Professional Documents
Culture Documents
Introduction
Design professionals can use this document to learn how to conduct the structural design of a
post-frame building system for lateral loading. Architects or engineers can use this document to
walk through the unique features of diaphragm design of post-frame building systems and the
detailed engineering calculations for the structural design of a typical post-frame building.
This document — Part 1: Lateral Design of a 72 ft. x 120 ft. x 16 ft Post-Frame Building, Wind-
Governed Design Example — contains the engineering design procedures and detailed
calculations to conduct the structural design of a single story post-frame building located on a
site where lateral design wind loads exceed lateral design seismic loads. It begins with a general
description of the post-frame building to be designed, followed by detailed descriptions and
calculations of design loads, roof diaphragm panel in-plane shear strength and stiffness,
shearwall panel in-plane shear strength and stiffness, the portion of the lateral wind load carried
to ground by the post-frame, and the portion carried to ground by the roof diaphragm and
shearwalls using an on-line computer program, the Diaphragm and Frame Interaction (DAFI)
Calculator.
The structure has a 72 ft. clear span, is 120 ft. long, and has a 16 ft. eave height. The building
has post-frames spaced 8 ft. on center along both sidewalls. Each post frame consists of wood
sidewall columns attached directly to engineered, 2x metal-plate connected wood gable trusses
with flat lower chords, and two equally sloped upper chords. The roof and walls are sheathed
with 29 ga corrugated steel sheathing. Preservative treated laminated wood sidewall columns
embedded directly into the ground provide the building foundation.
The design example continues with the structural design of the unique structural elements of the
post-frame system, including the nail-laminated wood sidewall columns, the shallow embedded
post foundation system, the wood sidewall girts, and the wood roof purlins. The document also
includes the detailed procedures and calculations to determine the adequacy of the roof
diaphragm panels and all the shearwall panels to carry the design in-plane shear loads.
The key structural connections required to ensure continuous load paths to ground are identified
and detailed procedures and calculations for designing each of the key connections are provided.
Finally, the document details the lateral and longitudinal bracing requirements for the building
system.
The design example follows provisions of the 2009 International Building Code, the 2005
National Design Specification for Wood Construction, ASCE 7-05: Minimum Design Loads for
Buildings and Other Structures, and the Post-Frame Building Design Manual. The appropriate
sections of these design references are cited throughout the design example.
This design tool was developed by Timber Tech Engineering, Inc. located in Kouts, Indiana.
Timber Tech Engineering’s assistance in developing the calculations and solution presentation is
hereby acknowledged. The truss design was provided by Lumber Specialties of Dyersville, Iowa
and their contribution is also acknowledged.
This example is divided into two parts. Part 1 is written as a teaching tool for designers not
familiar with post-frame building design in that it explains each step of the lateral design process
for a post-frame building and summarizes the results of the calculations. Part 2 is a
comprehensive calculation package that gives the background design calculations for each step
and is a much longer document. The reader is referred to the Part 2 comprehensive calculation
package through hyperlinks, placed at critical locations throughout the report, if more
information is desired. Both Part 1 and Part 2 can be used as stand alone documents.
This is a design example in which a 72' wide x 120' long x 16' high Post-Frame building's lateral
force resisting system is analyzed and designed for wind and seismic loading. The roof is gable
framed with a 3.5:12 pitch on each side. The building is located in Dane County, Wisconsin
where, surrounded by closely spaced wind obstructions, it qualifies for surface roughness
category B as defined in ASCE 7-05. This commercial building is comprised of the following
structural members:
Figure 1A shows the exterior elevations, and Figure 1B is a sketch of the plan view of the
building. There are (4) 36"x60" windows equally spaced on one endwall and (1) 24'Wx14'H
overhead door in the opposite endwall; there are (2) 36"x60" windows and (2) 16'Wx14'H
overhead doors and (1) 36"x80" man door in the rear sidewall and (2) 36"x80" man doors and (2)
16'Wx14'H overhead doors in the front sidewall. The exterior walls and roof are sheathed with
Grandrib 3, 29 gage structural metal sheathing manufactured by Fabral. On the interior, the
walls and ceiling are also sheathed with Grandrib 3, 29 gage structural metal sheathing by Fabral
(see Figure 3A and 3B for panel profile and fastener pattern, test panel size and configuration,
and in-plane shear strength and stiffness data). The ceiling is framed with 2x4 #2 SYP ceiling
joists 24" o/c between the trusses. The ceiling sheathing and roof sheathing have the same
orientation. The building is heated and insulated with R-19 insulation in walls and R-30
insulation in the ceiling. There is a 12" roof overhang on the gable ends and 24" overhang on the
sidewalls.
The design dead loads, snow loads, minimum roof live loads, wind loads and seismic loads are
all taken from ASCE 7-05, “Minimum Design Loads for Buildings and Other Structures” per
IBC 2009. The design loads and the ASCE 7-05 section reference for each are given in Table 1.
The design roof dead load is 4 psf and the design ceiling dead load is 5 psf. The dead loads of
the different materials for the roof plane are listed based on surface area and then converted to
the horizontal projection to give the top chord dead load.
The Design Main Wind Force Resisting System (MWFRS) and Components and Cladding
(C&C) wind pressures and suctions were calculated for positive, negative and zero internal
pressure conditions. Footnote 6 of Figure 6-10 in ASCE 7-05 specifies that if the roof wind
loads act to decrease the magnitude of the wall framing shear, that maximum post shear shall be
determined by neglecting the lateral forces acting on the roof. The controlling lateral wind force
to be resisted by the MWFRS was found by considering wind applied to roof and walls, wind
applied to walls only, and 10 psf wind pressure applied to the vertical projection. The lateral
force from seismic load was also calculated and compared to the wind force. The response
modification factor, R, and deflection amplification factor, Cd, were chosen from ASCE 7-05
Table 12.2-1. The comparison between wind and seismic was performed for both strength and
serviceability criterion using forces generated from the critical load combinations. It was found
that wind loading controls for strength design and serviceability requirements. The allowable
lateral deflection at the eave was found by taking the eave height divided by 120 (L/120 limit).
The actual deflection comes from the DAFI analysis in the Diaphragm Design section.
ASCE 7-05, Section 2.4.1 lists six design load combinations for allowable strength design. Of
these the controlling combinations for this building design are:
The 10 psf minimum wind load applied to the vertical projection (per ASCE 7-05 Section
6.1.4.1) controls the design of the MWFRS for this building as shown in Part 2 Section 2.5.4.
However, many individual building components are controlled by wind pressures derived from
coefficients. The purpose of this design example is to illustrate how wind pressures are applied
to each individual building surface, how they translate into shear and bending forces in the
diaphragm, and what affect these pressures have on individual building components. This
example will present the lateral design process for a post-frame building using wind pressures
and suctions from coefficients, and the effects of the 10 psf minimum wind load on the MWFRS
will be shown separately in Part 2 Appendix E. The MWFRS is a combination of the roof
diaphragm, shearwalls, and the post-frame. Part 2 Appendix E shows the adequacy of the roof
diaphragm, shearwalls, and post-frame for the 10 psf minimum wind load requirement.
The roof diaphragm, ceiling diaphragm and shearwalls (including inside and outside faces of
endwalls and sidewalls) will be sheathed with 29 gage Fabral Grandrib 3 structural steel
sheathing panels with the profile and fastener pattern shown in Figure 3A.
Figure 3A. Sheathing profiles and fastener patterns for the roof and wall panels
The primary dimensions of the diaphragm test panel used to determine the in-plane shear
strength and stiffness are shown in Figure 3B. The overall test panel dimensions are a = 9 ft and
b = 12 ft. The panel fastener schedule is (1) #10-1 ½ inch long screw at each
corrugation/framing intersection. The exception is that (2) screws are used per connection along
the diaphragm boundary. Purlins (2x4) on edge and spaced 2 ft. on center are attached to the
The in-plane structural properties of the Grandrib 3 test panels as provided in Table 6.1 (Test
Assembly #6) of the "Post-Frame Building Design Manual" (PFBDM) by the National Frame
Building Association (NFBA) are shown below.
Figure 3B. Test panel arrangement for determining in-plane shear strength and
stiffness of diaphragm test panels.
The maximum in-plane shear force cannot exceed the allowable unit shear strength, va,
multiplied by the diaphragm length. The PFBDM is silent on the controlling failure mode for the
different test series' conducted. If the failure was in the wood portion of the test assembly, a load
duration factor of 1.6 could be applied; however, if the failure was in the steel panels, then no
increase can be taken. We will use the conservative approach and assume steel failure.
The total in-plane shear strength of an individual diaphragm is calculated by multiplying the
allowable design shear strength, va, by the slope length of the diaphragm. The horizontal shear
stiffness of an individual diaphragm, ch, is obtained by adjusting the model diaphragm in-plane
shear stiffness, c, for the actual building size and roof slope as described in Section 6.4 of the
PFBDM and as shown in the following calculations.
bh ,1
c h ,1 roof c h , 2 roof G cos
s
a
G c
b
lb
c 2920
in
a 9 ft
b 12 ft
lb 9 ft lb
G 2920 2190
in 12 ft in
72 ft
bh ,1 2 ft 38 ft
2
s 8 ft
lb
c h ,1 c h , 2 2190 cos16.26 38 ft 9986 lb
in 8 ft in
lb
c h ,3 ceiling 2190 cos 0 72 ft 19710 lb
in 8 ft in
The total horizontal shear stiffness, Ch, of the roof assembly is calculated by summing the
horizontal shear stiffness values of the individual roof diaphragms including both roof slopes, ch,1
and ch,2 as well as the ceiling, ch,3.
The stiffness of the bare frame, k, is the ratio of an applied horizontal eave load divided by the
resulting calculated horizontal eave deflection. A computer analog of the frame consisting of
two posts and the truss has been used to calculate this term. The post to soil interface is assumed
to be a non-constrained post as defined in the PFBDM, Page 8-2; the structural analog of this
interface is shown in Figure 4A on page 22.
p lbs
k 133.3
in
P horizontal load
frame displacement
The endwall stiffness, ke, is calculated by summing the horizontal shear stiffness of the endwall
diaphragm and the sum of the bending stiffness of all the endwall posts. The horizontal shear
stiffness of the endwall diaphragm is deduced from the test panel shear stiffness using the same
equations as used to determine the roof diaphragm panel. The interior liner attached to the
endwalls is constructed the same as the exterior siding and is included by doubling the endwall
sheathing shear stiffness.
