Professional Documents
Culture Documents
How To Control Reactive Power in Larger Electrical Plants With Multiple Incomers
How To Control Reactive Power in Larger Electrical Plants With Multiple Incomers
The first solution is, according to Figure 1, to measure the load via three
current transformers of 1500 A/5 A with each incoming supply fed by one
power transformer of 1000 kVA. The three current paths are summed in a
summation current transformer with three input paths, of 5 A each, and one
output path of 5 A too.
This output is wired to the current path of the power factor relay controlling a
12-step central compensation bank of 600 kvar.
Suppose coupling circuit breaker 1 is opened – then the power factor relay is
not able to compensate the reactive power of consumers connected to the
busbar to the left. However, the relay notes a higher request for capacitors to
be switched in.
The first term symbolizes the total ratio of the three current transformers, and
the second, symbolizing the summation transformer to be multiplied, results
in a very high total ratio of k = 900. It is then necessary to check whether the
relay’s minimum sensibility of 1% will not be undersized.
There would be only the possibility of varying the factor of 0.65 up to 0.85 or,
in another calculation, to show at which percentage of the step size (50 kvar)
a power factor relay with fully automatic C/k adaption would start to control:
Regarding factor k, it does not matter whether all power transformers are in
operation or not. Factor k is just a characterizing constant of the entire
electrical plant.
Regarding the switching time delay per step, there is no need to preset the
same value, just an approximate one, for example in the range between 35
and 40 s per step.
The C/k calculation from Equation 1 again is simple as no summation current
transformer must be considered.
This would mean the preset C/k value depends on the position of the
coupling circuit breakers and is to be corrected all of the time. This is indeed
a major disadvantage if using power factor relays with manual or half-
automatic C/k adjustment.
Thus, the best solution would be to use power factor relays with the feature
of ‘full automatic C/k adaption’.
They always register the so-called compensation effect for each step
independently of the position of the coupling circuit breakers 1 and 2. Even if
breaker 2 is open and 1 is closed, the current transformer of compensation
bank C registers the full size of the capacitor, but the current transformers of
compensation banks A and B only half the size.
During the installation of large electrical plants with currents of more than
1000 A approximately occurring attention should strictly be paid that, for
example, cables from the power transformers to the busbars are of the
same length in order to ensure symmetrical load distribution.