600DT 17.

5mm DIN Rail Timer

Features:
! 15 Functions
! 8 Time Ranges
! Front Key Pad Setting
! Universal supply voltage
! Lithium Battery Backup
! Slim, Space Saving Design
! DIN Rail Mount

Size: DIN 17.5mm


Certifications: C UL US

PENDING

Technical Specifications Environmental Specifications

Temperature Operating: 0 to 50oC (32 to 122oF)


Input Specifications
Storage: -20 to 75oC (-4 to 167oF)
Accuracy Setting: ± 0.1% of set time or ±50msec Humidity (non-condensing) 95% RH
(whichever is greater)
Weight 69 gms (0.163 lbs)
For Y contact operation: +100msec
Repeat: ± 0.1 % Protection Level IP50 for faceplate
Reset Front Key, On interruption of power; IP40 for housing
Reset time < 100 msec IP20 for terminals

Output Specifications 44mm


Dimensions
Output Contact SPDT (1 C/O)
Contact Rating 8A @ 250V AC
45mm

67.5mm

35.3mm
90mm
Functional Specifications

Modes On delay (A)


Interval (B)
Asymmetrical cyclic OFF first (C) 17.5
mm
Asymmetrical cyclic ON first (D)
60mm
Cyclic equal OFF first (E) Symmetrical 35mm Din Rail (EN50022) Mouting

Cyclic equal ON first (F)


Pulse output (H) Terminal Connections
Delay on break (J)
+ -
Delay on make / break (K)
Interval after break (L) A1 A2
Single shot (P)
Retriggerable Single shot (Q)
Control
Latching relay (R) Contact Y1
Delay with Totalise (t)
15 25
Interval with Totalise (U)
16 18
Time Ranges 0 - 99.9 sec / min /hr NC NO
0 - 999 sec / min / hr
0 - 9:59 min:sec COM
0 - 9:59 hr:min
Cable Size (AWG): 16 ; Tightening Torque (Lb-inch): 4.5
Counting Direction Down Cable Size (mm2): 1.5 ; Tightening Torque (N-m): 0.5
Memory Yes (selectable)

Ordering Information
Supply Voltage
Certification
Supply Voltage 20-240V AC/DC (AC : 50 / 60 Hz) Part No. Supply Voltage
C UL US

Power Consumption 4VA max PENDING

600DT 20-240V AC/DC

600DT-CU 20-240V AC/DC

www.selec.com 1
600DT 17.5mm DIN Rail Timer

Timing Diagram

Function: ON Delay (A) Function: Interval (B) Function: Asymmetrical Cyclic OFF First (C)

Supply Supply Supply


Voltage Voltage Voltage
Start

NO Contact NO Contact NO Contact


NC Contact NC Contact NC Contact
T T T1 T2 T1 T2 T1 T2

T = set time T = set time T1 = OFF time ; T2 = ON time

Function: Asymmetrical Cyclic ON First (D) Function: Cyclic Equal OFF First (E) Function: Cyclic Equal ON First (F)

Supply Supply Supply


Voltage Voltage Voltage

NO Contact NO Contact NO Contact


NC Contact NC Contact NC Contact
T1 T2 T1 T2 T1 T2 T T T T T T
T1 = ON time ; T2 = OFF time T = set time T = set time

Function: Pulse Output (H) Function: Delay On Break (J) Function: Delay On Make / Break (K)
Supply Voltage Supply Voltage
Supply
(U) (U)
Voltage
Control Contact Control Contact
Y1 Y1

NO Contact NO Contact NO Contact


NC Contact NC Contact NC Contact
T1 T2 T T T T
t1
T1 = Off time ; T2 = On time T = set time; t1 < T T = Set time

Function: Interval After Break (L) Function: Single Shot (P) Function: Retriggable Single Shot (Q)
Supply Voltage Supply Voltage Supply Voltage
(U) (U) (U)
Control Contact Control Contact Control Contact
Y1 Y1 Y1

NO Contact NO Contact NO Contact


NC Contact NC Contact NC Contact
T T T T ta T
T = Set time T = Set time ta<T ; T = Set time

Function: Latching Relay (R) Function: Delay With Totalise (T) Function: Interval With Totalise (U)
Supply Voltage Supply Voltage Supply Voltage
(U) (U) (U)
Control Contact Control Contact Control Contact
Y1 Y1 Y1

NO Contact NO Contact NO Contact


NC Contact NC Contact NC Contact
t1 t2 t1 t2
t1 + t2= T ; T = Set time t1 + t2= T ; T = Set time

www.selec.com 2