Engine Selection | De-rate Calculator | Speed Interpolator

USA Purchased, Heat Exchanger Cooled, Export

Date 8/26/2019

Type Clarke Engine Enclosure: None

Pump Requirements Pump Max Power: 137 BHP


RPM(s): 2600, Interpolated

Derate Parameters Altitude: 200 meters


Ambient Temperature: 20° C
Right Angle Gear Loss: 0%
Derate Percent: 1.1%

Application Information Customer: VSP Ingenieros


Job Name: Planta Textil - Ate
Job Number: COT FF BCI 2019 - 1024
Run By: Paul Cercado Cuya
Results:
Ventilation Emission
Rated BHP Available Derate BHP Interpolation Data
Model RPM Fan Loss EPA Emission Tier Data
(kW) BHP (kW) (kW) (RPM, kW)
BHP (kW) Available

JU6H- (2350, 110.4) to NSPS Tier 1-


2600 148 (110.4*) - - 146.4 (109.2*) Yes
UFD2 (2600, 110.4) Compliant

Note: Derated BHP takes into account all the input derates for altitude, temperature and right angle gearbox. When no derates are input, this column
will be blank and engine selection(s) will be based upon rated BHP. When the Derated BHP column is filled in, then the engine selection(s) are based upon
this value. These derates are based on NFPA 20 standard.

Definitions: UL/FM - Engine that is Underwriters Laboratories Listed and Factory Mutual Approved.
LPCB - Engine that is Loss Prevention Council Board Approved
NL - Non-Listed Engine has no private agency certification, like UL, or insurance company certification, like FM. It applies to any engine that is not UL
Listed or FM Approved, ad is built to meet individual European country specifications.