Professional Documents
Culture Documents
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Short circuit study
Requirements:
Ib
Ib1 Ic2
Unbalanced Positive Negative Zero sequence
current phasor sequence current sequence current current phasor
phasors phasors
Va 1 1 1 Va1
Vb = a2 a 1 Va2
Vc a a2 1 Va0
ps Phaseto sequence
1
Va 0 Va Vb Vc
3
3I0
I0
b b
Ib Ib
I0
c c
Ic Ic
Let Zaa = Zbb = Zcc = Zs and Zab = Zac = Zba = Zbc = Zca
= Zcb = ZmTsp Vs = [Z] . Tsp.Is
+
Ea
In Zn
Ec Eb
+ +
Ib
b
Ic
c
Va2
Z2
Z2
Z2 Ib2 a
b
Ic2 V a2 = - Ia2 Z2
c
3Ia0 Zn Zg0
Va0
Z0
3Zn
Zg0
Zg0 Ib0 a
b
Ic0 V a3 = - Ia0 Z0
c
Transformers :
All are equal i.e. Zpt = Znt = Zzt for transformer.
Zzt 90% of Zpt, if magnetising branch is neglected.
Vf
Va1 Va2 Va1
Z1 Z2 Z0
Vab = 0 Va = 0 Va1 = 0
Vbc = 0 Vb = 0 Va2 = 0
Vca = 0 Vc = 0 Va0 = 0
Ia = Ia1
Ia 1 1 1 Ia1
Ib = a2Ia1 I a2 a 1 I
b a2
Ic = aIa1 Ic a a21 Ia0
Ia = Ib = Ic
Zf Zf Zf Zf Zf Zf
Z0
Vf
Ia1 , Ia2 0 , Ia0 0
Z1 Z f
c I =0
b
I I I =0
b a c
I
c
V a 1 V f Z 1 I a 1 Va 2 Z 2 I a 2 Va0 Z 0 I a0
V a1 V a 2 V a 0 V f Z 1 I a1 Z 2 I a 2 Z 0 I a 0
QV a V a 1 V a 2 V a 0 0
Vf 3V f
I a1 I a 2 I a 0 Ia Z1 Z 2 Z 0
Z1 Z 2 Z 0
30
Copyright @ Power Research & Development Consultants Pvt. Ltd
Fault Through Impedance :
a
b
I
b
c
I
c
Z
f I
a
Vf
Ia1 Ia2 Ia0
Z1 Z 2 Z0 3z f
Vf
I a1 and I a 2 I a1 , I a 0 0 , Va 0 0
Z 1 Z 2
33
Copyright @ Power Research & Development Consultants Pvt. Ltd
Fault Through Impedance :
a
Ia
b
c
Ib Ic
Zf
Vf
Ia1 Ia 2
Z 1 Z2 Z f
Va1 = Vf - Z1Ia1
Va1 Vf Z1 0 0 I a1
Va2 = - Z2Ia2 V 0 0 Z2 0 I a 2
a2
Va0 = - Z0Ia0 Va 0 0 0 0 Z0 I a 0
Va1 = Va2 = Va0
Vf - Z1Ia1 = - Z2Ia2 - Z0Ia0
36
Copyright @ Power Research & Development Consultants Pvt. Ltd
V f
V a1 V a2 V a0
Z 1 Z 2
Z 0
I a1 I a2 I ao
Ib = 0 and Ic = 0 c c’
Via
Vka Z aa
'
'
I a Z aa I f
I a1 1 a a2 Ia
I 1 1 a2 a
0
a2 3
I a 0 1 1 1 0
1 1
Ia1 Ia 2 Ia 0 Ia I f
3 3
38
Copyright @ Power Research & Development Consultants Pvt. Ltd
Va1 Vf Z1I a1 Va1 Vf Z1 0 0 I a1
Va 2 Z2 I a 2 V 0 0 Z2 0 I a 2
a2
Va 0 Z0I a 0 Va 0 0 0 0 Z0 I a 0
Vkl
I a1 I a 2 I ao
Z1 Z2 Z0 3Zaa
'
39
Copyright @ Power Research & Development Consultants Pvt. Ltd
Vkl is the Thevenin equivalent voltage, once the line is
removed, between buses k & l.
Solution Methodology:
40
Copyright @ Power Research & Development Consultants Pvt. Ltd
Open in phase A :
• Ia = 0
• Similar type of analysis like double line fault.
• Voltage is between two nodes, rather than between
node and ground.
• Impedance is the Thevenin‟s equivalent impedance
between nodes.
Z Z Z1 Z1 Z1 Z1
l 1
1 kk ll lk kl f
Vk Vl
I lf Z
l
Z2 Z2 Z2 Z2 Z2
Z '2 . Z '0 2 kk ll lk kl f
Z1'
Z '2 Z '0 Z
l
Z0 Z0 Z0 Z0 Z0
0 kk ll lk kl f
' 1 '
Z I .Z
I
2
I1 . 0
I
0 f 2
f f
Z
' Z
' f
Z
'
Z'
0 2 0 2 41
Copyright @ Power Research & Development Consultants Pvt. Ltd
Solution Methodology:
1. Form the Y bus for +ve, -ve and zero sequence.
2. Do the LU factorisation for +ve, -ve and zero sequence.
3. To find the driving point impedance-
Consider, Yx = z
x=Y-1z
x= Z.z
Let z have 1 in pth location and 0, at all other location.