The eave load, Pi, used in this analysis is the resultant lateral load from the controlling
combination of design loads acting over the tributary area of the eave, and is applied as a
concentrated load at the eave of each frame. The eave load is calculated by using either Frame-
Base Fixity Factors or Plane-Frame Structural Analysis.
The standard method of fixity factors typically assumes that a post is simply supported with zero
rotational resistance at ground level, or is fully fixed with zero rotation at ground level. Most
often neither of these assumptions is completely accurate. In the case of a non-constrained post
foundation, the top horizontal support of the foundation system is located a distance below
ground level. This means that there are some lateral and rotational deflections at the ground line.
It was found that the wall wind loads without the roof wind loads (ASCE 7-05, Fig 6-10, Note
#6) control the eave load calculation.
Pi shr q wr q lr hw f q ww q lw
f pin 0.5
f fixed 0.375
f new 0.42
Pi 8 ft 10.5 ft 0 psf 0 psf 16 ft 0.42 7.6 psf 2.4 psf 538lbs
DAFI (Diaphragm and Frame Interaction) is a computer program for calculating the distribution
of horizontal loads among the individual post-frames and roof diaphragm sections of a building.
It can be used to analyze diaphragm action in buildings in which bay spacings vary, the stiffness
of individual post-frames differ, endwalls are not assumed infinitely rigid, and/or the stiffness of
individual diaphragms are not the same. A Windows version of this program is available as a
free download from the National Frame Building Association website (nfba.org). It allows data
to be entered using a special screen editor. The data can be saved to and later recalled from an
input data file. For the example building and design loads, the DAFI inputs are:
Number of Bays = 15
Roof Diaphragm Shear Stiffness = 39683 lbf/in
Endwall 1 Shear Stiffness = 17117 lbf/in
Endwall 2 Shear Stiffness = 13693 lbf/in
Interior Frame Stiffness = 133.3 lbf/in
Eave Load on an Interior Frame = 538 lbf
Input this information in the DAFI ‘Default Values’ screen. Use the shear stiffness for
Endwall 1 as the default value and then adjust the shear stiffness for Endwall 2 within
the ‘Specific Values’ table.
Bay Number Diaphragm Stiffness Frame Number Frame Stiffness Eave Load
1 39683 1 17117 269
2 39683 2 133.3 538
3 39683 3 133.3 538
4 39683 4 133.3 538
5 39683 5 133.3 538
6 39683 6 133.3 538
7 39683 7 133.3 538
8 39683 8 133.3 538
9 39683 9 133.3 538
10 39683 10 133.3 538
11 39683 11 133.3 538
12 39683 12 133.3 538
13 39683 13 133.3 538
14 39683 14 133.3 538
15 39683 15 133.3 538
16 13693 269
The DAFI outputs are found on the ‘Frame Analysis’ and Diaphragm Analysis’ tabs in
the program. These tables are shown here and interpreted in the next section.
From the DAFI Frame Analysis screen, frame 9 is the most highly loaded frame. Frame 9 carries
76 lbs (Figure 3C), or 14% of the applied eave load. The horizontal deflection at the eave of
frame 9 is 0.57 inches.
From the DAFI Diaphragm Analysis screen, diaphragm 1 has the highest shear load. This shear load
of 3432 pounds plus the eave load of 269 pounds (shown on the Specific Values tab in DAFI) makes up
the total load resisted by Endwall 1 (DAFI Frame 1). Similarly, the total load resisted by Endwall 2
(3487 lbs) is the sum of the applicable shear load (3218 lbs) and eave load (269 lbs) from the DAFI
analysis.
The endwalls are sheathed inside and out with structural steel panels and the allowable shear
strength, va, is 110 lb/ft for each layer, 220 lb/ft total. These steel panels are the primary
component of the lateral force resisting system for this building. The panels are fastened to 2x4
girts with #10x1" screws 6" o/c at edges and 12" o/c at all intermediate framing. Though the
testing was done with purlins placed on edge, it is a reasonable assumption that the purlins with
flat orientation will yield equal or better results.
The shear load in the each endwall is resisted by the two layers of structural steel panels and the
wood columns in the endwall. The amount of load carried by each component can be calculated
according to the stiffness of each component. It was found that the exterior and interior panels
each carry 48% of the load and the wood columns carry 4%. The calculations in Part 2 show that
The shear strength of the steel panels is sufficient, no additional wood or metal strap
bracing is required.
The construction of the sidewall is identical to that of the endwall. Thus, the shear strength of the
sidewall is the same as the endwall, 220 lb/ft. The controlling load combination for wind loads
parallel to ridge is D+W, where windward and leeward pressures are applied to the tributary area
of the endwall. For simplicity, the columns are assumed to be fully rigid at ground level with a
fixity factor of 3/8. This means that 5/8 of the wind pressure on the endwalls will be taken
directly into the foundation by the columns. The sidewall shear forces are based upon wind
acting parallel with the ridge and the shear load on the sidewall is calculated by using 3/8 of the
wall height plus the roof gable. The sidewall shear equals 51 lb/ft:
Typically the endwalls in a post-frame building are the controlling shear walls. There are cases,
however, when sidewalls are the critical shear walls, especially in wide buildings that are short in
length. In those situations a more thorough analysis is required, in which a roof and sidewall
stiffness and possibly torsional effects on the overall building envelope are considered. An
analytical model of each column height with proper base conditions may also be required to
calculate loads on the diaphragm more accurately.
The roof and ceiling are also sheathed with structural steel panels. The panels are fastened to
2x4 purlins with #10x1" screws 6" o/c at edges and 12" o/c at all intermediate framing. The
shear load in the diaphragm is resisted by the one layer of structural steel panels on the sloping
roof plane, and one layer on the flat ceiling plane. The amount of load carried by each
component can be calculated according to the stiffness of each component as shown below. It
was found that the roof and ceiling diaphragms each carry 50% of the load.
The maximum unit shear load for roof or ceiling panels is 24 lb/ft:
Link to Part 2 Section 3.10 Roof Diaphragm Shear Strength Calculations >
The roof diaphragm acts like a deep beam where the ends of the beam are assumed to be fixed.
The diaphragm of this building consists of two individual roof diaphragms, one on each side of
the ridge, and one ceiling diaphragm. The bending forces in each diaphragm are resisted by roof
purlins and ceiling joists. Because only the edge purlins and ceiling joists are fastened together
in this building to provide continuous tensile resistance to tension chord forces, it is
conservatively assumed that the intermediate purlins and ceiling joists provide zero contribution
to the diaphragm bending resistance (Design equations for inclusion of all purlins are provided in
the PFBDM.). The individual (sixteen ft long typical) edge purlin members are fastened together
at splices with a single HTP37Z Simpson plate fastened to the side with 10dx1-1/2 nails
(tabulated capacity = 1600 lbs); the ceiling joists are spliced together with a single MSTA21
Simpson strap, fastened to the bottom edge with 10dx3" nails (tabulated capacity = 1505). The
design eave load (67.3 lbs/ft) is applied to the diaphragm at the eave, and redistributed to
individual diaphragms according to their stiffness. It was found that the individual roof
diaphragms each take 25% of the load, and the ceiling diaphragm carries the remaining 50%.
For simplicity, the load resistance contribution of the frame is ignored. Using these assumptions
the maximum chord force in the edge purlins of each diaphragm panel are:
It should be noted that typical roof diaphragm deflection consists of bending deflection, shear
deflection of sheathing panel, deflection due to nail slip, and deflection due to slip in chord
connection splices. Because the diaphragm stiffness in this example is based on a sample test, it
can be assumed that all of these deflection contributors, with exception of the deflection due to
slip in chord connection splices, are accounted for. It is further assumed that the deflection due
to slip in chord connection splices is minimal and is an insignificant contributor to the overall
diaphragm deflection.
Link to Part 2 Section 3.11 Roof Diaphragm Chord Force Calculations >
Figure 4A shows the structural analog of the post-frame consisting of the truss, a windward
column and a leeward column. The post to soil interface is modeled with a pin and a roller, and
all the loads are shown including the horizontal restraining force, Q = 462 lbs (From Section
3.7). The loads shown in Figure 4A are individual load cases which will be used in the ASCE 7-
05 load combinations. Wind loading on the roof is not shown because, in this example building,
it tends reduce the total lateral shear load. Visual Analysis 7.0 by IES, Inc. was used for the
column design.
From the Visual Analysis output, we are able to determine that a 3 ply 2x8 #1 SYP nail-
laminated (nail-lam) post is adequate for the applied loads (See Visual Analysis Report in Part 2
Appendix A). All applicable load combinations from ASCE 7-05 for combined axial and
bending stresses were checked, the controlling combination was D + 0.75(S+W), and combined
stress index (unity check) was 0.5. Nail-lam posts were chosen because they are pressure
preservative treated only at the embedded end, they can be easily notched at the top for a good
truss connection, and they are readily available in 3 ply 2x6, 3 ply 2x8, 4 ply 2x6 and 4 ply 2x8
sizes. The post design values (Fb = 1725 psi, Fc = 1650 psi, E = 1.7E6 psi, bxd = 4.31 x 7.19 in2,
SX = 37.11 in3, and IX = 133.36 in4) used in this design assume that the splice between the treated
and untreated plies is made with a structural finger joint (certified by a third party inspection
agency). If nail-lam columns with butt joints at the splice are used, they should be designed as
per ANSI/ASAE EP 559 using reduced strength and stiffness in the butt-spliced joint region.
The maximum post moment, Ma, maximum post shear, Vmax, and ground line shear, Va, from the
Visual Analysis computer program are:
Deflection Results
The maximum horizontal displacement from the DAFI output is 0.57 inches at frame 9.
Allowable displacement as per Table 1604.3 from IBC 2009 is L/120 or 1.6 inches for a 16 ft.
high wall with flexible finishes.
The post foundation is designed as a non-constrained post with a partial concrete collar located at
the bottom of the post. The post foundation depth calculation is iterative in that the designer
must assume a depth and check the outcome using design equations. We will assume 4 ft.
embedment below grade and a 24 inch high concrete collar attached to the post at the bottom
(Figure 5A). Please note, a collar that is less than 24 inches high is often satisfactory and may be
so for this example. The axial, shear and moment reactions on the foundation are imposed from
the column at ground level. The allowable lateral bearing soil pressure, S', is assumed to be 200
psf/ft of depth, and the initial allowable vertical bearing soil pressure is assumed to be 2000 psf
(ANSI/ASAE EP486.1, Table 1 for sandy gravel and/or gravel (GW and GP) soils). The
governing design equations for lateral design of the non-constrained case with a concrete collar
at the bottom are from Section 6.5.2 in ANSI/ ASAE EP 486. The adjusted allowable vertical
soil pressures along with controlling load combinations for gravity, lateral and uplift loads, and
other calculations are provided in Part 2 Appendix B.
