Professional Documents
Culture Documents
01-07 Equipment Support
01-07 Equipment Support
7 Equipment Support
7U
Table 7-1 lists the technical specifications of the APM30H outdoor cabinet.
Item Specifications
Table 7-2 lists the technical specifications of the IMB network cabinet.
Table 7-3 lists the technical specifications of the 19-inch open rack.
Available space 83 SU
The R01S100 outdoor cabinet uses a wall-mounted heat exchanger to passively dissipate heat.
In high-temperature (higher than 45°C) areas, you can install enhanced heat dissipation
modules on the outdoor cabinet to improve its heat dissipation capability.
The R01S100 outdoor cabinet provides a 4 U installation space, with the inner 2 U for the
power distribution box and power system and the outer 2 U for the NE. Figure 7-8 shows the
internal structure of the R01S100 outdoor cabinet.
Enhanced heat
dissipation module
Installation space
Battery compartment
Table 7-5 lists the technical specifications of the R01S100 outdoor cabinet.
Cabinet dimensions (with the 1113 mm (H) x 250 mm (D) x 670 mm (W)
enhanced heat dissipation
module and battery
compartment)
Item Specification
The R01S200 outdoor cabinet uses a wall-mounted heat exchanger to passively dissipate heat.
In high-temperature (higher than 40 ºC) areas, you can install enhanced heat dissipation
modules on the outdoor cabinet to improve its heat dissipation capability.
The R01S200 outdoor cabinet provides a 6 U installation space, with the right 2 U for the
power distribution box and power system and the left 2 U for the NE. Figure 7-10 shows the
internal structure of the R01S200 outdoor cabinet.
Enhanced heat
dissipation
module
Installation
space
Battery
compartment
Table 7-6 lists the technical specifications of the R01S200 outdoor cabinet.
Cabinet dimensions (with the 1200 mm (H) x 350 mm (D) x 750 mm (W)
enhanced heat dissipation
module and battery
compartment)
Item Specification
Appearance
Figure 7-11 and Table 7-7 show the appearance and structure of an ETP4830-4815AF,
respectively.
Interfaces on the monitoring module are reserved temporarily. Do not use these interfaces.
Otherwise, the power system may be reset or damaged.
Monitoring module Detects the status of the power system and storage batteries.
Two RS232/RS485 communication interfaces and one DB50
interface are reserved on the monitoring module.
Indicators
Indicators for the rectifier and monitoring modules are present on the front panel of the
ETP4830-4815AF. Table 7-8 and Table 7-9 list the indications of indicators for the rectifier
and monitoring modules respectively.
On 2s and off 2s The communication between the rectifier and the SMU is
interrupted.
Buttons
Table 7-10 describes the buttons on the panel of the monitoring module.
Note:
l The standby screen is displayed and the LCD screen becomes dark if you do not press
any button for 5 minutes.
l You need to log in again to enter the control and setting menus if you do not press any
button for 8 minutes.
Interfaces
Table 7-11 lists types and usage of the interfaces on the front panel of the ETP4830-4815AF.
Table 7-12 Relationships of the load output interfaces, interface for connecting to the storage
batteries, and fuses
Technical Specifications
Table 7-13 lists the technical specifications of the ETP4830-4815AF.
Operating 5%-95%
humidity
Altitude 0-4000 m
When the altitude ranges from 2000 m to 4000 m, the
operating temperature decreases by 1ºC for each additional
200 m.
Maximum 94%
efficiency of
the rectifier
module
Capacity 40 Ah
Number of 4
batteries
Regulated ≤ ±0.6%
voltage
precision
Appearance
Figure 7-12 shows the appearance and structure of an ETP4830-B1A2.
Rectifier module
Indicators
Indicators for the rectifier and monitoring modules are present on the front panel of the
ETP4830-B1A2. Table 7-14 lists the indications of indicators for the rectifier modules
respectively.
Table 7-15 Interfaces and air breakers on the front panel of the ETP4830-B1A2
LOAD1 1 Interface Output interface for load 1 LOAD1 and LOAD2 provide DC
power for two PIUs. For how to
LOAD2 1 Interface Output interface for load 2 connect the load interfaces to the
PIUs.
Figure 7-13 Relationships of the AC input interfaces, load output interfaces, and air breakers
RTN+
Load2 -48V AC INPUT2
Technical Specifications
Table 7-16 lists the technical specifications of the ETP4830-B1A2.
Maximum 4.9 A
current
DC Output lines 2
output
Default output -53.5 V DC
voltage
Item Specifications
Appearance
Figure 7-14 shows the appearance of a 27S48D power system.
Functions
The 27S48D power system accepts power in the range of 19 V to 30 V, and outputs -53.5 V
rated voltage and 7 A rated current.
In terms of electrical performance and structure, the 27S48D power system is divided into two
independent -53.5 V/5.6 A power modules. They are separated using an output diode and
installed in the same cabinet. Their currents are combined into a 7 A one through power
distribution, and the 7 A current is supplied to equipment. The 27S48D power system
provides functions such as short-circuit protection, overcurrent protection, output overvoltage
protection, and overheat protection.
Indicator
Table 7-17 lists the meaning of each 27S48D power indicator status.
Interface
Table 7-18 lists the types and functions of 27S48D power interfaces.
Technical Specifications
Table 7-19 lists the technical specifications of the 27S48D power system.
Item Value
Maximum input 20 A
current
Output current 7A
Weight < 7 kg
Appearance
Figure 7-15 shows the appearance of the HW-100-48AC14D-1 power system.
Functions
The HW-100-48AC14D-1 power system supports AC power ranging from 90 V to 264 V, and
outputs -48 V DC power in natural heat dissipation mode. The output power is 100 W. This
power system supports protection against output overcurrent, output undervoltage, output
short circuit, and overtemperature.
Technical Specifications
Table 7-20 provides the technical specifications of the HW-100-48AC14D-1 power system.
Maximum input 2A
current
Item Specifications
Dimensions (H x W x D) 40 mm x 171 mm x 72 mm
Weight < 1 kg
Appearance
Figure 7-16 shows the appearance of a lead-acid battery.
NOTE
The appearance, dimensions, and weight of lead-acid batteries are provided only for reference and those
of the delivered batteries prevail.
Technical Specifications
Table 7-21 shows the technical specifications of the lead-acid battery.
Weight ≤ 15 kg
GPS Antenna
NOTE
The appearance and technical specifications of a GPS antenna vary according to vendors.
A GPS antenna is used to receive satellite signals from GPS. Figure 7-17 shows the
appearance of a GPS antenna.
Weight 0.4 kg
Gain 38dBi
The appearance and technical specifications of a GPS surge protector vary according to vendors.
A GPS surge protector is used to protect devices from overcurrent or overvoltage due to
inducting lightning strokes introduced by feeders. Figure 7-18 shows the appearance of a
GPS surge protector.
Lightning current 20 KA
Protection voltage 20 V
Characteristic impedance 20 KA