You are on page 1of 7

Energy and Buildings 41 (2009) 175–181

Contents lists available at ScienceDirect

Energy and Buildings


journal homepage: www.elsevier.com/locate/enbuild

Modeling solar-driven ejector refrigeration system offering air conditioning


for office buildings
J. Guo *, H.G. Shen
School of Environmental Science and Engineering, Donghua University, 2999# North Renmin Road, Shanghai 201620, PR China

A R T I C L E I N F O A B S T R A C T

Article history: A lumped method combined with dynamic model is proposed for use in investigating the performance
Received 26 June 2008 and solar fraction of a solar-driven ejector refrigeration system (SERS) using R134a, for office air
Accepted 18 July 2008 conditioning application for buildings in Shanghai, China. Classical hourly outdoor temperature and solar
radiation model were used to provide basic data for accurate analysis of the system performance. Results
Keywords: indicate that during the office working-time, i.e., from 9:00 to 17:00, the average COP and the average
Solar-driven ejector refrigeration
solar fraction of the system were 0.48 and 0.82 respectively when the operating conditions were:
Lumped method
generator temperature (85 8C), evaporator temperature (8 8C) and condenser temperature varying with
Dynamic model
COP
ambient temperature. Compared with traditional compressor based air conditioner, the system can save
Solar fraction upto 80% electric energy when providing the same cooling capacity for office buildings. Hence, the system
offers a good energy conservation method for office buildings.
ß 2008 Elsevier B.V. All rights reserved.

1. Introduction inlet of the constant area tube, the system conditions such as
refrigerant and collector selections on the performance of the
Energy is considered as a major agent in the generation of system and presented abundant experimental data for reference
wealth and an important factor in economic development. With during system design. Other researchers [12] have presented
the sharp increase in the cost of the energy and the high energy numerical methods of simulating the ejector and studied the
consumed by the conventional air conditioners, the solar-driven parametric effect on the system performance. System optimization
ejector refrigeration system has recently received considerable investigations [13–15] have focused on various combined ejector
attention as alternative refrigeration for residential and commer- refrigeration systems for performance improvement.
cial space cooling application. An ejector driven by solar energy can An accurate SERS performance forecasting is an important
be used to replace the compressor which makes the refrigeration precondition for the optimal control and energy saving operation of
system to consume much less electric power than traditional air conditioning systems. Numerous prediction techniques, which
compressor based air conditioner. Moreover, the SERS is simple, mainly include thermodynamic method, dynamic method, lumped
reliable, and convenient for integration with buildings and can use method, exergy analysis method and the use of artificial neural
environmentally friendly working fluid. In addition, they utilize network (ANN) have been applied to predict the performance of
solar energy which is essentially non-hazardous, unlimited and SERS. Dynamic method is widely accepted as a technique which can
always available. describe in details what happens in the ejector while lumped
Since the idea of a SERS was advanced in the beginning of 1990s method offers a good way to tackle complex problems in actual
[1–3], a great deal of numerical and experimental works as well as situations. The advantage of the dynamic method with respect to
system optimization works have been reported in literatures [4,5]. other models is its ability to model the choking, shock and mixing
Various experimental studies [6–11] have examined the effect of the phenomena occuring in the ejector and can give detailed informa-
operation conditions such as the generator temperature, evaporator tion on the mass flow along the ejector. In this paper, the lumped
temperature and condenser temperature, the geometrical condi- method combined with dynamic model was used to forecast the
tions such as the area ratio (the cross section area ratio of constant performance of a solar-driven ejector refrigeration system.
area tube to the nozzle throat), the distance of the nozzle exit to the
2. System description

* Corresponding author. The SERS is shown in Fig. 1. It comprises of two loops, one is
E-mail address: shuheguo@163.com (J. Guo). solar collection loop which is the main energy source of ejector

0378-7788/$ – see front matter ß 2008 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2008.07.016
176 J. Guo, H.G. Shen / Energy and Buildings 41 (2009) 175–181