42
Copyright @ Power Research & Development Consultants Pvt. Ltd
Z11 Z12 L Z1p Z1n 0 Z1p
Zp1 Zp2 L Zpp Zpn 1 Zpp
x
M M M
Zn1 Zn2 L Znp Znn 0 Znp
Yx z
43
Copyright @ Power Research & Development Consultants Pvt. Ltd
[Vf ] = [Z] [If1]
= [Z] {[I0] - [If ]}
= [Z] [I0] + [Z][-If ]
= [V0] + [V]
V = [Z] [-If ]
Y[V] = [-If ]
Solve V using LU solution.
Above can be written as :
[Y]p[V]p = [-If]p , p: positive sequence and
similarly for other sequences.
44
Copyright @ Power Research & Development Consultants Pvt. Ltd
For faults other than open fault,
0
0
:
I f p I f
:
0
p
0
0
M
If p k I f
M
I f
M
0 45
Copyright @ Power Research & Development Consultants Pvt. Ltd
Example:
46
Copyright @ Power Research & Development Consultants Pvt. Ltd
Grounding Practice in
Power System :
Advantages of ungrounded system :
• Ground connection normally doesn‟t
carry current. Hence elimination saves the
cost.
• Current can be carried in other phases,
with fewer interruptions.
48
Copyright @ Power Research & Development Consultants Pvt. Ltd
Ungrounded System :
a
0.0
X = 16 % X = 8%
g
g
3 3 100 300
I
Z Z Z j24 j24 3 R j8
f
3 R j56
1 2 0
2
300
Power Loss
2
If R * R
3 R j56
51
Copyright @ Power Research & Development Consultants Pvt. Ltd
R
X = 16 % X = 8%
g
g
3 3 100 300
I
Z Z Z j24 j24 3 R j8
f
3 R j56
1 2 0
2
300
Power Loss
2
If R * R
3 R j56
52
Copyright @ Power Research & Development Consultants Pvt. Ltd
If : in pu, R : in pu
For three phase system, power loss
I f2 R
=
3 percentage of 3 phasesystemkVA rating
R is in percent p.u.
Maximum power loss = ?
Selection :
How much be the value of ground fault current ?
What should be the percent power loss in the ground
resistance ?
53
Copyright @ Power Research & Development Consultants Pvt. Ltd
Effectively grounded system:
Solidly grounded : No impedance between neutral and earth
X 0 system Ro
3.0 1.0
X 1 system X 1 system
69 kV 69 kV
25 MVA
X1 =34%
X2 =120%
A
X1 = X1 =7%
X2 =25% =X2=X0 B
54
Copyright @ Power Research & Development Consultants Pvt. Ltd
Effectively grounded system:
X0 7
For fault at A =
X 1 32
X 0 127 127
For faultat B = =
X 32+34 66
1
Reactance Grounded System
:
X0
. ; but no resonance (resonance grounding)
30
X
1
If Xg = 50 at A , find the nature of grounding at A & B.
55
Copyright @ Power Research & Development Consultants Pvt. Ltd
Resonant - Grounded System :
Capacitance current is tuned or neutralised by a neutral
reactor or similar device.
I
0 0
I2 0
I I
59
Copyright @ Power Research & Development Consultants Pvt. Ltd
Thank You
60
Copyright @ Power Research & Development Consultants Pvt. Ltd
TRANSIENT STABILITY STUDIES
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Stability
Non-oscillatory Oscillatory
Sufficient synchronizing torque Unstable control
action
f, v, loading not
syste
In Extremis Emergency
acceptable,
m load not met
DS DS DS G G G
Pm
f/N
Excitation system If
and control
Generator
f/N or
Pg Vt
Pg
Transmission Controls
Reactive power, Voltage control,
HVDC transmission and others
f Ptie Pg.total
Stability classification
• Transient stability : Transmission line faults, sudden
load change, loss of generation, line switching etc.
m2
m1 m1
0 m2 0
t Sec. t Sec.
Stable Unstable
0 0
t Sec.
t sec.
Stable Unstable
Stable
Unstable
Stable Unstable
m sm
Reference Axis sm
Reference axis at
Stationary
m sm t m
Copyright @ Power Research & Development Consultants Pvt. Ltd
71
d m d
sm m
dt dt
d 2 m d 2 m
2
dt dt 2
d 2 m
J 2
Tm Te N m
dt
d
m m Angularvelocityinradians persec.
dt
d 2 m
J m 2
Pm Pe watts
dt
d 2 m
M 2
Pm Pe ( Approx)
dt
Where M : Inertia constant = at synchronous
speed in Joules-sec per mechanical radian.
1 1
J sm
2
M sm
H 2 2 MJ / MVA
S S
2H S
M MJ per mechanical radian
sm
d m
2
M 2
Pm Pe watts
dt
2 HS d 2 m
Pm Pe
sm dt 2
2H d m 2
Pm Pe pu
sm dt 2
2 H d 2
Pm Pe
s dt 2
H d 2
2
Pm Pe pu
180 f d t
2 H d d
Pm Pe s
s dt dt
Let Pm Pe 1pu
2 H d
1pu, s t
s dt 2H
If t 2 H , s
Pm
At t = 0, breaker is opened.
