Kve-Uv: Capture Jet Hood With UV Technology
Kve-Uv: Capture Jet Hood With UV Technology
Date:05-2018 - Rev2
KVE-UV
Capture JetTM Hood with UV Technology
Air quality is becoming a major concern for everyone. • Integrated Capture Ray™ Ultraviolet cassette(s)
Many kitchens will require emissions control in their with complete controls and safety features.
exhaust systems to comply with growing demands for • Highly efficient Capture JetTM technology reduces
environmentally-friendly operation. the exhaust airflow volume required.
KVE-UV
1
Capture JetTM Hood with UV Technology
Form#: SS013_KVE-UV
Date:05-2018 - Rev2
1
4 2
Construction
The exposed part of the hood is made of stainless has been studied in detail using computational
steel. The joints of the inner liner have a fully-welded fluid dynamics (CFD) to ensure optimum results.
construction. The hood ends have double side
The Capture Ray™ control panel is designed to operate
wall construction. The Capture Jet TM is introduced
the UV lamps only under safe conditions and to give
through a special discharge panel (1). Grease and
a warning in the case of lamp failure, fan failure,
dirt extracted by the KSA multi-cyclone filter (2)
other operational failure or expiration of lamp lifetime.
can be removed from the hood by emptying the
Lifetime of one UV lamp is up to 10,000h, if system
collection tray (3). The air flow through the Capture
is maintained as per Halton’s Operation & Maintenance
Jet air chamber is determined by the T.A.B. ports
manual. The exposed parts are manufactured from
located inside the upper hood chamber(4). The
18 ga.
Capture Ray™ system is installed in a plenum, which
DIMENSIONS
KVE-UV inches
Length 48....168
Width 42....84
Height 24....30
QUICK DATA
*Hoods are ETL or UL listed for USA per UL710, and CANADA per ULC-S646 standards, and NSF certified.
KVE-UV
2
Capture JetTM Hood with UV Technology
Form#: SS013_KVE-UV
Date:05-2018 - Rev2
5
4
1
Capture &
3 Heat spilling containment
2
Side-Jets
Front capture air jets (2)
Function
The kitchen hood above cooking appliances collects the The grease vapor and effluents that are not collected by
warm air and contaminants (1). high-efficiency filters pass over the lamps. This causes a
chemical reaction that destroys the grease and converts
The Capture Jets (2) direct the contaminated air toward it into carbon dioxide and water vapor. The chemical
the KSA grease filters (3), where grease particles and action carries over into the duct (5) and helps keep the
other impurities are separated from the exhaust air duct and exhaust fan clean.
using the cyclone separation principle. Behind these
and inside the hood are a series of ultraviolet lamps (4).
• Closure Panels - for canopies below ceiling level • Face or Remote Mounted Switch Panels
• Backsplash • Factory Prepiped Fire Protection
• Side Skirts • Powder Coating in a Variety of Colors
• KFR - Filter Removal Tool • Custom/Design Stainless Steel Exterior Textures and
• LED Dimmable Lighting Finishes
• Recessed Fluorescent or Incandescent Lighting • Listed Exhaust Duct Balancing Damper
• Incandescent Globe Type Lights • Hood Mounted Fire Cabinet
• MEP - Master Electrical Panels • M.A.R.V.E.L. Demand Control w/VFD by Halton
Wiring diagram
KVE-UV
3
Capture JetTM Hood with UV Technology
Form#: SS013_KVE-UV
Date:05-2018 - Rev2
DIMENSIONS
W
KVE-UV - Wall model inches
Length 48....168
Width 42....84
Height 24....30
H
WEIGHTS (LB)
18 ga.
L
Estimated Crated inches Weight
Shipping Weight
Width 48” 85 lbs / ft.
Width 54” 90 lbs / ft.
Width 60” 95 lbs / ft.
Width 66” 100 lbs / ft.
Width 72” 105 lbs / ft.
2”
KVE-UV
4
Capture JetTM Hood with UV Technology
Form#: SS013_KVE-UV
Date:05-2018 - Rev2
8”
H
8”
E
B
A
D
C
r
to
ra
pa
se
r
lte
F
e
cl
Fi
rti
A
pa
KS
se
ea
G
Gr
Item Description
KVE-UV
5
Capture JetTM Hood with UV Technology
Balancing of Capture JetTM with UV Technology Hoods
Form#: SS013_KVE-UV
Date:05-2018 - Rev2
The capture jet and exhaust air flows are easily and
accurately determined by measuring the pressure
difference from the T.A.B. ports mounted in each plenum.
Corresponding air flows can be read from the diagrams
provided.
