration are
untreated may escalate into a widespread outage. Identification of
the out-of-step condition is a necessary precursor to the power used to detect the loss of synchronism. Approaches based on
system operation tools such as controlled islanding to prevent instantaneous measurements may become inferior in detection
system-wide collapse. The controlled islanding needs system-wide when there are outliers in the measurements. Wavelet decom-
consideration for an effective mitigation plan. The conventional position of the speed deviations over three cycles is observed
out-of-step detection is often devised without considering the to determine out-of-step in [10]. In [11] and [12], center-of-
wide-area scenario. A wide-area out-of-step identification ap-
proach based on frequency measurements is evaluated in this inertia (COI) angles are predicted from measurements, which
paper. Most of the times, the out-of-step results disconnection of are used to identify transient instability in the system. Support
equipment or part of the system. Hence, the proposed approach vector classifier is used in [13] and [14] to determine the power
allocates priority to avoid false detection thus preventing un- system transient stability status. In [15], decision tree approach
necessary system separation or disconnection. The methodology is followed to detect loss of synchronism in the system.
proposed is thoroughly verified for accuracy and performance
using the 68-Bus system. Transient instability or out-of-step identification is a prelim-
Index Terms—Out-of-step detection, power system, rotor angle inary step to deploy any counter-measures to an impending
stability, transient stability, wide-area monitoring widespread outage. The counter-measures such as controlled
islanding splits the system into self-sufficient coherent groups
I. I NTRODUCTION [16]. Splitting a healthy system based on an incorrect iden-
tification of the instability is not desirable. In addition, the
Sufficiently large disturbance in the power system can out-of-step condition should be detected as early as possible
introduce excursion in system parameters. The separation of (not too early or not too late) so as to avoid escalation into a
rotor angles between individual or groups of generators is one system-wide outage. Further, the loss of synchronism may be
of the indications of such large disturbances. The separation of experienced at a single generator or between groups of gener-
rotor angles results in loss of synchronism between individual ators, which require consideration of a system-wide measure
or groups of generators. The phenomenon is also known as the to determine out-of-step condition. As the instability evolves
out-of-step condition or transient instability [1]. The transient quickly [1], the intended identification method should not be
instability can be characterized by power swings, rotor angle computationally expensive to be an online application. In this
variations, and fluctuations in voltage and current. paper, a threshold based out-of-step identification method is
Traditionally, the loss of synchronism can be visualized by proposed by considering the factors mentioned above.
time-domain simulation of the power system model [2]. Al-
The rest of the paper is organized as follows. The theoretical
though the time-domain simulation provides accurate results,
background to out-of-step identification is presented in Section
deploying in online application is not feasible because they are
II. In Section III, the proposed methodology is explained.
computationally heavy. Instead of analyzing the time-domain
Simulation studies are performed to provide validation of the
simulation trajectories, the equal-area criterion, which utilizes
proposed method in Section IV. Finally, the paper is concluded
the power-angle relation can be used to identify the existence
in Section V.
of the out-of-step condition in the system [1] and [3]. The basic
equal-area criterion applies to the two-area system. In [4], a
power-time curve is utilized in place of the power-angle curve II. BACKGROUND
to facilitate the equal-area criterion in a multi-machine system. The power delivered by the generator changes when there
The equal-area criterion depends on the instances of the fault is a disturbance or operating state change in the power
inception and clearing, which may not be available in real-time system. The sudden change in the demand causes a momentary
deterministically. Local measurements are used to determine accumulation or deprivation of energy at the generator, which
the out-of-step condition based on the impedance seen by a results in increment or decrement in the generator rotor angle
978-1-5386-6159-8/18/$31.00 © 2018 IEEE and velocity [1]. The loss of synchronism can be determined
60.2
60.15
Frequency (Hz)
60.1
60.05
60
59.95
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Time (sec)
Case id. Faulty line Case id. Faulty line Case id. Faulty line
1 27 - 53 18 34 - 33 35 52 - 55
2 23 - 22 19 34 - 35 36 54 - 53
3 24 - 23 20 36 - 34 37 55 - 54
4 24 - 68 21 36 - 61 38 56 - 55
5 25 - 54 22 37 - 68 39 57 - 56
6 26 - 25 23 38 - 31 40 58 - 57
7 27 - 37 24 38 - 33 41 59 - 58
8 27 - 26 25 43 - 17 42 60 - 57
9 28 - 26 26 44 - 39 43 60 - 59
10 29 - 26 27 44 - 43 44 63 - 58
11 29 - 28 28 45 - 35 45 63 - 62
12 30 - 53 29 45 - 39 46 63 - 64
13 30 - 61 30 45 - 44 47 65 - 62
14 31 - 30 31 46 - 38 48 65 - 64
15 31 - 53 32 47 - 53 49 66 - 56
16 32 - 30 33 49 - 46 50 66 - 65
17 33 - 32 34 52 - 37 51 67 - 66
Fig. 4. Rotor frequency and angle dynamics following the fault at Line 18-50.
Fig. 3. Rotor frequency and angle dynamics following the fault at Line 41-42.