Initially Pe = 1 pu on machine rating Pm = 1pu and
kept unchanged.
Machine rating
H system H mech
System MVA
KE f tlb
2 32.2 60
550 f tlb/ sec746Watts
1 WR 2N 746 2 2
6
10
2 32.2
60 550
H
S machine
Copyright @ Power Research & Development Consultants Pvt. Ltd
78
Example :
Smach = 1333 MVA
WR2 = 5820000 lb - ft2
N = 1800 RPM
550 10
2 32.2 60
H
1333
= 3.2677575 pu (MJ/ MVA)
On 100 MVA base : H = 1333 / 100 = 43.56 (MJ /
MVA)
G1 ,H1
Pm2 Pe2
G2 ,H2
H1 d 1 2
H 2 d 2
2
2 Pm1Pe1 2 Pm 2 P e 2
f dt f dt
H1H 2 d 2
f dt 2 Pm1Pm 2 Pe1Pe 2
Copyright @ Power Research & Development Consultants Pvt. Ltd
80
1 = 2 = ; since the machines swing together
Hd 2
Pm Pe
f d t 2
H = H1 + H2
Pm = Pm1 + Pm2
Pe = Pe1 + Pe2
G1 and G2 are called coherent machines.
Inertia Constant
2
J om 106 MWs
1 2
2
J:Moment of inertia in kgm 2
2
om: Rated speed in mechanical radian / sec RPM
60
1
J om 10 6
2
J RPM
2
H 2 9
5.48 10
MVA rating MVA rating
Copyright @ Power Research & Development Consultants Pvt. Ltd
82
British Units
Given
WR 2
J 1.356 27547.77168 kg mt 2
32.2
2
J ( RPM )
H 5.48 106 MWs / MVA
MVA rating
Stored energy
H MVA rating MWs
Mechanical starting time
2 H sec
f dt 2 H1 H 2
H1 H 2 1 d 2 1 2 H2 H1
P P Pm 2 Pe 2
H1 H 2 f H1 H 2 H1 H 2
m1 e1
dt 2
H1 H 2 1 d 2 1 2 H 2 Pm1H1 Pm 2 H 2 Pe1H1 Pe 2
H1H 2 f dt 2 H1 H 2 H1 H 2
H d 212
Pm12 Pe12
f d t 2
Where ,
H 1 2 Pm12 2 m1 1 m 2
H H H P H P
H1 H 2 H1 H 2
H 2 Pe1H1 Pe 2
Pe12
H1 H 2
Relative swing (with reference to one machine) is more important,
rather than absolute swing.
T in sec. T in sec.
jxd’
+
Ref.
E’ Vt
jxd’ I
-
Vt
E’ = Vt + (0 + jxd’) I
jXs
E1E 2
P sin
Xs
E1 : Magnitude of voltage at bus1
E2 : Magnitude of voltage at bus2
: 1 - 2
Xs : Reactance
Pe=Pmax sin
Pm
u 1800
O s 900
Stable
• At s ; Pm = Pe ; net accelerating torque = 0.
• Let Pe decrease slightly.
• H d 2
Pm Pe is ve
f dt 2
increase (acceleration)
comes back to original position.
• Stable region . Hence s is stable operating point.
increases, (acceleration)
· Pe further decreases.
· Chain reaction never comes back to
normal value .
Hence u is unstable operating point.
System
P
o
w
e Po
r
frequency
fo
Copyright @ Power Research & Development Consultants Pvt. Ltd
97
Let the load be 10,000 MW. i.e. P0 = 10,000
Let for 1 Hz change in frequency, let the load change be 700
MW.
Po f C f 700( decrease in load )
p
700
Po ( f f o ) C f 700 power number
p
1
700
Cf 7%
p
10,000
If Pisin pu; f isthe perunitchangein f requency
thenon100MVAbase :
7
C f 100 3.5
p
1
50
What it implies :
· Initial load 10,000 MW.
· Loss of generation 700 MW
· Increase in load 700 MW
· Frequency 49 Hz.
Copyright @ Power Research & Development Consultants Pvt. Ltd
98
Load Model Parameters
Load model paraters
Residential
Summer 0.9 1.2 2.9 0.8 -2.2
winter 0.99 1.5 3.2 1.0 -1.5
Commercial
summer 0.85 0.99 3.5 1.2 -1.6
winter 0.9 1.3 3.1 1.5 -1.1
Industrial 0.85 0.18 6.0 2.6 1.6
Power plant 0.8 0.1 1.6 2.9 1.8
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Excitation System Components
Transducer
Ref.
Regulator Exciter Generator
PSS
Limiter + relay
Vref
Ver Controller Vtr Power Efd Et
Regulator amplifier
Plant
(Exciter)
Feedback elements
Block Schematic
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Reactive Power Control
Synchronous generators
Transformers
Loads
Compensating devices
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Control Devices:
Sources /Sinks --- Shunt capacitor, Shunt inductor
(Reactor), Synchronous condenser, and SVC.