1.75 1.60
1.65 1.50
1.55
1.40
1.45
1.35 1.30
1.25 1.20
1.15 1.10
1.05
1.00
0.95
0.85 0.90
0.75 0.80
0.65 0.70
0.55
0.60
0.45
0.35 0.50
0.25 0.40
500 600 700 800 900 1000 1100 1200 700 800 900 1000 1100 1200 1300 1400 1500
1.50 1.20
1.40 1.10
1.30
1.00
1.20
1.10 0.90
1.00
0.80
0.90
0.70
0.80
0.70 0.60
0.60
0.50
0.50
0.40 0.40
0.30 0.30
800 900 1000 1100 1200 1300 1400 1500 1600 1700 900 1000 1100 1200 1300 1400 1500 1600 1700 1800
KVE-UV
6
Capture JetTM Hood with UV Technology
KVE-UV - 4 Filters, 2 Collars KVE-UV- 4.5 Filters, 2 Collars
Form#: SS013_KVE-UV
Date:05-2018 - Rev2
1.30 1.30
1.20 1.20
1.10 1.10
1.00 1.00
0.90 0.90
0.80 0.80
0.70 0.70
0.60 0.60
0.50 0.50
0.40 0.40
0.30 0.30
1100 1300 1500 1700 1900 2100 1200 1400 1600 1800 2000 2200 2400
1.20 1.20
1.10 1.10
1.00 1.00
0.90 0.90
0.80 0.80
0.70 0.70
0.60 0.60
0.50 0.50
0.40 0.40
0.30 0.30
1300 1500 1700 1900 2100 2300 2500 1400 1600 1800 2000 2200 2400 2600 2800
1.30 1.20
1.20
1.10
1.10
1.00
1.00
0.90
0.90
0.80
0.80
0.70
0.70
0.60
0.60
0.50 0.50
0.40 0.40
0.30 0.30
1600 1800 2000 2200 2400 2600 2800 3000 3200 1500 1800 2100 2400 2700 3000 3300
KVE-UV
7
Capture JetTM Hood with UV Technology
KVE-UV - 7 Filters, 2 Collars KVE-UV- 7.5 Filters, 2 Collars
Form#: SS013_KVE-UV
Date:05-2018 - Rev2
1.30 1.20
1.20 1.10
1.10 1.00
1.00 0.90
0.90
0.80
0.80
0.70
0.70
0.60
0.60
0.50
0.50
0.40
0.40
0.30 0.30
1800 2100 2400 2700 3000 3300 3600 1800 2100 2400 2700 3000 3300 3600 3900
1.30
1.20
1.10
1.00
0.90
0.80
0.70
0.60
0.50
0.40
0.30
2100 2400 2700 3000 3300 3600 3900 4200
Suggested specifications
General Exhaust
Kitchen hoods are constructed from 18 gauge stainless The exhaust airflow will be based on the convective
steel. The kitchen hoods shall be supplied complete with heat generated by the appliances underneath each
outer casing/main body, inner liner, exhaust duct, pressure hood system. Submittals shall include convective heat
measurement T.A.B. ports, fluorescent light fixtures, calculations based on the input power of the appliance
Capture Jet air supply nozzles, secondary filter, KSA served
grease filters, perimeter drain channel and collection cup.
Outer casing panels shall be constructed of stainless steel
with a brushed satin finish. Each joint shall be welded and
liquid tight, avoiding harmful dripping of condensation.
KVE-UV
8
Capture JetTM Hood with UV Technology
Capture JetTM System Access Panels
Form#: SS013_KVE-UV
Date: 05-2018 - Rev2
The hood shall be designed with Capture JetTM Each hood is provided with an access panel for
technology to reduce the exhaust airflow rate required, easy access of the UV cassettes. The ballast access
and to improve the capture and containment efficiency panel is located within the hood to provide access to
of the hood, while reducing energy consumption. components within the ballast box.
The Capture JetTM air shall be introduced through a
special discharge panel and shall not exceed 10% Capture Ray™
of the calculated exhaust airflow. The Capture JetTM The system includes one stainless steel plenum to
discharge velocity will be a minimum of 1500 feet per house the ultra violet cassettes. The hood is complete
minute. Slot or grille type discharge shall not be used. with a control panel indicating the total hours of
The Capture JetTM shall be internally mounted with operation, safety alarms, security on, and exhaust fan
a speed control and will not require a fire damper or failure.
electronic shut down in fire mode.
There are two sizes of UV cassettes:
T.A.B.™ Ports -one short, which is (234W) 38” long
The airflows through the extractors and the Capture -one long, which is (390W) 66” long
JetTM air chamber are to be determined through the
integral T.A.B.™ (Testing and Balancing) ports mounted The UV control panel is suitable for a single phase
in the hood. The airflows are to be determined by the power supply and is constructed to meet the UL listed
pressure vs. airflow curves supplied by Halton. protection standard.
Grease Filters The cassette access plate includes a hinged door for
The hood shall be equipped with KSA multi-cyclone ease of maintenance and replacement of the UV bulbs.
stainless steel grease extractors. The KSA filters The cassettes are mounted on a rack and are easily
shall be NSF and UL classified. The grease extraction removed by disconnecting the electrical connectors
efficiency is 93% on particles with a diameter of 5 on the cassettes end. The door comes equipped with
microns and 98% on particles with a diameter of 15 safety switches. If the door is not secured in the closed
microns or larger as tested by an independent testing position, the system will not operate.
laboratory. The pressure loss over the extractor shall
not exceed 0.50” of water at flow rates approved by The control panel is connected to the electrical box
U.L. for heavy load cooking. Sound levels shall not of the fan via a relay which detects any electrical fan
exceed an NC rating of 55. Baffle or slot type extractors failures. The system will not operate, if the fan does
shall not be used. not work. The fan is not supplied by Halton.