Soil bearing resistance = 2000[1 + 0.2(ftg depth ft - 1ft) + 0.2(ftg width ft - 1ft)]
= 2000[1 + 0.2(4.67ft - 1ft) + 0.2(2ft - 1ft)] = 3868 psf
The lateral design criteria for shear and moment resistance, from ANSI/ASAE EP 486, Section
6.5.2 are, respectively,
Check both equations for an embedment depth of 4.0 ft to see if it provides adequate lateral load
resistance:
Va Vr
602 200(0.51)/2{2(4.0)3/[(0.68)(4.0)] – 3(4.0)2}
Vad + Ma Mr
602(4.0) + 1850 =4258 = -[200(0.51)/4]{4.04/[(0.68)(4.0)] – 2(4.03)} - [200(2.0
-0.51)/4]{[4.04 – 3(4.0)(2.03) + 3(2.04)]/[0.68(4.0)] –
2(4.03) - 6(4.0)(2.02) + 4(2.03)} = 9471
4 ft post embedment OK
The required embedment depth is the larger of the required depths from both the shear and
moment criterion. Both design equations require an iterative solution. These iterative
calculations, performed in a spreadsheet shown in Part 2 Appendix B, show that an embedment
depth of 3.27 ft provides adequate lateral load resistance. We will keep the embedment depth of
4 ft because it is widely accepted in the industry. The designer could decide to use a more
shallow embedment depth provided the lateral load criterion is satisfied and minimum frost
depth conditions for the building site are met.
U = g(MF + wsVs)
Use an 8 in. x 24 in. diameter footing with a 24 in. high x 24 in. diameter concrete collar and 4
ft. post embedment.
Purlins are positioned on edge on top of top chord of truss and typically span over two spans for
the total length of 16 ft. Due to the sloping roof, the gravity loads are not aligned with the strong
axis of the purlin. At the same time, the purlin can only move about its strong axis as the
movement about the weak axis is restricted by the attached rigid roof panels. Thus, the gravity
loads on the purlin should be broken down into strong axis and weak axis components, or 'y' and
'x' components on the sloping coordinate system. Purlins must be designed for three wind load
areas: interior purlins, edge purlins, and corner purlins. The design calculations are provided in
Part 2 Appendix C.
2x4 #2 S. Pine on edge @ 24" on center except 16" on center in unbalanced snow area 10.5 ft.
each side of ridge.
The maximum CSI value for the interior purlins is 0.97 for 2x4 purlins spaced 16 inches on
center for the D + Sunbalanced load combination. The maximum CSI value for the edge and corner
purlins spaced 24 inches on center for the load combinations with dead and wind loading is 0.44.
Girts must be designed for two wind load areas: interior girts and edge girts. All analyses assume
the purlins are loaded flatwise and are spaced 24 inches on center. The calculations show that
No. 2 SYP 2x4 girts spaced 24 inches on center are satisfactory in all wall sections. The
maximum CSI value for girts located at the edge is 0.83. The design calculations are provided in
Appendix C.
2x4 #2 S. Pine flat against posts @ 24" on center continuous over two spans.
Only connections critical to the lateral force resisting system are included in this section.
Connection details are presented in Section 9: Design Summary. The key connections presented,
in order, and identified in Figure 7A are:
Trusses are placed in a pocket created by notching the center lamination at top of post. The
exterior laminations are then extended to the top of top chord of truss, and fastened to truss with
(5) 16d common wire nails on each side. This connection is designed to resist vertical and
horizontal shear loads. The vertical shear load, or load from truss uplift, can be calculated using
tributary areas and roof wind pressures, or can be provided by a truss designer. In this example
the uplift loads are calculated using tributary areas and wind pressures.
The horizontal shear load at top of post can be approximated using tributary area and wind
pressures, which is a product of (fixity factor)(column height)(column spacing)(controlling wind
pressure), assuming that the column is pinned or fixed at bottom (grade level) and has a
horizontal roller support at top. The fixity factor is 0.5 for a pinned base and 0.375 for a fixed
base. For non-constrained columns that fall between fixed and pinned, see discussion in Section
3.4. A more accurate horizontal shear load can be determined by modeling the critical frame, the
frame closest to the more rigid endwall, in a computer program, or by using DAFI result outputs.
This example utilizes results from DAFI.
The truss is fastened to a glulam header over the 16 ft. sidewall door opening with (2) H10A
Simpson hurricane ties, one tie on each side of beam. The specific gravities of truss and beam
are assumed to be 0.55.
The shear load from the roof diaphragm is transferred to the endwall truss and then to wall
sheathing. This load path does not directly rely on the truss to post connection. The shear forces
from the ceiling diaphragm, however, are transferred to the endwall posts first and then to girts
and sheathing. There are 10 posts in endwall 1, the endwall with largest shear loads, to which
the ceiling ledger is fastened. The endwall ceiling ledger is fastened to each post with (4) 16d
nails.
There is a 2x8 #2 SYP skirt board on the exterior side of the end wall, and a 2x4 #2 SYP bottom
girt on the interior side of the end wall. The skirt board and bottom girt to post connection is the
last connection in the load path of the lateral force resisting system before the lateral loads are
transferred to the ground. The skirt board and the bottom girt are fastened to each post with (4)
16d galvanized common wire nails.
The edge purlins serve as tension and compression chords of the roof diaphragm. In order to
provide continuity in tensile resistance in the tension chord of the diaphragm, the purlins must be
fastened together at each splice. In this design an HTP37Z Simpson strap is used at each purlin
splice (the designer may choose to try a 2x4 splice block with nailed connection as an
alternative). The edge purlin must also be fastened to the endwall truss to transfer loads into
sidewall sheathing. To accommodate this connection, a 2x8x10 inch wood block is attached to
truss and purlin as shown in the Connection Detail (Edge Purlin to Truss Connection) in Section
9 (the designer may choose to use a Simpson hanger or strap as an alternative). To provide
adequate withdrawal capacity, the block is attached to truss with (8) #8x3" wood screws, four (4)
screws at top of top chord of truss and four (4) screws at bottom of top chord. The purlin is
fastened to the block with (5) 16d nails. This connection must be at all edge purlins for each roof
diaphragm; there are the total of four (4) purlins and eight (8) such connections in the building.
The edge ceiling joists serve as tension and compression chords of the ceiling diaphragm. In
order to provide continuity in tensile resistance in the tension chord of the diaphragm, the edge
ceiling joists must be fastened together at each splice. In this design an MSTA21 Simpson strap
is used at each purlin splice. The edge ceiling joists must also be fastened to corner posts to
transfer loads into sidewall sheathing. This connection is made with (6) 16d nails.
Each post is connected below grade to a concrete collar (backfill) with (1) #4 x 16 inch hot
dipped galvanized rebar. This connection is checked using the provisions of the 2005 National
Design Specification for Wood Construction (NDS) by AF&PA for a 1/2 inch diameter bolt in
high moisture conditions.
The design loads for each of cases 7.1 to 7.8 are given in the immediately following table. These
design loads are taken from the load calculations in Section 2 and the diaphragm analysis results
in Section 3.
This design example is focused on resistance to lateral loads and the connections related to these
loads only; however, some other important connections that should be addressed in a complete
building design include:
Guidelines for handling, bracing and installing metal plate connected wood trusses are contained
in the Building Component Safety Information (BCSI) booklet published jointly by TPI and
WTCA. Also work is currently underway on a new ANSI/TPI 3 standard dealing with
temporary and permanent bracing of metal plate connected wood trusses.
The bottom chord continuous lateral restraint and web member restraint are specified on the truss
manufacturer’s design drawing. Figure 8A is the truss design drawing for this building and it
shows six webs, designated by bolder lines, which are to receive T-brace reinforcement. T-brace
reinforcement is being used here as opposed to continuous web lateral restraints because of the
wide spacing of the trusses. The truss drawing also indicates that the bottom chord lateral
restraints are to be spaced no more than 10 ft. on center unless a rigid ceiling is directly applied.
In this example building, there is a ceiling constructed with steel panels. However, we have
elected to keep the bottom chord lateral restraints in the design since they will likely already
have been installed as part of the temporary bracing scheme. L-Reinforcement is used with the
lateral restraints based upon Table 2 of BCSI – B10 Post Frame Truss Installation, Restraint and
Bracing.
8.2 X-Bracing
Truss members that are braced with continuous lateral restraints can all buckle in the same
direction if sufficient diagonal or X-bracing is not provided. The main purpose of the diagonal
bracing is to create a triangle with the continuous lateral restraints and direct axial forces into the
sidewalls. This type of bracing is considered part of the permanent building stability bracing
scheme and is not shown on the truss design drawing.
X-bracing is used at each bottom chord lateral restraint to brace it off to the roof and ceiling
planes. This is designed to resist a force in the lateral restraint equal to 5% of the max
compression force in the bottom chord times the number of trusses between brace locations
divided by the number of lateral restraints. The ceiling was ignored in this calculation.
= [0.05(858)(7)]/6 = 50 lbs
Bottom chord diagonal bracing has not been used in this plan. The ceiling diaphragm serves to
distribute wind and bracing loads to the bearing walls, and the X-bracing diagonally braces the
lateral restraints. Therefore, bottom chord diagonals are not needed. If the building had no
ceiling, bottom chord diagonal bracing would have been used to help distribute loads from the X-
bracing to the bearing walls.
Corner bracing is used on the bottom side of the top chord at each corner of the building.
Truss design is usually conducted by the truss manufacturer using the provisions of ANSI/TPI 1,
“National Design Standard for Metal Plate Connected Wood Truss Construction” with the top
chord live or snow load, the top chord dead load, the bottom chord live load, and the bottom
chord dead load specified by the building designer. In this design example, the designer would
specify the following loads for the truss design:
Figure 8B is a truss bracing plan for the roof system. The blue lines show the bottom chord
continuous lateral restraint running continuously from endwall to endwall. The green lines show
the corner bracing, and the cyan lines show the X bracing.
