You are on page 1of 3

Data sheet for three-phase squirrel cage motor

SIMOTICS HV A-compact PLUS


Article number 1RQ1500-6JA60-Z
Options A40+A65+G50+K97+M13+M52

Client order no. Item no.


Order no. Consignment no.
Offer no. Project
Remarks

General data Environmental conditions


Standards/specifications IEC 60034 Coolant temperature 40 °C
Usage area Safe Area Ambient temperature -20 °C … 40 °C
Type of explosion protection None Installation altitude 1000 m

Electrical data Mechanical data


Rated power P N 1500 kW Type of construction IM 1001 (IM B 3)
Rated voltage U N 6 kV Degree of protection IP 55
Voltage fluctuations ± 5 % (IEC 60034-1, range A) Shaft height 500
Frequency f N 50 Hz Method of cooling IC 611
Frequency fluctuations ± 2% (IEC 60034-1, range A) Type of insulation MICALASTIC - VPI
Stator circuit Y (Star) Rotor winding material Alumineum
Rated current I N 177 A Bearing design Rolling-contact bearing
Number of poles 6 Bearing cooling Air cooled
Rated speed n N 992 1/min Bearing DE 6234
Rated torque M N 14447 Nm Bearing NDE 6228
Partial load P / P N 5/4 4/4 3/4 2/4 Vibration severity grade, acc. IEC Vibration severity grade A
60034-14
Efficiency η % 95.4 95.8 96.0 95.9
Direction of rotation Clockwise (view on DE)
Power factor cos φ 0.85 0.85 0.82 0.74
Sound pressure level L pA (1m), Tolerance +3dB
mains
- no-load 80 dB(A)
Mode of operation continuous operation (S1)
- load
Thermal class 155 (F), utilized to thermal class 130 (B)
Measuring surface level Ls 19 dB(A)
Starting / rated current I A /I N 5.6
Coating (paint finish) Standard coating
Tolerance I A /I N + 20% (IEC 60034)
Color, paint shade RAL 7030
Starting / rated torque M A /M N 1.16
Total weight # 7100 kg
Breakdown / rated torque M K /M N 2.5
Rotor weight 1519 kg
Moment of inertia J 57.9 kg.m²
Dynamic foundation load at 2- pole terminal short circuit
Safe stall time hot / cold 13.0 s / 28.0 s
downward / upward -/- kN / -/- kN
Perm. no. of consecutive starts, 3/2
cold/warm *
Type of terminal box
*at max.external moment of 940 kg.m²
inertia Type of terminal box 1XD2 313-3AA
*U /U N ≥ 90 %, M Last ~ n ², M L ast /M N ≤ 0.5 % Terminal box, Star connection without

Factory location
Factory location China

# These values apply to catalog design with standard environmental conditions.

Offer no. , Item no. Page 1 of 2 Version: 2020.01


Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Generiert: 01.03.2021 07:07:54
Special design

A40 2 resistance thermometers PT 100 for 2-, 3- or 4-wire connection from terminal box for anti-friction bearings

A65 6 embedded resistance thermometers Pt 100 without lightning arresters for 3- or 4-wire connection from terminals

G50 Shock pulse measurement (SPM), measuring nipple at D.E. and N.D.E.

K97 Clockwise rotation

M13 Anti-condensation heating 220-240V (min. 198V, max. 264V)

M52 Separate auxiliary terminal box for anti-condensation heating

SIDRIVE IQ View

Enjoy the product in our Augmented Reality App "SIDRIVE IQ


View". Now available for iOS and Android devices. Download
the App from Apple or Google Play Store and scan the QR-
code.

Offer no. , Item no. Page 2 of 2 Version: 2020.01


Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Generiert: 01.03.2021 07:07:54

You might also like