You are on page 1of 2

600XU 17.

5mm DIN Rail Timer

Features :
13 Functions
!
10 Time Ranges
!
LED Indications : Relay ON, Power ON
!
Front knobs for Time Range, Time Scale & Mode Setting
!
Slim, Space Saving Design
!

DIN 17.5mm Certifications :

Display Specifications Mechanical Specifications

LED Indications Relay ON, Power ON Mounting DIN Rail Mount


Weight 64gms

Input Specifications
Dimensions
Accuracy Setting : ±5% of F.S.
Repeat : ± 0.5% (F.S. = Full Scale) 600XU 44mm

Output Specifications
45mm

Relay Contact 1 C/O SPDT

67.5mm

35.3mm
90mm
Contact Rating 5A @ 250V AC

Functional Specifications 17.5


mm
Modes On delay (A)
60mm
Interval (B)
Cyclic equal OFF first (C)
Cyclic equal ON first (Ci) Terminal Connections
Pulse output, 500ms fixed (D)
Delay on break (E) 600XU + -
Delay on make / Delay on break (F)
Interval after break (H) A1 A2
Single shot (I)
Retriggerable single shot (J)
Latching relay (K) Control
Delay on make with totalise (Ai) Contact
Interval with totalise (Bi) Y1
15 25
Time Ranges 0.1 - 1sec, 0.3 - 3sec, 1 - 10sec, 3 - 30sec
0.1 - 1min, 0.3 - 3min, 1 - 10min, 3 - 30min 16 18
0.1 - 1hr, 0.3 - 3hr NC NO

Resolution 0.1sec COM


Reset On power interruption
Cable Size (AWG) : 16; Tightening Torque (Lb-inch) : 5.3....7.08 ibf.in
Reset time < 100msec
Cable Size (mm2) : 1.5; Tightening Torque (N-m) : 0.6....0.8 N. M

Auxiliary Supply Specifications

Supply Voltage 20 to 240V AC (50 / 60Hz), 12 to 240V DC


Power Consumption 3.2 VA max

Environmental Specifications

Temperature Operating : 0 to 50oC (32 to 122oF)


Storage : -20 to 75oC (-4 to 167oF)
Humidity (non - condensing) 95% RH

www.selec.com 1
600XU 17.5mm DIN Rail Timer

Timing Diagram

Function: ON delay (A) Function: Interval (B) Function: Cyclic equal OFF first (C)

Supply Supply Supply


Voltage Voltage Voltage
Start Control
Contact (Y1)

NO Contact NO Contact NO Contact


NC Contact NC Contact NC Contact
T T T T T

T = set time T = set time T = set time

Function: Cyclic equal ON first (Ci) Function: Pulse output (D) Function: Delay on break (E)
Supply Voltage
Supply Supply
(U)
Voltage Voltage
Control Contact
Y1
NO Contact NO Contact NO Contact
NC Contact NC Contact
T T T NC Contact
T P T T
T = set time t1
T = Set time ; P = 500msec T = set time; t1 < T

Function: Delay on make / break (F) Function: Interval after break (H) Function: Single shot (I)
Supply Voltage Supply Voltage Supply Voltage
(U) (U) (U)
Control Contact Control Contact Control Contact
Y1 Y1 Y1

NO Contact NO Contact NO Contact


NC Contact NC Contact NC Contact
T T T T T T
T = Set time T = Set time T = Set time

Function: Retriggable single shot (J) Function: Latching relay (K) Function: Delay on make with totalise (Ai)
Supply Voltage Supply Voltage Supply Voltage
(U) (U) (U)
Control Contact Control Contact Control Contact
Y1 Y1 Y1

NO Contact NO Contact NO Contact


NC Contact NC Contact NC Contact
ta T t1 t2
ta<T ; T = Set time t1 + t2= T ; T = Set time

Function: Interval with totalise (Bi)


Supply Voltage
(U)
Compliance
Control Contact
Y1
Applicable EMI / EMC Standards
NO Contact
NC Contact Product Standard
t1 t2
t1 + t2= T ; T = Set time
Category Reference Standards Testing Level
Electrostatic Discharge IEC 61000-4-2 Level-3
Electrical Fast Transient / Brust IEC 61000-4-4 Level-3
Ordering Information
Electromagnetic Field IEC 61000-4-3 Level-3
Product Code Supply Voltage Certification
Surge IEC 61000-4-5 Level-3
600XU-A-1-CU 20 to 240V AC, 12 to 240V DC
Conducted RF IEC 61000-4-6 Level-2

Rated Power Frequency IEC 61000-4-8 Level-4

Voltage Dip / Short Interruptions IEC 61000-4-11 Level-3

Conducted Emissions CISPR-11 Class-B


Rated Emissions CISPR-22 Class-A

Emission & Immunity IEC 61326-1


Safety IEC 61010-1
PFMF (Passing criteria) IEC 61000-4-8 Class A