(named entrained fluid hereinafter) from the evaporator and the


Nomenclature two fluids mix together in the mixing chamber. In the diffuser, the
velocity of the mixed fluid is stepped down and the pressure is
A area (m2) lifted to the condenser pressure.
COP coefficient of performance
Cp specific heat of gas at constant pressure (kJ/(kg K)) 3. Mathematical model
D diameter (mm)
Being driven by solar energy, the performance of the SERS is
f solar fraction
affected not only by geometrical parameters of the ejector, but also
h enthalpy (kJ/kg)
by local climatic conditions. Taking these into considerations, a
I solar radiation (W/m2) lumped method combined with dynamic model was developed to
m mass flow rate (kg/s) investigate the performance of the SERS. The environmental
M Mach number friendly refrigerant R134a was used as the working fluid. And the
P pressure (Pa) climatic conditions of Shanghai were used for field modeling.
Q heat (W) The designed cooling capacity of the system was 6 kW with
R gas constant (kJ/(kg K)) evaporation temperature at 8 8C. A vacuum tube collector of 15 m2
T temperature (K) was employed for analysis.
V velocity (m/s)
3.1. Modeling the ejector performance

Greek symbols The main geometrical parameters of the designed ejector are
g specific heat ratio shown in Fig. 2. The dynamic model of ejector performance
h coefficient prediction similar to that given in reference [16] with the outlet of
Fm isoentropy coefficient of mixture the convergent–divergent nozzle located at somewhere in front of
v entrainment ratio, v = me/mm the constant area tube was adopted to analyze the system with real
gas property derived from NIST REFPROP (Version 6.01) [17].
Subscripts Suppose two chokes occur for both the motive and the
entrained fluids, then the mass flow follows the gas dynamic
AS after shock
equations:
c cooling
sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
DO diffuser outlet  ðg þ1Þ=ðg 1Þ
P in At gh 2
e entrained fluid m¼ p ffiffiffiffiffiffi
ffi (1)
T in R g þ1
HR heat required
I calculation step " #ðg þ1Þ=2ðg 1Þ
2
in inlet Aiþ1 M i 1 þ ððg  1Þ=2ÞMiþ1
¼ (2)
m motive fluid Ai M iþ1 1 þ ððg  1Þ=2ÞMi2
mt mixture
!r=ðr1Þ
NO nozzle outlet 2
Pi 1 þ ððr  1Þ=2ÞMiþ1
¼ (3)
t nozzle throat P iþ1 1 þ ððr  1Þ=2ÞMi2
y section y–y
3 constant area tube For a given ejector, the area is known, and the Mach number and
pressure PNO at convergent–divergent nozzle exit can be obtained
by Eqs. (2) and (3). Assuming that the entrained fluid mixed with
the motive fluid at section y–y, where it forms the ‘‘dynamic
refrigeration system (ERS) and the other is ejector refrigeration throat’’ for the entrained fluid, i.e., Mey = 1. For a given inlet
loop which supplies useful cooling to the user. stagnant pressure Pe, the pressure of the entrained fluid (Pey) at the
The solar collection loop is composed of collector, a hot water mixing section can be calculated by Eq. (3). Also, supposing the
storage tank, an auxiliary heater and a circulating pump. The motive fluid and the entrained fluid mixed at section y–y with
auxiliary heater is located between the hot water storage tank and uniform pressure, i.e. Pmy = Pey, known the convergent–divergent
the generator of the ejector refrigeration loop. When the hot water nozzle outlet Mach number and with pressure obtained as
temperature in the tank is not high enough to drive the ejector mentioned above, the Mach number of the motive fluid at section
refrigeration loop, the auxiliary heater will start automatically. y–y can be calculated by Eq. (3) if PNO > Pey. Otherwise, shock
The ejector refrigeration loop consists of two subsystems: the happens at the outlet of the convergent–divergent nozzle, and the
power subsystem, and the refrigeration subsystem. In the power flow abides by the shock wave theory. Then the cross-section area
subsystem, the refrigerant flows through the generator, the ejector, of the motive fluid core Amy at section y–y and that of the ejector at
the condenser and the circulating pump, and finally flows back to section y–y Ay can be obtained from Eq. (2) and the geometrical
the generator to supply high pressure motive fluid to the ejector. In parameter of the ejector, and consequently, the cross-section area
the refrigeration subsystem, the refrigerant flows through the of the entrained fluid Ay at section y–y is given by:
ejector, the condenser, the expansion valve, the evaporator, and
then back to the suction of the ejector to supply the required Aey ¼ Ay  Amy (4)
cooling capacity. The main part of the ejector refrigeration loop is
The mass flow of the entrained fluid me can be calculated by Eq. (1)
the ejector (Fig. 2), which is composed of a convergent–divergent
and the entrainment ratio is:
nozzle, suction chamber, mixing chamber and a diffuser. The
motive fluid is first accelerated to supersonic velocity in the me
v¼ (5)
convergent–divergent nozzle, which entrains the evaporated fluid mm
J. Guo, H.G. Shen / Energy and Buildings 41 (2009) 175–181 177

Fig. 1. Schematic diagram of solar-driven ejector refrigeration system.