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Speed Governor Systems :
Energy Supply
steam or water
Speed
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Types of Control:
Primary Control : Governor action
Secondary Control : AGC, load frequency control (For
selected generators)
Speed
Ref. Turbine Generator
Droop(Goveror)
+
1/R 1 Tws 1
1 Tws Tms KD
-
speed
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Load Shedding:
Trip signal 49.5
0.4 Hz/s
10% load rejection
1 Hz/s
15% load rejection
2 Hz/s
30% load rejection
4 Hz/s
50% load rejection
48
Other measures:
* Fast valving
* Steam by-passing
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Modules in a Program:
1. Data reading
2. Initialization
Steady state load flow
Control block parameter AVR, Gov., Machine, Motor, PSS, VDC, SVC.
3. Disturbance model
4. Control block modeling
5. Machine modeling
6. Load flow solution
7. Protective relay modeling
8. Special functions
Cyclic load
Arc furnace
Re-closure
9. Results output
Report
Graph
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Typical Swing Curve :
Constant Efd
90
60
30
AVR & PSS
AVR with no PSS
1 2 3 4 5 6
Time in seconds
10
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Typical Swing Curve :
180
60
0.01
1 2 3 4 5
Time in Sec.
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
AVR : Type 1
Vref s=f(Efd)
+ - Efd
VT 1 k1 1
1 sT1 1 sT2 k 2 sT3
- + +
PSS
sk 3
1 sT4
Mapping Range
T1 Tr 0.01 -- 0.10
T2 Ta 0.025 -- 0.2
T3 TE 0.5 -- 1.0
T4 TF1 0.5 -- 1.0
K1 KA 25 -- 200
K2 KE -0.5 -- 1.0
K3 KF 0.01 -- 0.1
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
AVR : Type 2
Vref SE
VRmax
VT + - Efd
1 k1 1
1 sT1 1 sT2 k 2 sT3
- + +
-
VRmin
Vs
sk3
1 sT4 1 sT5
Mapping Range
Mapping Range
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Steam Turbine Governing
System
P-up
C max
ref Pref+ Pmax
1+sT2 + P5
1/T3 1/S
0 k1(1+sT1)
+ - -
C min Pmin
P-dn
Ps
1/(1+sT1 ) 1/(1+sT2) (1/1+sT3) (1/1+sT4)
T2 : 10.0 k3 : 0.324 k3 + k4 : HP
T3 : 0.5 k5 : 0.4 k5 + k6 : IP
T4 : 99.9 k7 : 0.0 k7 + k8 : LP
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Hydro Governor
P-up
Cmax
Pmax
ref + 1 1 1
1 sT1 T2 s
Ps
+ -
- Pmin
Cmin
P-dn
sT3
+ k1 .
1 sT3
Transient Droop Compensator
+
k2
Permanent Droop Compensator
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Hydro Turbine
Ps DM
1-sT1
T1 (T) : 1.0
1+0.5sT1
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Transient Stability Enhancement
Philosophy :
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Transient Stability Enhancement
Methods :
1. High speed fault clearing.
2. Reduction of transmission system reactance.
3. Regulated shunt compensation.
4. Dynamic Braking.
5. Reactor switching.
6. Independent pole operation of circuit breaker.
7. Single pole switching
8. Fast valaving.
9. Generator tripping.
10. Controlled system separation and load shedding.
11. High speed excitation systems.
12. HVDC transmission link control.
11
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Major references used in the development of
Transient Stability Studies Module
1. Dommel, N. Sato “Fast Transient Stability Solutions”, IEEE
Transactions on Power Apparatus and Systems, 1972, PP 1643 -
1650.
2. W. Dommel, “Digital computer solution of electromagnetic transients
in single and multiphase networks”, IEEE Transactions on Power
Apparatus and Systems, April 1969, Vol. PAS-88, PP 388 - 399.
3. IEEE Committee Report, “Dynamic Models for Steam and Hydro
Turbines in Power System Studies”, IEEE PES Winter Meeting, New
York, Jan./Feb. 1973. (Paper T 73 089-0).
4. IEEE Committee Report, “Proposed Excitation System Definitions for
Synchronous Machines”, IEEE Transactions on Power Apparatus and
Systems, Vol. PAS-88, No. 8, August 1969.
5. IEEE Committee Report, “Computer representation of excitation
systems”, IEEE Transactions Power on Apparatus and Systems,
June 1968, Vol. PAS-87, PP 1460 - 1464.
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Queries & Discussions
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Thank You
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Introduction to Power
System Protection
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Topics for Discussion
Protective relaying
Need for protection
Types of Protection
General Philosophy
Over-Current Relays
Distance Relays
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Introduction
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Protective Relaying
Safeguard equipment from damage during
abnormal operating conditions.