Figure 8C is Cross Section A/1 taken at the location indicated on the Truss Bracing Plan. The
roof and ceiling diaphragms are shown on this figure and the truss webs that receive a T-brace
and/or an X-brace. The bottom chord continuous lateral restraint is also identified.
Figure 8D shows how the X bracing should be applied when running across 3 trusses, while
Figure 8E shows an X brace detail across 2 trusses.
The post-frame design is summarized in the following series of design drawings by Timber Tech
Engineering, Inc.
NOTE: This design example is divided into two parts. Part 1 is written as a teaching tool for designers not familiar with post-frame
building design in that it explains each step of the lateral design process for a post-frame building and summarizes the results of the
calculations. Part 2 is a comprehensive calculation package that gives the background design calculations for each step and is a
much longer document. Both Part 1 and Part 2 can be used as stand alone documents.
TABL E OF CONTENTS
SECTION PAGE
▪ SECTION 6: CONNECTIONS 21
▪ APPENDIX A
A1: FRAME STIFFNESS 2
A2: EAVE LOAD 3
A3: POST DESIGN 4
▪ APPENDIX D
PURLIN DESIGIN 2
GIRT DESIGN 9
NOTE: ASCE 7-05 Section 6.1.4.1 requires the main wind force resisting system (MWFRS) be
designed for a horizontal wind pressure of 10 psf multiplied by the area of the building projected onto a
vertical plane normal to the assumed wind direction. The MWFRS for this building is the roof
diaphragm, shearwalls and post-frame. The 10 psf minimum wind load requirement controls the design
of the MWFRS for this building as shown in section 2.5.4 of this report. However, individual building
components are controlled by wind pressures derived from coefficients. This design example is a
detailed look at the lateral design of a post-frame building using wind pressures and suctions from
coefficients, and Appendix E is included to show that the MWFRS is adequate for the 10 psf minimum
wind load requirement.
Section 1: Building Descr iption
Wind-Governed Design Example
This is a design example in which a 72' wide x 120' long x 16' high Post-Frame building's lateral force resisting system is analyzed
and designed for wind and seismic loading. The building is located in Dane County, Wisconsin where, surrounded by closely spaced
wind obstructions, it qualifies for surface roughness category B as defined in ASCE 7-05. This commercial building is comprised of
the following structural members:
24 in o/c and 16
2x4 #2 SYP, on edge, fastened to truss with (1) in o/c in
Roof Purlins
60d R.S. nail and (2) 16d toenails, each unbalanced
snow area
There are (4) 36"x60" windows equally spaced on one endwall and (1) 24'Wx14'H overhead door on opposite endwall; there are (2)
36"x60" windows and (2) 16'Wx14'H overhead doors and (1) 36"x80" man door in rear sidewall and (2) 36"x80" man doors and (2)
16'Wx14'H overhead doors in front sidewall. The exterior walls and roof are sheathed with Grandrib 3, 29 gage structural metal
sheathing manufactured by Fabral. On the interior, the walls and ceiling are also sheathed with Grandrib 3, 29 gage structural metal
sheathing by Fabral (see Figure 3A and 3B for panel profile and fastener pattern, test panel size and configuration, and in-plane shear
strength and stiffness data). The ceiling is framed with 2x4 #2 SYP ceiling joists 24" o/c in between the trusses. The ceiling
sheathing and roof sheathing have the same orientation. The building is heated and insulated with R-19 insulation in walls and R-30
insulation in the ceiling. There is a 12" roof overhang on the gable ends and 24" overhang on the sidewalls.
Section 2: ASCE 7-05 L oad Calculations
The wind load calculations, including main wind force resisting system (MWFRS) and components and cladding (C& C) loads, are
presented first; followed by dead, live and snow load calculations. Seismic loading is then calculated and compared to wind to see
which controls the lateral design for strength and deflection. This section concludes with allowable lateral deflection criterion and
controlling load combinations for various components.
2.1 Wind Design M ethod 2 - Analytical Pr ocedur e - L ow-Rise Building (ASCE 7-05, 6.5, 6.5.12.2.2)
Building I nputs: Calculation I nputs:
Length Parallel to Ridge, B 120 ft Basic Wind Speed, V 90 mph
Length Normal to Ridge, L 72 ft Topographic Factor, K zt 1.00
Wall Height, z 16 ft
Post Sidewall Spacing, s 8 ft
Post Endwall Spacing, s 8 ft Envelope: Enclosed Building
Building Midheight, h 21.25 ft Wind Directionality Factor 0.85
Roof Pitch (rise per 12 units of run) 3.5 Building Category II
Eave Overhang 2 ft Exposure Category B
Definitions:
Case A - Wind Direction Normal to Roof Ridge, Pressure Coefficients Vary With Roof Angle.
Case B - Wind Direction Parallel to Ridge, Pressure Coefficients are Constant for all Roof Angles.
Interior Zones - Zones 1 - 6 Below
Edge Zones - Zones 1E - 6E Below
I nter mediate Calculations:
Importance Factor, I 1.00 Table 6-1 Calculated Roof Angle 16.3 deg
Nom. Height of Atmospheric Boundary (zg) 1200 Internal Press. Coefficient, Gcpi 0.18 -0.18
Vel. Press. Exp. Coefficient, K z 0.635
3-s Gust Speed Power Law Exponent (α) 7 Velocity Pressure, qh 11.2 psf
2.1.1 M ain Wind For ce Resisting System: ASCE 7-05, Figur e 6-10 Equation: p = qh[(GCpf -(Gcpi )]
Case A Case B
P (psf) P (psf)
Gcpf I* II** III ~ Gcpf I* II** III ~
Zone 1: Windward Side Wall 0.50 3.6 7.6 5.6 0.40 2.5 6.5 4.5
Zone 2: Windward Roof -0.69 -9.7 -5.7 -7.7 -0.69 -9.7 -5.7 -7.7
Zone 3: Leeward Roof -0.45 -7.1 -3.1 -5.1 -0.37 -6.2 -2.1 -4.1
Zone 4: Leeward Side Wall -0.40 -6.4 -2.4 -4.4 -0.29 -5.3 -1.2 -3.2
Zone 5: Gable Wall -0.45 -7.0 -3.0 -5.0
Zone 6: Gable Wall -0.45 -7.0 -3.0 -5.0
Zone 1E: Windward Side Wall Edge 0.75 6.4 10.4 8.4 0.61 4.8 8.8 6.8
Zone 2E: Windward Roof Edge -1.07 -14.0 -10.0 -12.0 -1.07 -14.0 -10.0 -12.0
Zone 3E: Leeward Roof Edge -0.65 -9.3 -5.3 -7.3 -0.53 -7.9 -3.9 -5.9
Zone 4E: Leeward Side Wall Edge -0.59 -8.6 -4.6 -6.6 -0.43 -6.8 -2.8 -4.8
Wind load should not be less than 10 psf on vertical projection. (ASCE 7-05, 6.1.4.1)
Because the structure is less than 30ft high, the torsional cases 1T, 2T, 3T and 4T do not apply. (ASCE 7-05, Fig. 6-10, note 5)
2.1.2 Components and Cladding: ASCE 7-05, Figur e 6-11 Equation: p = qh[(Gcp)-(Gcpi)]
Note: Only negative loads are shown because they are larger than positive and so control the design.
Effective Wind
Component: Wall Girts Component: Roof Purlins
Ar ea: span length 2
multiplied by an Effective Area: 21.33 ft Effective Area: 21.33 ft2
effective width that Zone Gcp P (psf) Zone Gcp P (psf)
need not be less I* II** ~
III I* II** III ~
than one-third the 4: Wall Interior -1.0 -13.7 -9.7 -11.7 1: Roof Interior -0.9 -11.7 -7.6 -9.6
span length. 5: Wall Edge -1.3 -16.4 -12.4 -14.4 2: Roof Edge -1.5 -19.2 -15.2 -17.2
3: Roof Corners -2.4 -28.9 -24.8 -26.8
* Internal Pressure Positive ** Internal Pressure Negative ~ Internal Pressure Zero
Back
2.2 Dead L oad Calculations
2.2.1 Wall Dead L oad 3 psf
I nputs:
Horizontal Distance Eave to Ridge, W 38 ft
Equations: W ≤20 ft. (ASCE 7-05, Figure 7-5)
▪0 Windward Unbalanced
▪ (pg)(I) Leeward Unbalanced
W > 20 ft
▪ 0.3*ps Windward Unbalanced
▪ ps + hd(γ)/(√(S)) Leeward Unbalanced, the latter extended from the ridge
a distance of [8(√(S))(hd)]/3
I nter mediate Calculations:
Roof Angle = 16.26 degrees hd = 2.13 ft
g = 17.9 pcf S = Roof slope run for a rise of 1 = 3.4286
punbal, leeward = 43.7 psf for a distance of 10.5 ft from the ridge, then 23.1 psf to eaves
punbal, windward = 6.9 psf
Back
2.5 Seismic L oad Calculations
2.5.2 Calculation I nputs:
2.5.1 Building and Site I nputs: Spectral Response Acceleration, S1 0.05
Site Class D Spectral Response Acceleration, SS 0.15
Basic Structural System: Response Modification Factor, R 7
All other structural systems: Height to Highest Level (ft), hn 16
Light-framed walls sheathed w/ steel sheets Weight of Structure (lbs), W 6240
Seismic Design Category: D (ASCE 7-05, 11.6) (9 psf)(72+2 +2 ft)(8 ft)+2(3 psf)(16 ft)(8 ft)
Effective Weight of Structure (lbs), We 5760
(9 psf)(72+2 +2 ft)(8 ft)+2(3 psf)(16 ft)(8 ft)(3/8)
2.5.3 I nter mediate Seismic Calculations 2.5.4 Wind Resolved to Hor izontal Point L oad at Eave, Fw
Seismic Use Group II Building Inputs: Load from Roof
Occupancy Importance Factor, I E 1 Fixity Factor 0.375 (lbs)
Sms 0.240 Wind Force with 10 psf min, Fw = 1320 lbs 840
SDs 0.160 Wind Force with Roof and Walls, Fw = 256 lbs -223
Sm1 0.120 Wind Force with Walls only, Fw = 479 lbs 0
SD1 0.080 NOTE: The 10 psf minimum requirement of ASCE 7-05, 6.1.4.1
CT 0.02 controls the design of the main wind force resisting system
Cu 1.7 (MWFRS). The MWFRS for this building is the roof diaphragm and
Acceleration Site Coefficient, Fa 1.6 shearwalls, and the post-frame. This example will proceed with
Velocity Site Coefficient, Fv 2.4 building component design using wind pressures from coefficients,
and then show that MWFRS is adequate for 10 psf minimum load in
App. Fund. Period, Ta 0.16
Appendix E at the end of this report.
