You are on page 1of 2

XT546 / XT246 / XT346 Dual Display, Multifunction Timer

Features :
! Single Set Point
! LED Indications : Relay ON, Seconds, Minutes, Hours
! 3 digits, 7 segment LED, Dual Display

Certification :
48 x 48mm 72 x 72mm 96 x 96mm

Display Specifications Environmental Specifications

Display 3 digits, 7 segment LED, Dual display Temperature Operating : 0 to 50oC (32 to 122oF)
Height of Upper Display : 0.3785" Storage : -20 to 75oC (-4 to 167oF)
Height of Lower Display : 0.2720" Humidity (non - condensing) 95% RH
LED Indications Relay ON, Hr / Min /Sec

Mechanical Specifications
Input Specifications
Mounting Panel Mount
Accuracy Setting : ±0.05 % of set time or 50msec Weight XT546 : 142gms
Repeat : ±0.05% XT246 : 180gms
Start Input Gate / Pulse (Programmable) XT346 : 240gms

Output Specifications Dimensions

Relay Contact 2 C/O SPDT B G


Contact Rating 5A @ 250V AC

D
A

F
Functional Specifications
E C
Modes ON delay, Interval, Cyclic ON first, Cyclic OFF first
Time Ranges 0 - 9.99sec DIM B C D E F G
0 - 99.9sec Models A
0 - 999sec XT546 48 48 94 45 4 46 46
0 - 9:59min : sec
0 - 99.9min XT246 72 72 83.7 67 10 69 69
0 - 999min XT346 96 96 73 90.5 10 92 92
0 - 9:59hr : min
0 - 99.9hr
0 - 999hr Terminal Connections
Resolution 0.01sec XT546
Counting Direction Down L
1 11 6 COM
+
Set Point 1 START
- 2 7
Time Setting By keys on front panel N RST

NO1 NO2
Reset Front, Remote, 3 8

On power interruption (programmable) COM1 COM2


4 9
Memory Retention Yes (selectable)
5 12 10
Configuration Lock Yes NC1 NC2

Cable Size (mm2) : 1.5; Tightening Torque (N-m) : 0.5


Auxiliary Supply Specifications
XT246 XT346
Supply Voltage 85 to 270V AC (50 / 60Hz) , 24V AC/DC (Optional) L
START
+ 1 10
-15% to 10% tolerance L
+ 1 8
START
-
2 11 COM
N
Power Consumption 4VA max -

N
2 9 COM
3 12
RST
3 10 RST 4 13

4 11 5 14
NO1
5 Part No. 12
NO2
6 15
NO1 NO2
COM1 COM2 7 16
6 13
COM1 8 17 COM2
NC1 7 14
NC2
NC1 9 18
NC2

www.selec.com 1
XT546 / XT246 / XT346 Dual Display, Multifunction Timer

TIMING DIAGRAMS

1. On delay, Interval modes : 2. Cyclic ON first, Cyclic OFF first modes :

Supply Supply

Start Start

Reset Reset

Output Output
ON Delay t t Cyclic ON t1 t2 t1 t2
t1 = ON
Output
t = Set time
Interval t t time Output t 2 = OFF
delay Cyclic OFF t2 t1 t2 t1 time

Typical application of Continuous start and Typical application of Gate start :


reset in On delay mode :

Supply
Supply
Gate
Start
Reset
Reset
t1 + t2 = t
Output t = set time
On delay delay
Output t = Set t t1 th t2
On delay th = hold
t t time time.
delay

Compliance Ordering Information


Applicable EMI / EMC Standards
Product Code Supply Voltage Certification
Product Standard
Category Testing Level XT546 85 to 270V AC
Reference Standards
Electrostatic Discharge IEC 61000-4-2 Level-3 XT546-CE 85 to 270V AC

Electrical Fast Transient / Brust IEC 61000-4-4 Level-3 XT546-24V 24V AC / DC

Electromagnetic Field IEC 61000-4-3 Level-3 XT246-24V 24V AC / DC

Surge IEC 61000-4-5 Level-3 XT246 85 to 270V AC

Conducted RF IEC 61000-4-6 Level-2 XT346 85 to 270V AC

Rated Power Frequency IEC 61000-4-8 Level-4

Voltage Dip / Short Interruptions IEC 61000-4-11 Level-3

Conducted Emissions CISPR-11 Class-B


Rated Emissions CISPR-22 Class-A

Emission & Immunity IEC 61326-1


Safety IEC 61010-1
PFMF (Passing criteria) IEC 61000-4-8 Class A

www.selec.com 2