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Need for Protection
Loss of equipment (Permanent or Partial damage)
Loss of production
Revenue loss
Fire hazard, loss of life
Loss of confidence level in using electricity as a
commodity
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Functions of Protection
Primary function - Prompt removal of faulty
element suffering a short circuit, or when it starts
to operates in an abnormal manner
Secondary function, to provide indication of
location and type of failure
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Types of Protection
Over voltage protection – Lightning/Surge
arrestors, Insulation co-ordination
Fault protection (over loading/current) -
Application of Relays
Protection for human (safety) – Earthing and
Earth mats, clearances, insulation
12
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Protection Philosophy
Cricket Protection
Position the fielders Designs the system
and sets the relays
Delivers the ball Charges the system
Batsman hits the ball Fault occurs
Mid-off stops/fails Primary relay
operates/ fails
Long-off stops/ fails Backup relay
operates / fails
Match lost ? Loss of
Power/Revenue
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Protection Features
Sensitive – detection of short circuit or abnormal
condition
Selectivity – ensure that only the unhealthy part of
the system is disconnected
Speed – to prevent or minimize damage and risk of
instability of machines
Reliability – to ensure proper action even after long
periods of inactivity and also after repeated
operations under severe conditions
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Protection System Design
Design of circuit breakers
and isolating devices
Battery
Transducer (sensing
devices)
CB
Trip Coil
Relay design Aux. Relay Contacts
Switch
Relay application and co- Relay
ordination CT
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Protection Statistics
Correct and Undesired
Operation as per the
settings.
Settings are wrong, not
updated
Human Error
Leaving the trip circuit
open after test
Open circuited trip coils
Mechanical failure of circuit
breaker
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Causes of Protection Failure
Current or voltage supply to the relays
DC-tripping voltage
Protective relays
Tripping circuit or breaker mechanism
Circuit breaker
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Equipment Selection
Relay selection
Selecting a relay scheme to recognize the existence
of a fault within a given protective zone
Initiate circuit breaker operation
Circuit breaker selection
Determine the interruption requirement
Normal current and voltage rating
Selection of breakers and location
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Fault Characteristics
Magnitude
Frequency
Phase angle
Duration
Rate of change
Direction or order of change
Harmonics or the wave shape
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Protection Scheme Design
Divide the system into
zones
Design appropriate
breakers
Minimize the amount of
load being disconnected
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Types of Relays
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Schematic of a Static Relay
Over-Current :
TRIP
CT
ICT R
FC COM T NOT AR
PP
13
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Schematic of an NR
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Over-Current Relays
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Basics
Relays operate based on the current sensed.
Can be used as primary or backup protection
May be directional or non-directional
Operation time depends on curve selected
Settings involve selecting the plug setting and
the time setting
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Definitions
Plug Setting
Plug setting is that value of current above
which the relay should operate.
Time dial setting
The time dial setting of the relay provides the
discrimination between the primary and backup
relay.
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Standard Curves
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Curve Equations
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Relay Co-ordination
Identification of main and backup relays
Steady state analysis
Determination of plug setting
Determination of definite time setting
Determination of time dial setting
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Distance Relays
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Basics
*Distance relays are the most widely used relays for
transmission lines protection.
*The relay measures the distance in terms of
impedance by measuring the voltage and current.
*Major advantage is that relay acts as primary as
well as remote back up.
*The present digital distance relays offer more
functionalities in terms of protection, monitoring and
control rather than just impedance measurement
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Types of Characteristics
Mho
Quadrilateral
Lentical
Quadra-Mho
Elliptical Characteristics
Circular
14
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Mho Characteristic
X
Zone-3
Zone-2
(R3X3) Zone-1
(R2X2)
(R1X1)
offset R
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Quadrilateral Characteristics
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Impedance Calculation
Relays operate if the impedance seen is within
the set characteristics known as zones.
Separate zones are present for phase and earth
loops.
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Philosophy
Zone Direction Protected Reach Time Setting (s)
Zone 1 Forward 80 % of the PL Instantaneous
For Single Circuit –
0.35
120 % of the PL
Zone 2 0.5 to 0.6 – If Z2
(for 400kV and Forward reach overreaches
above) For Double Circuit –
50% of the shortest
150 % of PL
line;
0.35 – otherwise
120% of PL or
Zone 2 (for 220kV
Forward 100% of PL + 50% of 0.35
and below
ASL
PL: Protected Line, ASL: Adjacent Shortest Line, ALL: Adjacent Longest Line
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Philosophy
Zone Direction Protected Reach Time Setting (s)
Zone 3 Forward 120% 0f (PL + ALL) 0.8 to 1.0
0.5 if Z4
10% for the Long
overreaches 50% of
line (>100 km)
Zone 4 Reverse reverse shortest
20% for short line
line
(<100 km)
0.35: otherwise
Note : Z2 reach should not encroach the next lower voltage level
: If Z3 reach encroaches next voltage level (after considering in feed), Z3 time must
be coordinated
: If utility uses carrier blocking scheme, then the Z4 reach may be increased as the
requirement. It should cover the LBB of local bus bar and should be coordinated with Z2 time of
the all other lines.
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Zone 1
Instrument Transformer errors
Transmission line is not completely balanced
Hence apparent impedance is susceptible to an error
of 20%.
Zone 1 is under reached to prevent incorrect
operation for fault on next line (Eg. Close to adjacent
bus) Who covers
the Remaining
?
Zone 1 reach
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Zone 2 for single circuit line
To provide coverage to remaining portion of
protected line
Over reach margin should be min 20% (for reason
discussed in Zone1)
Zone 1 reach
Zone 2 reach What about
backup
protection for
fault here ?
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Zone 2 for double circuit line
Zone 1 reach
Zone 2 reach What about
backup
protection for
fault here ?