According to gas dynamic equations (6) and (7), the temperature generator and the performance of the ERS are:
and velocity of motive and entrained fluids are:
Q c ¼ me ðh2  h6 Þ (10)
T in g1 2 Q HR ¼ mm ðh1  h5 Þ (11)
¼1þ My (6)
Ty 2 Qc h2  h6
COPERS ¼ ¼v (12)
Qg h1  h5
qffiffiffiffiffiffiffiffiffiffiffi Under the condition that the motive fluid undergoes a shock wave
V y ¼ My g RT y (7)
at the outlet of the nozzle, the pressure and Mach number after the
shock wave are described by Eqs. (13) and (14).
Based on energy and momentum conservation of the motive,
entrained and the mixed fluid, and taking the energy loss into P AS 2g
¼1þ ðM 2  1Þ (13)
consideration, the parameters of the mixture are: PNO g þ 1 NO
2
2 1 þ ððg  1Þ=2ÞMNO
Fm ½mm V my þ me V ey  ¼ ðmm þ me ÞV mt (8) MAS ¼ (14)
! ! 2
g MNO  ððg  1Þ=2Þ
2 2
Vpy Vey
mm C p T my þ þ me C p T ey þ
2 2
 2
 3.2. Modeling the performance of the system
V
¼ ðmm þ me Þ C p T mt þ mt (9)
2 Once the performance of the ejector and its refrigeration system
is obtained, the performance of the SERS can be described by:
Call for the database NIST REFPROP (Version 6.01) for the
properties of the gas, the cooling capacity, heat required by the COPSERS ¼ COPERS hcol (15)

Fig. 2. Schematic diagram of ejector geometry.


178 J. Guo, H.G. Shen / Energy and Buildings 41 (2009) 175–181

Where, hcol is the efficiency of the solar collector, given by: Then the effective solar energy gain and the solar fraction can be
calculated by the following equations:
T col  T a
hcol ¼ F R ðat Þ  F R U L (16)
Q col ¼ Acol I hcol (17)
I

Where, FR is the heat transfer factor, t and a are the solar incident heat geained from solar energy Q col
f ¼ ¼ (18)
ratio and absorption, respectively. UL is the total heat loss heat required for the generator=h Q HR =h
coefficient of collector, Tcol is the water temperature of the
collector, and Ta is the ambient temperature. where, Acol is the collector area, m2, I is solar radiation, W/m2.

Fig. 3. Schematic schedule of the program.


J. Guo, H.G. Shen / Energy and Buildings 41 (2009) 175–181 179

Fig. 4. Validation of the model. Fig. 6. COP of the ERS under various generator temperature.

Based on the assumption that: (1) the power consumed by the The entrainment ratio of the ejector used for the system
circulating pumps and that by the control system is neglectable; analysis is shown in Fig. 5. For a given ejector, higher generator
(2) the velocity at the ejector inlet, outlet and evaporator outlet is temperature means higher motive fluid pressure, which leads to a
neglectable; (3) the condenser temperature is 5 8C higher than higher velocity at the exit of the convergent–divergent nozzle and
the ambient temperature; and (4) the collector temperature is more fluid from the evaporator is entrained. When the inlet
10 8C higher than the generator temperature, then the perfor- temperature of the motive fluid is higher than the designed
mance of the system can be predicted by the program descript temperature, shock wave will happen. With energy loss during the
in Fig. 3. shock wave, the entrainment capacity of the motive fluid after the
shock wave is decreased sharply.
4. Results and discussions The COP of the ERS is shown in Fig. 6, and it has a similar trend
as the entrainment ratio of the ejector because the performance of
4.1. Performance of the ejector and its refrigeration system the system is greatly affected by the entrainment ratio of the
ejector. More refrigerant fluid entrained by the ejector means the
For a given ejector, the performance can be calculated based system supplies more cooling capacity, with a small increase in
on the mathematical model mentioned in Section 3.1. For heat requirement for heating the motive fluid. Hence, the system
validation, the results calculated by the model were compared offers better performance.
with the experimental values and also with the one-dimension Fig. 7 shows the cooling capacity of the designed ejector
model by Huang et al. [16], and with that calculated by CFD under critical condenser pressure. The critical cooling capacity
software package Fluent 6.2 [18]. The deviations are shown in of the ejector increases with increasing generator temperature.
Fig. 4. The results were found to be in good agreement with Under the design condition of generator temperature at 85 8C,
experimental values with deviations no more than 10%, which the cooling capacity reaches maximum. After that, shock wave
means the model is effective for analysis the performance of happens at the exit of the nozzle which leads to energy loss,
the ejector and can be used as basis for performance analysis of consequently, the performance and the cooling capacity of the
the SERS. ERS decrease sharply.