Fundamental Period, T 0.27
Seismic Coefficient, Cs 0.023
Cs min 0.007
Cs max 0.042
Seismic Base Shear, V = 143 lbs Controlling Wind Load:
Lateral Seismic Force at Roof, FR = 132 lbs Wind Force per Frame, Fw = 479 lbs
[F R = 143 x 5760 / 6240 ]
2.5.5 Seismic vs. Wind Compar ison
Controlling Load Combination Strength Comparison Serviceability Comparison
D+W 479 lbs Wind Controls the Strength Design (D+0.7E)C d < D+W: Wind Controls
D+0.7E 92.2 lbs Serviceability Requirements
2.6 Stor y Dr ift and Wind Deflections
Allowable Story Drift = 0.02 hs1 (ASCE 7-05, Table 12.12-1)
Story Height, hs1 = 192 in
Allowable Stor y Dr ift = 3.84 in
Other Deflection Criterion = l/120 (ASCE 7-05, Section 12.12.2 and IBC 2009, Table 1604.3)
Allowable Deflection at Eave = 1.6 in (controlling deflection criterion)
Actual Calculated Deflection = 0.57 in (see DAFI outputs)
Story Drift from Elastic Analysis, δ1e = n/a in (seismic does not control the strength or serviceability design)
Deflection Amplification Factor, Cd = 4.5
Calculated Stor y Dr ift at Eave , δ1 = n/a in
Story drift requirements are satisfied - calculated story drift is less than controlling allowable story drift
Back
2.7 Contr olling L oad Combinations
Wall Posts D+0.75(S+W) Post Foundation (Lateral Loading) D+W and 0.6D+W
Roof Diaphragm D+W and 0.6D+W Post Foundation (Uplift) 0.6D+W
Endwall Shearwalls D+W and 0.6D+W Wall Girts D+W and 0.6D+W
Roof Truss D+S Purlins 0.6D+W or D+S
Back
ch,1 roof = 9986 lbf/in
ch,2 roof = 9986 lbf/in
ch,3 ceiling = #### lbf/in
The endwall stiffness, ke, is calculated by summing the horizontal shear stiffness of the wall diaphragm and the bending stiffness of
the endwall posts. The horizontal shear stiffness of the wall diaphragm is found by adjusting the model diaphragm shear stiffness for
the actual size of endwall. The interior liner is constructed the same as the exterior siding and is included in the endwall calculations.
The eave load, Pi, used in this analysis is the resultant lateral load from the controlling combination of design loads acting over the
tributary area of the eave, and is applied as a concentrated load at the eave of each frame. The eave load is calculated using Frame-
Base Fixity Factors or by Plane-Frame Structural Analysis.
The standard method of fixity factors typically assumes that a post is simply supported with zero rotational resistance at ground level,
or is fully fixed with zero rotation at ground level. Sometimes neither of these assumptions are completely accurate. In the case of a
non-constrained post foundation, the top horizontal support of the foundation system is located a distance below ground level. This
means that there are some lateral and rotational deflections at the ground line. As a result, the standard 0.375 fixity factor for a
rigidly supported column is a rough approximation. Assuming a pinned base condition for the post yields a higher eave load and is
conservative for the diaphragm design; conversely, assuming a perfectly fixed base condition yields a lower eave load and is
conservative for the post design. We have chosen to use a fixity factor of 0.42 which is a little more toward fixed than pinned.
Back
f pin= 0.5 (fixity factor for a pin post base support)
f fixed= 0.375 (fixity factor for a fixed post base support)
Pi, pin= 639 (Eave Reaction With Pinned Column Base)
Pi, fixed= 479 (Eave Reaction With Fixed Column Base)
f new= 0.42
Pi = 538 lbs P i = s[ h r (q wr - q lr ) + h w f new (q ww - q lw )]
A windows version of this program is available as a free download from the National Frame Building Association website
(nfba.org). It allows data to be entered using a special screen editor. The data can be saved to and later recalled from
an input data file.
Shear Load in Endwall 1 = 3701 lbf DAFI Output: Load Resisted by Frame 1
Shear Load in Endwall 2 = 3487 lbf DAFI Output: Load Resisted by Frame 16; Wall with 20' Door
Horizontal Diaphragm Shear = 3432 lbf DAFI Output: Largest Diaphragm Shear Load
Shear Load in Endwall 1, V max, 1 = 3701 lbf DAFI Output: Load Resisted by Frame 1
Shear Load in Endwall 2, V max, 2 = 3487 lbf DAFI Output: Load Resisted by Frame 16; Wall with 24' Door
Allowable Shear Strength, va = 110 lbf/ft (from Table 6.1 test assembly #6 of PFBDM)
vmax ≤va <ok> (actual shear in endwalls is less than allowable shear)
Back
3.9 Sidewall Shear Str ength Check
Wind Parallel To Ridge
The controlling load combination for wind loads parallel to ridge is D+W, where windward and leeward pressures are applied to the
tributary area of the endwall. For simplicity the columns are assumed to be fully rigid at ground level with a fixity factor of 3/8.
Typically the endwalls in a post-frame building are the controlling shear walls. There are cases, however, when sidewalls are the
critical shear walls, especially in wide buildings that are short in length. In those situations a more thorough analysis is required, in
which a roof and sidewall stiffness and possibly torsional effects on the overall building envelope are considered. An analytical
model of each column height with proper base conditions may also be required to calculate loads on the diaphragm more accurately.
Allowable Shear Strength, va = 220 lbf/ft (Exterior Sheathing and Interior Liner)
Fixity Factor, f fixed= 0.375 (assume zero column rotation at ground level)
Tributary Area, A t = 810 ft2 (see sketch above)
Length of Wall, L sidewall = 79 ft (length of sidewall minus all door and window openings)
qww = 10.0 psf (10 psf minimum requirement controls the design)
qlw = 0.0 psf (10 psf minimum requirement controls the design)
Maximum Shear Load, V max = 8100 lbs
Actual Shear Load, vsidewall = 51 lbf/ft V max /L sidewall /2walls
vsidewall ≤va <ok> (actual shear in sidewall is less than allowable shear)
Ch, roof = ch,1 roof + ch2, roof = 19973 lbf/in (horizontal stiffness provided by roof sheathing)
Ch, ceiling = 19710 lbf/in (horizontal stiffness provided by ceiling sheathing)
L s, roof = 79.17 ft (width of building plus overhangs divided by cosine of roof angle)
L s, ceiling = 72 ft (width of building)
vmax, in-plane = V max, in-plane / L s (shear load in plane of the roof or ceiling sheathing)
Back
M ax
Total M ax L oad in Shear L oad in
Hor izontal Horizontal
Roof Hor izontal L oad Plane of Plane of Allowable Shear
Stiffness of L oad on θ
Component Stiffness of Ratio Component, Component, L oad, va
Component Component,
Diaphr agm V max, in-plane va
V max, hor izontal
Ceiling
19710 39683 0.497 1704 0 1704 24 110
Sheathing
vmax ≤va <ok> (actual shear in diaphragm is less than allowable shear)
3.11 Roof Diaphr agm Chor d For ces
The roof diaphragm acts like a deep beam where the ends of the beam are assumed to be fixed. The diaphragm of this building
consists of two individual roof diaphragms, one on each side of ridge, and of one ceiling diaphragm. The bending forces in each
diaphragm are resisted by roof purlins and ceiling joists. Because only the edge purlins and ceiling joists are fastened together to
provide a continuous tensile resistance to tension chord of diaphragms, it can be conservatively assumed that the intermediate purlins
and ceiling joists provide zero contribution to the bending resistance of diaphragms. The load is applied to the diaphragm at eave,
and redistributed to individual diaphragms according to their stiffness. For simplicity, the load resistance contribution of frames is
ignored. The purlins are fastened together at splices with a single HTP37Z Simpson plate fastened to the side with 10dx1-1/2 nails;
the ceiling joists are fastened together at splice with a single MSTA21 Simpson strap, fastened to the bottom edge with 10dx3" nails.
It should be noted that typical roof diaphragm deflection consists of bending deflection, shear deflection of sheathing panel,
deflection due to nail slip, and deflection due to slip in chord connection splices. Because the diaphragm stiffness in this example is
based on a sample test, it can be assumed that all of these deflection contributors, with exception of the deflection due to slip in chord
connection splices, are accounted for. It is further assumed that the deflection due to slip in chord connection splices is minimal and
is an insignificant contributor to the overall diaphragm deflection.
Load Ratio to Each Diaphragm , p = ch,x/Ch (individual diaphragm stiffness divided by total diaphragm stiffness)
Load on Roof Diaphragm, w = 67.29 lbf/ft (eave load, Pi , divided by column spacing, s)
2
End Moment, M ex = wxL x /12 (controls the design)
2
Midspan Moment, M mx = wxL x /24* (moment equation for a beam with fixed end supports)
Tension/ Compression Force, Tx = M ex/bx (controlling moment divided by depth of individual diaphragm)
* A moment is generated in the diaphragm as the diaphram deflects lateraly under horizontal wind or seismic loads. The resulting
bending forces travel along the length of the buidling through the edge ceiling joists and purlins which are restricted from moving
longitudinaly by rigid sidewalls; hence, the diaphragm is assumed to be rigidly fixed at the endwalls.
HTP37z Simpson Strap = 1600 lbs (allowable tension capacity as specified by the manufacturer)
MSTA21 Simpson Strap = 1505 lbs (allowable tension capacity as specified by the manufacturer)
Px ≤Pa <ok> (actual tension load is less than allowable tension load)
Back
Section 4: Post Design
4.1 L oads
The post embedment below grade is 4 ft; a 24" diameter x 24" high concrete collar is poured around the post, on top of an 8" thick
concrete footing. The reactions on the foundation are imposed from the column at ground level, as shown in Figure 5A below. The
allowable lateral bearing soil pressure, S', is assumed to be 200 psf/ft of depth, and the initial allowable vertical bearing soil
pressures are assumed to be 2000 psf (EP486.1, Table 1). Per Footnote 4 of the EP486.1 Table 1, the vertical allowable foundation
pressures "are for footings at least 300 mm (1 ft) wide and 300 mm (1 ft) deep into natural grade. Pressure may be increased 20%
for each additional 300 mm (1 ft) of width and/or depth to a maximum of three times the tabulated value. Source: Table 18-1-A
UBC." The adjusted allowable vertical soil pressures along with controlling load combinations for gravity, lateral and uplift loads, and
other calculations are provided in Appendix B.