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Zone 3
Zone 3 protection is backup protection for fault on
adjacent line. Considering
Need to reach the PL + ALL Errors
Zone 1 reach
Zone 2 reach
Zone 3 reach
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Resistive Reach (Zone 1)
Earth
Should provide maximum coverage considering fault
resistance, arc resistance and tower footing
resistance.
Should be <4.5 * X1 (X1=Zone 1 reach)
Phase
Reach should be set to provide coverage against all
types of anticipated phase to phase faults subject to
check of possibility against load point encroachment
Should be <3*X1
15
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Resistive Reach (Zone 2 and
Zone 3)
The philosophy used for Zone 1 is applicable here
also.
Additionally
Due to in-feeds, the apparent fault resistance
seen by relay is several times the actual value,
this should be considered before arriving at the
setting.
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Queries and Discussions
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Thank You
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Protection Case Studies
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Topics for Discussion
Overcurrent Relays
Distance Relays
Differential Relays
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Overcurrent relays
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Relay coordination sample ~
B-1
R1
• Generator data
• Generator fault level : B-2
• Maximum : 1000 MVA R2
16
Copyright @ Power Research & Development Consultants Pvt. Ltd
6
Relay data
Relay
Sl No Maximum
Relay Name CT rating Characteristics
Load Current(A)
1 R1 800 800/1 3s
2 R2 400 400/1 3s
3 R3 200 200/1 3s
4 R4 100 100/1 3s
Relay Pairs
Sl No Primary Relay Backup Relay
1 R4 R3
2 R3 R2
3 R2 R1
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Fault Studies results
Fault Current
Relay Impedance Fault Bus Fault MVA
in A
R1 0.1 1 1000 52486.388
R2 0.2 2 500 26243.194
R3 0.3 3 333.33 17495.288
R4 0.4 4 250 13121.590
2 R3 R2 3 17495.288
3 R2 R1 5 26243.194
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Plug setting computation
For Relay R4
% Setting Primary Setting Remarks
50 50 < Load Current
75 75 < Load Current
100 100 = Load Current
Load Primary
Relay CT Rating % Setting
Current Current
R1 800 800/1 100 800
R2 400 400/1 100 400
R3 200 200/1 100 200
R4 100 100/1 100 100
16
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Time setting computation
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Time setting computation
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Final relay settings
Relay Plug Setting TMS
R1 800 0.6
R2 400 0.47
R3 200 0.29
R4 100 0.05
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Co-ordinated Curves
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Application
• Backup to distance relays (220/132 kV and
below)
• HV and LV side of ICT as backup to differential
relays
• DEF is used in 400 kV line as protection for high
impedance earth faults.
• Non directional OC is also used in 400kV line
under fuse fail condition
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
DOC Setting Philosophy
• For 220 kV and 132 kV line with only one main distance
protection, DOC must be set in such a way that for fault
at remote bus the DOC (IDMT) is coordinated with Zone
2 time typically 1.1 s
• For DOC at 400 kV side of ICT, it is to be set such that
for fault at remote end bus (longest line), DOC (IDMT) is
coordinated with Zone 3 time
• Instantaneous DOC can be used at 400 kV side of ICT,
set such that
– It does not pickup for fault on 220 kV bus
– It does not pickup for transformer charging current
– Time setting of 0.05 s to 0.1 s can be considered.
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
DEF Setting Philosophy
• For 220 kV and 132 kV line with only one main distance
protection, DEF (IDMT) must be set in such a way that it is
coordinated with Zone 2 time
• For 400 kV line or where two main distance protection is
used, DEF is used only for protection against high impedance
faults and is coordinated with Zone 3 time
• For DEF at 400 kV side of ICT, it is to be set such that for
fault at remote end bus (longest line), DEF (IDMT) is
coordinated with Zone 3 time
• Instantaneous DEF can be used at 400 kV side of ICT, set
such that
– It does not pickup for fault on 220 kV bus
– It does not pickup for transformer charging current
– Time setting of 0.05 s to 0.1 s can be considered.
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Instantaneous Setting calculation
315 MVA
Zps=0.12 pu
15000 MVA
Ia = 3225 A Zebra
55 km
R2
3φ Fault
3000 MVA
• Reflected Current = 1.3 * 3225 = 4195 A
• Inrush Current = 8*450 = 3600 A
• Ip>> = Highest of the above two = 4200 A (Set
value).
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Distance relays
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
R1 = 0.0297 Ω/km
200 km
Station 4
130 km Twin Moose
G
CT input Twin Moose
21 162 km
Station 3
Twin Moose
CCVT input
17
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Zone 1
• Primary referred
• X1_prim = 0.332 *130*0.8 = 34.5 Ω
• Secondary referred
• X1_sec = 34.5*CTR/PTR, CTR:CT
Ratio, PTR: PT Ratio
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Zone 2
• Protected line is single circuit
• Adjacent Shortest Line: 80 km to Station 5
• X2_Prim = 0.332*130*1.2 = 51.79 Ω (130+26
km)
• X2 covers only 32% of Adjacent Shortest Line.
• Operating Time : 0.35s
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Zone 3
• Adjacent Longest Line is 200 km to Station 4
• X3_Prim = 0.332*(130+200)*1.2 = 131.47 Ω
• That is 130 km PL + additional 266 km
• Time Setting
• Check if Zone 3 of PL encroach Zone 3 of adjacent
line protection
• Zone 3 of Station 2- Station 5 line is 202.8 km.