Fig. 5. Entrainment ratio of the designed ejector. Fig. 7. Cooling capacity of the ERS under various generator temperature.
180 J. Guo, H.G. Shen / Energy and Buildings 41 (2009) 175–181

Fig. 11. Variation of COP of the SERS with time.


Fig. 8. Hourly ambient temperature variations in Shanghai (July).

day in July calculated from the model proposed by Liu and Jordan
[19]. Given the performance of the ejector as mentioned above and
the climate conditions as shown in Figs. 8 and 9, the hourly
performance of the ERS and SERS can be obtained (Figs. 10 and 11).
Fig. 10 shows the hourly COP of the ERS with the evaporator
temperature at 8 8C and the condenser temperature varying with
the ambient temperature. Under fixed inlet pressures of motive
fluid and entrained fluid, the mixed fluid is easier to flow through
with higher condenser temperature, therefore, more refrigerant
fluid can be entrained and the entrainment ratio of the ejector
increases, consequently, the cooling capacity and the COP of the
ERS also increase.
Comparing Figs. 8–10, although the solar radiation reaches
maximum at 12:00, the ambient temperature and the entrainment
ratio of the ejector reach maximum at 14:00. It indicates that the
condenser temperature has greater effect on the performance of
the ERS than the generator temperature. As the condenser
temperature not only determines the condenser pressure which
Fig. 9. Hourly solar radiation in Shanghai (July). in turn influences the entrainment ratio and COP of the ERS as
mentioned above, but it also influences the heat required by the
4.2. Performance of the SERS generator. Under a higher condenser temperature, the ejector
entrains more refrigerant and supplies more cooling capacity.
The climate conditions of Shanghai were used for the Furthermore, a higher condenser temperature causes a decrease in
performance prediction of the SERS. Figs. 8 and 9 show the hourly the heat required by the generator when it generates the same
outdoor ambient temperature and total solar radiation on a typical quality and quantity of motive fluid.

Fig. 10. Variation of COP of ERS with time. Fig. 12. Hourly solar fraction.
J. Guo, H.G. Shen / Energy and Buildings 41 (2009) 175–181 181