Figure 5A. FBD of non-constrained post foundation with concrete collar from ANSI/ASAE EP486.1.
Purlins are positioned on edge on top of top chord of truss and typically span over two spans for the total length of 16ft. Due to the
Dead Load, DL = 2.5 psf (on surface area, see Roof Dead Load Section)
Roof Live Load, LL r = 20 psf (on horizontal projection, does not control)
Snow Load, SL balanced = 23.1 psf (on horizontal projection)
Snow Load, SL unbalanced, windward = 6.9 psf (on horizontal projection)
Snow Load, SL unbalanced,leeward = 43.7 psf, for a distance of 10.5 ft from ridge, then 23.1 psf
Interior Roof Wind Load, qinterior = -11.7 psf (component and cladding)
Edge Roof Wind Load, qedge = -19.2 psf (component and cladding)
Corner Roof Wind Load, qcorner = -28.9 psf (component and cladding)
Deflection Criterion = l/150 and l/120 for Live and Dead + Live Loads
Roof angle, θr = 16.3 degrees
2x4 #2 S. Pine flat against posts @ 24" on center continuous over two spans (Design details are provided in Appendix C).
Interior Wall Wind Load, qinterior = -13.7 psf (component and cladding)
Edge Wall Wind Load, qedge = -16.4 psf (component and cladding)
Deflection Criterion = l/90 (IBC 2009, 1604.3, Footnote a)
Section 7: Connections
Detailed Connection Calculations Are Provided In Appendix D
The end shear at top of post equals the calculated horizontal reaction of the critical frame. This reaction is the sum of three (3)
components:
Horizontal Roof Load, Fr = 0 lbs (1) (roof component of calculated eave load divided by 2 posts)
Resisting Force by Diaphragm, Rd = -377.7 lbs (2) F d = [ (eave load)-(load resisted by Frame 2)] [ q ww /(q ww +q lw )]
Resistance by Opposite Post, R2 = -9.72 lbs (3) R 2 = Δ2 (k)q lw /(q ww -q lw ), where k = frame stiffness
Shear at Top of Post, V 2 = -387 lbs (V 2 = F r + R d + R 2 )
Allowable Shear Capacity = 2275 lbs (Detailed connection calculations are provided in Appendix D)
M aximum Tension For ce, T max = 535 lbs (T x from Section 3.11 Roof Diaphragm Chord Forces)
Allowable Tension Capacity, T a = 1850 lbs (Detailed connection calculations are provided in Appendix D)
Allowable Tension Capacity, T a = 1513 lbs
7.7 Ceiling Joist to Ceiling Joist Splice and to Cor ner Post Connection
The edge ceiling joists serve as tension and compression chords of the ceiling diaphragm. In order to provide a continuity in tensile
resistance in the tension chord of the diaphragm, the ceiling joists must be fastened together at each splice. In this design a MSTA21
Simpson strap is used at each purlin splice. The edge ceiling joists must also be fastened to corner posts to transfer loads into
sidewall sheathing.
M aximum Tension For ce, T max = 557 lbs (T x from Section 3.11 Roof Diaphragm Chord Forces)
Allowable Tension Capacity, T a = 1505 lbs (Detailed connection calculations are provided in Appendix D)
Allowable Tension Capacity, T a = 1474 lbs
Net Uplift For ce, Qnet = 1153 lbs (from Section 5.1 Post Reactions at Grade Level)
Number of Reinfor cing Bar s = 1
Allowable Shear Capacity, Z' = Z(CD)(CM) = 1720(1.6)(0.7) = 1926 lbs
Back
Section 8: Other Design Consider ations
This design example focused on resistance to lateral loads. Some other important connections not contained in this example, may
include:
▪ Overhead Door Header(s) to Post Connection - Vertical and Horizontal shear
▪ Girt to Post Connection - Withdrawal due to wind suction
▪ Purlin to Truss Connection -Withdrawal (uplift) due to wind suction
▪ Roof Sheathing to Purlins Connection -Withdrawal (uplift) due to wind suction
▪ Wall Sheathing to Girts Connection - Withdrawal due to wind suction
It is also important to note that the truss design will be performed by the truss designer using the loading and geometry provided by
the building designer. Guidelines for handling, bracing, and installing metal plate connected wood trusses are contained in the
Building Component Safety Information (BCSI) booklet published jointly by TPI and WTCA. The truss bracing design for this
building should take into account the bottom chord and compression web lateral restraint requirements shown on the truss design
drawings, as well as the on center spacing of the trusses.
APPENDIX A
FRAME STIFFNESS
FRAME EAVE REACTION
POST DESIGN
A.1 Fr ame Stiffness
LOADING ON FRAME
Back
A.2 Post Design
NODE NAMES
(IES Visual Analysis 7.0)
MEMBER NAMES
(IES Visual Analysis 7.0)
Back
DEAD LOADS
(IES Visual Analysis 7.0)
UNITY CHECK
Applied Stresses from Controlling Load Combination Divided by Adjusted Allowable Sresses
(IES Visual Analysis 7.0)
Visual Analysis Report - Sidewall Post Design
Company: Timber Tech Engineering, Inc. Engineer: Dimitry Reznik
VisualAnalysis 7.00 Report
Table of Contents
Project Header
Table of Contents
Load Cases
Load Combination Summary
Section Properties
Member Elements
Design Groups
Nodal Loads
Member Uniform Loads
Nodal Displacements
Member Unity Checks
Design Group Results
Nodal Reactions
Load Cases
——————————————————————————————————————————————————————————————————————————————————
Load Case Design Checks Seismic Type Results Analyze? Envelope?
——————————————————————————————————————————————————————————————————————————————————
Section Properties
————————————————————————————————————————————————————
Section Theta Ax Iz Sz(+y) Sz(-y)
deg in^2 ft^4 ft^3 ft^3
————————————————————————————————————————————————————
Member Elements
—————————————————————————————————————————————————————————————————————————————————————————
Member Section Material (1)Node (2)Node Length Rz1 Rz2 One Way Framing
ft
—————————————————————————————————————————————————————————————————————————————————————————
Design Groups
———————————————————————————————————————————————————————————————————
Group/Me Elements LL Factor Unity Design Shape Overstrength
———————————————————————————————————————————————————————————————————
Nodal Loads
—————————————————————————————————————————————————————————
Load Case Node Direction Force Moment
lb lb-ft
—————————————————————————————————————————————————————————
Nodal Displacements
————————————————————————————————————————————————————————
Node Result Case Name DX DY RZ
in in deg
————————————————————————————————————————————————————————
Axial Check:
Member Result Offset Axial fa Fa Fa' CP Unity
Name Case # ft State psf psf psf Check
P1-Dry 18.01 0.00 Comp. -8322 237600 96370 0.25 0.09
P1-Dry 19.01 0.00 Comp. -8322 237600 96370 0.25 0.09
P1-Dry 20.01 0.00 Comp. -13870 237600 89881 0.42 0.15
P1-Dry 21.01 0.00 Comp. -35059 237600 94171 0.32 0.37
P1-Dry 22.01 0.00 Comp. -27823 237600 93253 0.34 0.30
P1-Dry 23.01 0.00 Comp. -35059 237600 96370 0.25 0.36
P1-Dry 24.01 0.00 Comp. -35059 237600 96370 0.25 0.36
P1-Dry 25.01 0.00 Comp. -13870 237600 96370 0.25 0.14
P1-Dry 26.01 0.00 Comp. -13870 237600 96370 0.25 0.14
P1-Dry 27.01 0.00 Comp. -27823 237600 96370 0.25 0.29
P1-Dry 28.01 0.00 Comp. -27823 237600 96370 0.25 0.29
P1-Dry 29.01 0.00 Comp. -42122 237600 94171 0.32 0.45
P1-Dry 30.01 0.00 Comp. -32475 237600 93253 0.34 0.35
P1-Dry 31.01 0.00 Comp. -13870 237600 96370 0.25 0.14
P1-Dry 32.01 0.00 Comp. -13870 237600 96370 0.25 0.14
P2-Dry 18.01 0.00 Comp. -8319 237600 96370 0.25 0.09
P2-Dry 19.01 0.00 Comp. -8319 237600 96370 0.25 0.09
P2-Dry 20.01 0.00 Comp. -13865 237600 89881 0.42 0.15
P2-Dry 21.01 0.00 Comp. -35054 237600 94171 0.32 0.37
P2-Dry 22.01 0.00 Comp. -37778 237600 93253 0.34 0.41
P2-Dry 23.01 0.00 Comp. -35054 237600 96370 0.25 0.36
P2-Dry 24.01 0.00 Comp. -35054 237600 96370 0.25 0.36
P2-Dry 25.01 0.00 Comp. -13865 237600 96370 0.25 0.14
P2-Dry 26.01 0.00 Comp. -13865 237600 96370 0.25 0.14