• The Two Zone 3 are overlapping and hence must be
time coordinated.
• Time = 0.8+ 0.06 (tcb)+0.03 (treset)+0.06 (tsf )= 0.95
(set 1s)
• tcb, treset and tsf values are as per CEA report
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Points to be Considered
• Obtain the actual line parameters from line impedance
test results. If not available, consider the standard
values.
• Check Relay Setting type
• Primary or secondary referred values
• RX or Z
• Computation of Zero sequence compensation factor.
(K0, Kn or Kr-Kx
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Points to be Considered
• Note the shortest and longest line emanating from
the adjacent substation, along with impedance
values
• For double circuit lines, check if it is two single
circuit tower or one double circuit tower
• If necessary, carry out system study to study the
effect of in feed, mutual coupling, power swing to
achieve coordinated setting.
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Load Encroachment Consideration
• Basic Check
• Rated V = 63.5 V and Rated I = 1 A. (Secondary
Referred)
• Phase Impedance = (0.85*V)/(1.5*I) = 36 Ω
• R reach must always be less than 36 Ω
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Operating Time coordination
• Zone 1 is primary protection, hence instantaneous
operation
• Zone 2 is a overreach zone and hence needs to be
delayed.
• If errors involved is less, then Zone 2 can trigger for Zone 1 fault of
adjacent line. Hence Zone 2 is to be coordinated with Zone 1.
Time (s)
0.35
0
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Operating Time Coordination
• For fault at 80% of segment B, Segment B zone 1 can
also under reach by 20%
• Hence only Zone 2 of Segment B pick up
• Segment A Zone 2 can also pickup.
• Hence segment A Z2 to be coordinated with segment
B Z2
0.5 to 0.6
Time (s)
0.35
0
Segment A Segment B
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Operating Time coordination
• For 220 kV and below, if Zone 2 of PL can encroach the
Zone 2 of ASL, then coordination is achieved by
reducing the Zone 2 reach of PL to coordinate with
Zone 2 reach of ASL.
Reduced Zone 2 reach for
coordination purpose
Time (s)
0.35
0
Segment A Segment B
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Operating Time coordination
• Zone 3 is the backup protection and hence needs to
be operate after Zone 1 or Zone 2 has failed to clear
the fault.
• Zone 3 is coordinated with Zone 2 time of adjacent
line relay.
0.8 to 1.0
0.5 to 0.6
Time (s)
0.35
0
Segment A Segment B
18
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Load Encroachment Consideration
• Reach setting is given considering the various “under
reach” effect that can occur. This makes the resistive
setting “high”
• Phase loop measures the phase impedance and hence
has to be set such that it does not trip for abnormal or
emergency system loading condition
• Emergency loading condition is to be used to decide the
load encroachment point.
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Load Encroachment Consideration
• Following criteria may be considered
• 1.5 times the thermal rating of line
OR
• 1.5 times associated bay equipment rating
(minimum of all equipment)
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Power Swing Blocking
• During power system disturbances, unbalance
exist between generators which cause the
operating point to oscillate
• R-X trajectory might enter the zones of protection
• Blinder schemes are traditionally used to detect
swings and prevent unnecessary tripping
• The rate of change of impedance is used to
differentiate between power swings and faults
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Power Swing Blocking Schemes
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
PSB Options
No power swing blocking
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Stability Studies for PSB Settings
• Identify the generators which are prone to instability
and the lines where power swings are observed.
• Determine the location where system should be
separated
• Time and reach settings are calculated
• Outermost zone reach should be within the inner
boundary
• Outer boundary should be less than load impedance
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Carrier Aided Protection
Transfer
Unblocking
Direct
Blocking
Permissive
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Permissive Under-Reach
A Close to A
B
Z1 Z1
Z2 Z2
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Permissive Over-Reach
A Close to A
B
Z1 Z1
Z2 Z2
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Queries & Discussions
19
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Thank You
20
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Principles of Unit
Protection
1
Copyright @ Power Research & Development Consultants Pvt. Ltd
Topics for Discussion
20
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Introduction
Meaning
Protection which responds to faults only
in one zone
No need for time grading
Normally fast acting – not affected by
fault severity
Operates based on the comparison of
boundary conditions
20
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Types of Unit Protection
Differential Protection
Utilizes Current
Over-Fluxing Protection
Utilizes Voltage and Frequency
Backup-Impedance Protection
Utilizes Current and Voltage
20
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Differential Protection
20
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Setting Consideration
The effect of magnetizing inrush during initial
energization should be considered.
20
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Phase Correction and Zero
Sequence Filtering
20
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Ratio Correction
20
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Biased Differential Relay
20
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Requirement of Biased
Relays
Errors which vary proportionally with the operating
conditions such as:
– Errors due to transformer taps
– CT errors
– Ratio Mismatch – Difficulty in obtaining exactly
similar currents in both secondaries
Transient Errors
– CT Saturation
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Operating Characteristics
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
• During CT
saturation
magnetizing
impedance = zero
• Infinite
CT Saturation
magnetizing current
will flow in the
shorted path.
• Secondary of the
network acts as
open circuit.
