2 Installation
I/O Configuration

Relay Mounting To flush mount the SEL-751A in a panel, cut a rectangular hole with the
dimensions shown in Figure 2.1. Use the supplied front-panel gasket for
protection against dust and water ingress into the panel (IP65). For extremely
dusty environments, use the optional IP54-rated terminal dust-protection
assembly (SEL Part #915900170). The 10°C temperature derating applies to
the temperature specifications of the relay.

7.36
(187.0)

5.47
(139.0)

i9089b
Figure 2.1 Relay Panel-Mount Dimensions

Refer to Section 1: Introduction and Specifications, Models, Options, and


Accessories for information on mounting accessories.

I/O Configuration
Your SEL-751A offers flexibility in tailoring I/O to your specific application.
In total, the SEL-751A has six rear-panel slots, labeled as Slots A, B, C, D, E,
and Z. Slots A, B, and Z are base unit slots, each associated with a specific
function. Optional digital/analog I/O, communications, RTD, and voltage
cards are available for the SEL-751A. Figure 2.2 shows the slot allocations for
the cards.
Because installations differ substantially, the SEL-751A offers a variety of
card configurations to provide options for the many diverse applications.
Choose the combination of option cards most suited for your application from
the following selection.