P2-Dry 27.01 0.00 Comp. -37778 237600 96370 0.25 0.39
P2-Dry 28.01 0.00 Comp. -37778 237600 96370 0.25 0.39
P2-Dry 29.01 0.00 Comp. -42117 237600 94171 0.32 0.45
P2-Dry 30.01 0.00 Comp. -45749 237600 93253 0.34 0.49
P2-Dry 31.01 0.00 Comp. -13865 237600 96370 0.25 0.14
P2-Dry 32.01 0.00 Comp. -13865 237600 96370 0.25 0.14
Axial Check:
Member Result Offset Axial fa Fa Fa' CP Unity
Name Case # ft State psf psf psf Check
P1-Wet 18.01 0.00 Comp. -8396 237600 327108 0.86 0.03
P1-Wet 19.01 0.00 Comp. -8396 237600 327108 0.86 0.03
P1-Wet 20.01 0.00 Comp. -13994 237600 198947 0.93 0.07
P1-Wet 21.01 0.00 Comp. -35184 237600 266412 0.90 0.13
P1-Wet 22.01 0.00 Comp. -27948 237600 247798 0.91 0.11
P1-Wet 23.01 0.00 Comp. -35184 237600 327108 0.86 0.11
P1-Wet 24.01 0.00 Comp. -35184 237600 327108 0.86 0.11
P1-Wet 25.01 0.00 Comp. -13994 237600 327108 0.86 0.04
P1-Wet 26.01 0.00 Comp. -13994 237600 327108 0.86 0.04
P1-Wet 27.01 0.00 Comp. -27948 237600 327108 0.86 0.09
P1-Wet 28.01 0.00 Comp. -27948 237600 327108 0.86 0.09
P1-Wet 29.01 0.00 Comp. -42247 237600 266412 0.90 0.16
P1-Wet 30.01 0.00 Comp. -32599 237600 247798 0.91 0.13
P1-Wet 31.01 0.00 Comp. -13994 237600 327108 0.86 0.04
P1-Wet 32.01 0.00 Comp. -13994 237600 327108 0.86 0.04
P2-Wet 18.01 0.00 Comp. -8393 237600 327108 0.86 0.03
P2-Wet 19.01 0.00 Comp. -8393 237600 327108 0.86 0.03
P2-Wet 20.01 0.00 Comp. -13989 237600 198947 0.93 0.07
P2-Wet 21.01 0.00 Comp. -35179 237600 266412 0.90 0.13
P2-Wet 22.01 0.00 Comp. -37902 237600 247798 0.91 0.15
P2-Wet 23.01 0.00 Comp. -35179 237600 327108 0.86 0.11
P2-Wet 24.01 0.00 Comp. -35179 237600 327108 0.86 0.11
P2-Wet 25.01 0.00 Comp. -13989 237600 327108 0.86 0.04
P2-Wet 26.01 0.00 Comp. -13989 237600 327108 0.86 0.04
P2-Wet 27.01 0.00 Comp. -37902 237600 327108 0.86 0.12
P2-Wet 28.01 0.00 Comp. -37902 237600 327108 0.86 0.12
P2-Wet 29.01 0.00 Comp. -42242 237600 266412 0.90 0.16
P2-Wet 30.01 0.00 Comp. -45874 237600 247798 0.91 0.19
P2-Wet 31.01 0.00 Comp. -13989 237600 327108 0.86 0.04
P2-Wet 32.01 0.00 Comp. -13989 237600 327108 0.86 0.04
Nodal Reactions
———————————————————————————————————————————————————————
Node Result Case Name FX FY MZ
lb lb lb-ft
———————————————————————————————————————————————————————
Back
NON CONSTRAI NED FOOTI NG WI TH BOTTOM CONCRETE COL L AR (EP 486.1)
VERTICAL REACTIONS HORIZONTAL REACTIONS MOMENTS
Dead Load (lbs) 3010 Dead Load (lbs) 0 Dead Load (ft-lbs) 0
LiveR Load (lbs) 6080 LiveR Load (lbs) 0 LiveR Load (ft-lbs) 0
Snow Load (lbs) 6862 Snow Load (lbs) 0 Snow Load (ft-lbs) 0
Wind Uplift (lbs) 2959 Wind Load (lbs) 602 Wind Load (ft-lbs) 1850
REACTI ONS
D 3010 D 0 D 0
D+Lr 9090 D+Lr 0 D+Lr 0
D+S 9872 D+S 0 D+S 0
W-0.6D (Uplift) 1153.458 D+W 602 D+W 1850
FI NAL REACTI ONS:
Vertical, P (lbs): 9872 Horizontal, V a (lbs): 602 Moment, M a (ft-lb): 1850
Uplift, Q (lbs): 1153.46
NON-CONSTRAI NED FOOTI NG WI TH BOTTOM CONCRETE COL L AR (ASAE EP486.1 2003)
Initial Allowable vertical soil pressure, Sv (psf) 2000 (EP486.1 Table 1, without the allowable increase factor)
Allowable lateral bearing soil pressure, S' (psf/ft) 200 (EP486.1 Table 1)
Actual post embedment depth, d (ft) 4
REQUI RED POST EMBEDMENT DEPTH AND UPLI FT RESI STANCE CALCULATI ON
U= 2394.7 lbs > Q= 1153.5 lbs Depth Increase: 73.3 % Width Increase: 20.0 %
Sv = 3866.7 psf > Sa = 3142.4 psf S s = P/ π( w/2) 2
S v → ASAE EP486.1, 2003, Table 1
U=Uplift Resistance of Soil, Sv = Allowable Vertical Soil Pressure (including increases)
V a = Shear at Ground Surface, M a = Moment at Ground Surface, Q=Uplift at Ground Surface, Sa = Actual Vertical Soil Pressure
Back
APPENDIX C
PURLIN DESIGN
GIRT DESIGN
Back
APPENDIX D
DESIGN OF CRITICAL CONNECTIONS
Tr uss to Post Connection - Uplift - Ver tical Shear
w k1 = 1.05
Nail Penetration into main member (in) p 1.5 k2 = 1.09
Specific Gravity of Main Member G 0.55 F em = 5526
Specific Gravity of Side Member 0.55 F es = 5526
Duration Factor CD 1.6 (NDS 2005, Table 2.3.2) Re = 1.0
Wet Service Factor CM 1 p= 2.00
Temperature Factor Ct 1 1+R e = 2.0
Toe Nail Factor Ctn 1 Is 610
End Grain Factor Ceg 1 (NDS 2005, 11.5.2) IIIm 286
Depth Penetration Factor Cd 0.9259259 (Cd=p/10D) IIIs 222
Lateral Design Value (lbs) Z 154 (controlling yield value) IV 154
Total Allowable Lateral Capacity (lbs) Z' 2275 ← Z'=(# of Nails) x Z x C D x C d x C eg x C tn x C M x C t
Back
Tr uss to Post Connection - Hor izontal Shear at Fr ame 2, the Contr olling Fr ame for Hor izontal Shear
w k1 = 1.05
Nail Penetration into main member (in) p 1.5 k2 = 1.09
Specific Gravity of Main Member G 0.55 F em = 5526
Specific Gravity of Side Member 0.55 F es = 5526
Duration Factor CD 1.6 (NDS 2005, Table 2.3.2) Re = 1.0
Wet Service Factor CM 1 p= 2.00
Temperature Factor Ct 1 1+R e = 2.0
Toe Nail Factor Ctn 1 Is 610
End Grain Factor Ceg 1 (NDS 2005, 11.5.2) IIIm 286
Depth Penetration Factor Cd 0.9259259 (Cd=p/10D) IIIs 222
Lateral Design Value (lbs) Z 154 (controlling yield value) IV 154
Total Allowable Lateral Capacity (lbs) Z' 2275 ← Z'=(# of Nails) x Z x C D x C d x C eg x C tn x C M x C t
Back
Tr uss to Glulam Header Connection - Uplift
Number of straps/brackets/hangers 2
Specific Gravity G 0.55
Duration Factor CD 1 C D is included by bracket manufacturer
Wet Service Factor CM 1
Design Value per strap/bracket/hanger 1140
Total Allowable Capacity (lbs) 2280
Ceiling L edger to Endwall Posts Connection - Shear Tr ansfer fr om Ceiling Diaphr agm to Endwall
w k1 = 1.05
Nail Penetration into main member (in) p 2 k2 = 1.09
Specific Gravity of Main Member G 0.55 F em = 5526
Specific Gravity of Side Member 0.55 F es = 5526
Duration Factor CD 1.6 (NDS 2005, Table 2.3.2) Re = 1.0
Wet Service Factor CM 1 p= 2.00
Temperature Factor Ct 1 1+R e = 2.0
Toe Nail Factor Ctn 1 Is 610
End Grain Factor Ceg 1 (NDS 2005, 11.5.2) IIIm 286
Depth Penetration Factor Cd 1 (Cd=p/10D) IIIs 222
Lateral Design Value (lbs) Z 154 (controlling yield value) IV 154
Total Allowable Lateral Capacity (lbs) Z' 9830 ← Z'=(# of Nails) x Z x C D x C d x C eg x C tn x C M x C t
Back
Bottom Gir t to Endwall Posts Connection - Shear Tr ansfer fr om Wall Sheathing to Endwall Posts
w k1 = 1.05
Nail Penetration into main member (in) p 2 k2 = 1.09
Specific Gravity of Main Member G 0.55 F em = 5526
Specific Gravity of Side Member 0.55 F es = 5526
Duration Factor CD 1.6 (NDS 2005, Table 2.3.2) Re = 1.0
Wet Service Factor CM 0.7 p= 2.00
Temperature Factor Ct 1 1+R e = 2.0
Toe Nail Factor Ctn 1 Is 610
End Grain Factor Ceg 1 (NDS 2005, 11.5.2) IIIm 286
Depth Penetration Factor Cd 1 (Cd=p/10D) IIIs 222
Lateral Design Value (lbs) Z 154 (controlling yield value) IV 154
Total Allowable Lateral Capacity (lbs) Z' 6881 ← Z'=(# of Nails) x Z x C D x C d x C eg x C tn x C M x C t
Back
L OAD Pur lin to Pur lin Connection at Splice, Diaphr agm Tension Chor d
Tension Load in Diaphragm Chord (lbs) Tmax 535 ← Tension from Roof Diaphragm Chord Forces Section
HTP37Z Simpson Str ap
AL L OWABL E CAPACI TY
Number of straps/brackets/hangers 1
Specific Gravity G 0.55
Duration Factor CD 1 C D is included by the manufacturer
Wet Service Factor CM 1
Design Value per strap/bracket/hanger 1850
Total Allowable Capacity (lbs) 1850
Ceiling Joist to Ceiling Joist Connection at Splice, Diaphr agm Tension Chor d
L OAD
Tension Load in Diaphragm Chord (lbs) Tmax 557 ← Tension from Roof Diaphragm Chord Forces Section
M STA21 Simpson Str ap
AL L OWABL E CAPACI TY
Number of straps/brackets/hangers 1
Specific Gravity G 0.55
Duration Factor CD 1 C D is included by the manufacturer
Wet Service Factor CM 1
Design Value per strap/bracket/hanger 1505
Total Allowable Capacity (lbs) 1505
Back
L OAD Pur lin to Endwall Tr uss Connection, Diaphr agm Tension Chor d