• During this
situation secondary
current Is = zero
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
High Impedance Differential
Protection
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Comparison of Differential
Schemes
Low Impedance High Impedance
• Identical CTs not required • Stable for CT saturation for
external faults
• Not stable for CT • Identical CTs are preferred
Saturation for external for sensitive operation
faults
• May require an MOV to
• No protection for over- protect Relay against
voltage required voltage developed during
external faults
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Restricted Earth Fault
Protection
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
Amplification of Neutral
Current
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Currents During External Faults
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
Currents During an Internal
Fault
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Applications
Transformer Protection
Differential Relays
Mainly percentage biased relays
2nd and 5th harmonic restraints are provided
High Set may be provided on HV winding
21
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Modern Day Transformer Protection
22
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Line/Cable Protection
Differential Protection
– Percentage biased schemes are used
– Inrush currents are considered
– Major challenge was the distance between two ends
Pilot Wire Protection
– Measurements communicated over the pilot wire
– Balanced voltage as well as circulating current schemes are
used
22
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Balanced Voltage Scheme
22
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Comparison of Pilot Wire
Schemes
Balanced Voltage Circulating Current
Works on the tripping Works on blocking principle
principle
Interruption to the pilot Interruption of the pilot
wires causes blocking wires causes tripping
Short circuit of pilot wires Short circuit of pilot wires
leads to tripping leads to blocking
Overcurrent protection Overcurrent protection
required to prevent required to block operation
incorrect tripping due to for large currents due to
short circuit of pilot wires pilot wire interruption
22
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Bus-Bar Protection
Differential Schemes
Incoming and outgoing currents are
balanced
Multiple CT connections
Both High and Low Impedance Schemes are
used
Partial Bus Bar Relay
Retention of supply to healthy portion of the
network
22
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
Partial Bus Bar Relay Example
225
225
Overall Differential
Protection
22
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
Setting Examples
Sample Network
22
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
General Parameters
22
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Secondary Ratio
Compensation
22
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Primary Side Ratio
Compensation
Parameter Value Unit
Primary full Load current At Maximum tap Voltage 249.9351815 A
Primary side Full load Current on CT secondary side at Mid tap Voltage 0.874773135 A
Primary full Load current on CT secondary side At Maximum tap Voltage 0.833117272 A
Primary full Load current on CT secondary side At Minimum tap Voltage 0.920813826 A
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 0
Differential Current
Computation
Parameter Value Unit
Primary full Load current on CT secondary with ratio
0.952380952 A
correction At Maximum tap Voltage
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 1
Restraint Current
Calculation
Parameter Value Unit
Restraint current at maximum tap 0.976190476 A
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 2
Relay Settings
Setting Value Unit
Min Current 0.15 A
Slope 1 Start 0.75 A
Slope 1 20
Slope 2 Start 1.33 A
Slope 2 75
High Set 12.5 A
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 3
Relay Characteristics
0.9
0.8
0.7
I differential on CT Secondary
0.6
0.5
0.4
0.3
0.2
0.1
0
0 0.5 1 1.5 2 2.5
I restraint on CT Secondary
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 4
REF - CT Selection
The voltage across the stabilizing resistor at maximum through fault
current is given by
Vs = k*Ikmax*(RCT + 2. RL)/ n volts
Where:
RCT= current transformer secondary winding resistance
RL = One way maximum lead resistance from the CT to the
relaying point
Ikmax = maximum external fault current
k = stabilizing factor used to account for the distorted voltage
wave due to faults.
n = transformation ratio of the CT
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 5
REF - Voltage Settings
Considerations
Always, relay operating voltage should be less than Vk/2 but
more than Vs.
If stability voltage increases beyond Vk, CT enters saturation
region for which there is infinite Magnetization (Current), but
voltage remains at the same level (no huge change in
voltage). This condition is seen as open circuited on the
secondary.
Vset >Vs, such that relay will not operate for external fault
with CT saturation condition.
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 6
REF - Stabilizing Resistor Design
The value of the Iprim at which the relay operates at certain settings
can be calculated as follows:
Iprim = n * (Ir + m*(Vs/Vk)*Io) A
Where,
n = the transformation ratio of the current transformer
Ir = the current value representing the relay setting
m = the number of current transformers included in the
protection
Io = the magnetizing current of one current transformer at knee
point voltage, Vk.
The relay setting current Ir can be computed as
Ir = (Iprim / n) - m*(Vs/Vk)*Io A
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 7
REF - Metrosil Requirement
The following equations should be used to estimate the peak
transient voltage that could be produced for an internal fault.
Vp = 2 * sqrt(2. Vk(Vf – Vk)) volts
Vf = If *(RCT + 2.RL + Rs) volts
Where:
Vp = Peak voltage developed by the CT under internal fault
conditions.
Vk = Current transformer knee-point voltage.
Vf = Maximum voltage that would be produced if CT saturation
did not occur.
If = Maximum internal secondary fault current.
RCT = Current transformer secondary winding resistance.
RL = One way maximum lead burden from current transformer to
relay.
Rs = Stabilizing resistor.
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 8
Queries & Discussions
23
Copyright @ Power Research & Development Consultants Pvt. Ltd 9
Thank You
24
Copyright @ Power Research & Development Consultants Pvt. Ltd 0