Considering the efficiency of the solar collector, heat loss of the (3) Compared with traditional compressor based air conditioner,
storage tank and pipes as well as the heat transfer efficiency in the the SERS conserves more than 75% of electric energy when it is
generator, the hourly overall performance of the SERS is as shown used to supply air conditioning during daytime for office
in Fig. 11. From 8:00. to 16:00, the system worked under steady buildings.
performance between 0.43 and 0.53 with cooling capacity of 6 kW. (4) The system offers a good energy conservation method for air
During other times, the solar radiation intensity weakens and conditioning of office buildings.
the ambient temperature drops, therefore, the overall COP of the
system decreases sharply. From the view of this character, the
References
system exerts its best performance when being used in daytime.
Therefore, it’s appropriate for the system to supply air conditioning [1] Srinivasa Murthy, R. Balasubramanian, M.V. Krishna Murthy, Experiments on
for office buildings. vapour jet refrigeration system suitable for solar energy applications, Renewable
The hourly solar fraction of the system is shown in Fig. 12. With Energy 1 (5/6) (1991) 757–768.
[2] M. Sokolov, D. Hershgal, Optimal coupling and feasibility of a solar-powered year-
more solar energy gain from 10:00 to 13:00, the solar fraction round ejector air conditioner, Solar Energy 50 (6) (1993) 507–516.
during this period is more than 1.0, which means no additional [3] M. Sokolov, D. Hershgal, Solar-powered compression-enhanced ejector air con-
electric energy is needed (except that used for the instrument and ditioner, Solar Energy 51 (3) (1993) 183–194.
[4] B. Zhang, S.Q. Shen, Development of solar ejector refrigeration system, in:
circulation pumps) for the system to supply air conditioning. Proceedings of the 1st International Conference on Sustainable Energy Technol-
During other hours at daytime, the solar fraction of the system is ogies, 2002.
between 0.45–0.94 except at 17:00, the solar fraction drops to as [5] K. Chunnanond, S. Aphornratana, Ejectors: applications in refrigeration technol-
ogy, Renewable and Sustainable Energy Reviews 8 (2004) 129–155.
low as 0.15. When the system is equipped in office buildings, and
[6] S. Aphornratana, I.W. Eames, A small capacity steam-ejector refrigerator: experi-
the office time is from 9:00 to 17:00, the average solar fraction of mental investigation of a system using ejector with movable primary nozzle,
the system is 0.82. That is to say, only 18% electric energy is needed International Journal of Refrigeration 20 (5) (1997) 352–358.
[7] I.W. Eames, A.E. Ablwaifa, V. Petrenko, Results of an experimental study of an
to provide the same cooling capacity. Compared with traditional
advanced jet-pump refrigerator operating with R245fa, Applied Thermal Engi-
compressed air conditioning system, the SERS can conserve more neering 27 (2007) 2833–2840.
than 75% of electric energy. [8] A. Selvaraju, A. Mani, Experimental investigation on R134a vapour ejector refrig-
eration system, International Journal of Refrigeration 29 (2006) 1160–1166.
[9] T. Sankarlal, A. Mani, Experimental investigations on ejector refrigeration system
5. Conclusions with ammonia, Renewable Energy 32 (2007) 1403–1413.
[10] B.J. Huang, V.A. Petrenko, I.Y.A. Samofatov, N.A. Shchetinina, Collector selection
In this study, the lumped method combined with dynamic for solar ejector cooling system, Solar Energy 71 (4) (2001) 269–274.
[11] A. Selvaraju, A. Mani, Analysis of an ejector with environment friendly refriger-
model for performance prediction of solar-driven ejector refrig- ants, Applied Thermal Engineering 24 (2004) 827–838.
eration system for providing air conditioning to office buildings [12] E.D. Rogdakis, G.K. Alexis, Design and parametric investigation of an ejector in an
was investigated. The results of the mathematical simulation have air-conditioning system, Applied Thermal Engineering 20 (2000) 213–226.
[13] A. Arbel, M. Sokolov, Rvisiting solar-powered ejector air conditioner—the greener
demonstrated that the solar-driven ejector refrigeration system the better, Solar Energy 77 (2004) 57–66.
can be designed to meet the cooling requirements of air [14] X.J. Zhang, R.Z. Wang, A new combined adsorption-ejector refrigeration and
conditioning for office buildings. The following conclusions were heating hybrid system powered by solar energy, Applied Thermal Engineering
22 (2002) 1245–1258.
obtained:
[15] J.L. Yu, Y.F. Ren, H. Chen, Y.Z. Li, Applying mechanical subcooling to ejector
refrigeration cycle for improving the coefficient of performance, Energy Conver-
(1) For the studied case, the condenser temperature influences sion and Management 48 (2007) 1193–1199.
[16] B.J. Huang, J.M. Chang, C.P. Wang, V.A. Petrenko, A 1-D analysis of ejector
more on the performance of the SERS than the generator
performance, International Journal of Refrigeration 22 (1999) 354–364.
temperature. [17] NIST Standard Reference Database 23, NIST Thermodynamics and Transport
(2) From 9:00 to 17:00, on typical clear sky days, the average COP Properties of Refrigerants and Refrigerant Mixtures, REFPROP, Version 6.01, 1980.
of the system is 0.48 with most of the daytime remaining [18] E. Rusly, Ejector cooling with reference to combined ejector-vapour compression
system, Ph.D. Thesis, University of Melbourne, 2004.
steady between 0.43–0.53, except at 17:00, when it drops as [19] Y.H. Benjamin Liu, C. Richard Jordan, The interrelationship and characteristic dis-
low as 0.29. The average solar fraction is 0.82. tribution of direct, diffuse and total solar radiation, Solar Energy 4 (3) (1960) 1–19.

You might also like