Tension Load in Diaphragm Chord (lbs) Tmax 535 ← Tension from Roof Diaphragm Chord Forces Section
NAI L S - WOOD TO WOOD - SHEAR - NDS 2005, ASD
Nail Size 16d Intermediate Calculations
Number of nails # 5 KD 2.2
Nail Diameter (in) D 0.162 F yb (psi) 90000
Nail Length (in) L 3.5 2+R e = 3.0
Width of Side Member (in) w 1.5 1+2R e = 3.0
AL L OWABL E CAPACI TY
p k2 = 1.02
Specific Gravity of Main Member G 0.55 F em = 5526
Specific Gravity of Side Member 0.55 F es = 5526
Duration Factor CD 1.6 (NDS 2005, Table 2.3.2) Re = 1.0
Wet Service Factor CM 1 p= 2.50
Temperature Factor Ct 1 1+R e = 2.0
Toe Nail Factor Ctn 1 Is 1508
End Grain Factor Ceg 1 (NDS 2005, 11.5.2) IIIm 374
Depth Penetration Factor Cd 1 (Cd=p/10D) IIIs 513
Lateral Design Value (lbs) Z 178 (controlling yield value) IV 178
Total Allowable Lateral Capacity (lbs) Z' 284 ← Z'=(# of Nails) x Z x C D x C d x C eg x C tn x C M x C t
Tension Load in Diaphragm Chord (lbs) Tmax 535 ← Tension from Roof Diaphragm Chord Forces Section
WOOD SCREWS - WI THDRAWAL - NDS 2005, ASD
Screw Size # 8
Number of screws # 4 (# of effective screwsn not total)
Screw Diameter (in) D 0.164 Note: if a certain adjustment factor is not shown, its
Screw Length (in) L 3 value is assumed to be 1.0
AL L OWABL E CAPACI TY
Ceiling Joist to Cor ner Post Connection, Diaphr agm Tension Chor d
L OAD
Tension Load in Diaphragm Chord (lbs) Tmax 557 ← Tension from Roof Diaphragm Chord Forces Section
NAI L S - WOOD TO WOOD - SHEAR - NDS 2005, ASD
Nail Size 16d Intermediate Calculations
Number of nails # 6 KD 2.2
Nail Diameter (in) D 0.162 F yb (psi) 90000
Nail Length (in) L 3.5 2+R e = 3.0
Width of Side Member (in) w 1.5 1+2R e = 3.0
Width of Main Member (in) 7
AL L OWABL E CAPACI TY
w k1 = 1.05
Nail Penetration into main member (in) p 2 k2 = 1.09
Specific Gravity of Main Member G 0.55 F em = 5526
Specific Gravity of Side Member 0.55 F es = 5526
Duration Factor CD 1.6 (NDS 2005, Table 2.3.2) Re = 1.0
Wet Service Factor CM 1 p= 2.00
Temperature Factor Ct 1 1+R e = 2.0
Toe Nail Factor Ctn 1 Is 610
End Grain Factor Ceg 1 (NDS 2005, 11.5.2) IIIm 286
Depth Penetration Factor Cd 1 (Cd=p/10D) IIIs 222
Lateral Design Value (lbs) Z 154 (controlling yield value) IV 154
Total Allowable Lateral Capacity (lbs) Z' 1474 ← Z'=(# of Nails) x Z x C D x C d x C eg x C tn x C M x C t
NOTE: The 10 psf minimum wind load applied to the vertical projection (per
ASCE 7-05 Section 6.1.4.1) controls the design of the MWFRS for this building as
shown in Section 2.5.4. The MWFRS is a combination of the roof diaphragm and
shearwalls, and the post-frame. The scope of this Appendix includes design checks
to show the adequacy of the diaphragm and shearwalls. The Visual Analysis model
was run again to check the post for increased lateral deflection at the eave and the
new unity check is 0.72. This step is not shown, but the procedure is identical to
the one used in Appendix A.
ASCE 7-05 L oad Calculations
Pr oj ect Name: 72'x120'x16' Post-Frame Building
L ocation: Dane County, Wisconsin
M ethod 2 - Analytical Pr ocedur e - L ow-Rise Building (ASCE 7-05, 6.5, 6.5.12.2.2)
Building I nputs: Calculation I nputs:
Length Parallel to Ridge, B 120 ft Basic Wind Speed, V 90 mph
Length Normal to Ridge, L 72 ft Topographic Factor, K zt 1.00
Wall Height, z 16 ft
Post Sidewall Spacing, s 8 ft
Post Endwall Spacing, s 8 ft Envelope: Enclosed Building
Building Midheight, h 21.25 ft Wind Directionality Factor 0.85
Roof Pitch (rise per 12 units of run) 3.5 Building Category II
Eave Overhang 2 ft Exposure Category B
Definitions:
Case A - Wind Direction Normal to Roof Ridge, Pressure Coefficients Vary With Roof Angle.
Case B - Wind Direction Parallel to Ridge, Pressure Coefficients are Constant for all Roof Angles.
Interior Zones - Zones 1 - 6 Below
Edge Zones - Zones 1E - 6E Below
I nter mediate Calculations:
Importance Factor, I 1.00 Table 6-1 Calculated Roof Angle 16.3 deg
Nom. Height of Atmospheric Boundary (zg) 1200 Internal Press. Coefficient, Gcpi 0.18 -0.18
Vel. Press. Exp. Coefficient, K z 0.635
3-s Gust Speed Power Law Exponent (α) 7 Velocity Pressure, qh 11.2 psf
Wind L oad Results:
A. M ain Wind For ce Resisting System: ASCE 7-05, Figur e 6-10 Equation: p = qh[(GCpf -(Gcpi )]
Case A Case B
P (psf) P (psf)
Gcpf I* II** III ~ Gcpf I* II** III ~
Zone 1: Windward Side Wall 0.50 3.6 7.6 5.6 0.40 2.5 6.5 4.5
Zone 2: Windward Roof -0.69 -9.7 -5.7 -7.7 -0.69 -9.7 -5.7 -7.7
Zone 3: Leeward Roof -0.45 -7.1 -3.1 -5.1 -0.37 -6.2 -2.1 -4.1
Zone 4: Leeward Side Wall -0.40 -6.4 -2.4 -4.4 -0.29 -5.3 -1.2 -3.2
Zone 5: Gable Wall -0.45 -7.0 -3.0 -5.0
Zone 6: Gable Wall -0.45 -7.0 -3.0 -5.0
Zone 1E: Windward Side Wall Edge 0.75 6.4 10.4 8.4 0.61 4.8 8.8 6.8
Zone 2E: Windward Roof Edge -1.07 -14.0 -10.0 -12.0 -1.07 -14.0 -10.0 -12.0
Zone 3E: Leeward Roof Edge -0.65 -9.3 -5.3 -7.3 -0.53 -7.9 -3.9 -5.9
Zone 4E: Leeward Side Wall Edge -0.59 -8.6 -4.6 -6.6 -0.43 -6.8 -2.8 -4.8
Wind load should not be less than 10 psf on vertical projection. (ASCE 7-05, 6.1.4.1)
Because the structure is less than 30ft high, the torsional cases 1T, 2T, 3T and 4T do not apply. (ASCE 7-05, Fig. 6-10, note 5)
Minimum Floor Live Load = n/a psf (ASCE 7-05, Table 4-1)
M inimum Roof L ive L oad Top Chord 20 psf
Bottom Chord 0 psf
Total (on horizontal projection) 20 psf (ASCE 7-05, Table 4-1)
Snow L oad Calculations
I nputs:
Horizontal Distance Eave to Ridge, W 38 ft
Equations: W ≤20 ft. (ASCE 7-05, Figure 7-5)
▪0 Windward Unbalanced
▪ (pg)(I) Leeward Unbalanced
W > 20 ft
▪ 0.3*ps Windward Unbalanced
▪ ps + hd(γ)/(√(S)) Leeward Unbalanced, the latter extended from the ridge
a distance of [8(√(S))(hd)]/3
I nter mediate Calculations:
Roof Angle = 16.26 degrees hd = 2.13 ft
g = 17.9 pcf S = Roof slope run for a rise of 1 = 3.4286
punbal, leeward = 43.7 psf for a distance of 10.5 ft from the ridge, then 23.1 psf to eaves
punbal, windward = 6.9 psf
Seismic L oad Calculations
Calculation I nputs:
Building and Site I nputs: Spectral Response Acceleration, S1 0.05
Site Class D Spectral Response Acceleration, SS 0.15
Basic Structural System: Response Modification Factor, R 6.5
All other structural systems: Height to Highest Level (ft), hn 16
Light Framed Walls w/ Shear Panels Weight of Structure (lbs), W 6240
Seismic Design Category: D (ASCE 7-05, 11.6) (9 psf)(72+2 +2 ft)(8 ft)+2(3 psf)(16 ft)(8 ft)
Effective Weight of Structure (lbs), We 5760
(9 psf)(72+2 +2 ft)(8 ft)+2(3 psf)(16 ft)(8 ft)(3/8)
I nter mediate Seismic Calculations Wind Resolved to Hor izontal Point L oad at Eave, Fw
Seismic Use Group II Building Inputs: Load from Roof
Occupancy Importance Factor, I E 1 Fixity Factor 0.375 (lbs)
Sms 0.240 Wind Force with 10 psf min, Fw = 1320 lbs 840
SDs 0.160 Wind Force with Roof and Walls, Fw = 256 lbs -223
Sm1 0.120 Wind Force with Walls only, Fw = 479 lbs 0
SD1 0.080
CT 0.02
Cu 1.7
Acceleration Site Coefficient, Fa 1.6
Velocity Site Coefficient, Fv 2.4
App. Fund. Period, Ta 0.16
Fundamental Period, T 0.27
Seismic Coefficient, Cs 0.025
Cs min 0.007
Cs max 0.045
Seismic Base Shear, V = 154 lbs Controlling Wind Load:
Lateral Seismic Force at Roof, FR = 142 lbs Wind Force per Frame, Fw = 1320 lbs
[F R = 154 x 5760 / 6240 ]
Seismic vs. Wind Compar ison
Controlling Load Combination Strength Comparison Serviceability Comparison
D+W 1320 lbs Wind Controls the Strength Design (D+0.7E)C d < D+W: Wind Controls
D+0.7E 99.3 lbs Serviceability Requirements
Stor y Dr ift and Wind Deflections
Allowable Story Drift = 0.02 hs1 (ASCE 7-05, Table 12.12-1)
Story Height, hs1 = 192 in
Allowable Stor y Dr ift = 3.84 in
Other Deflection Criterion = l/120 (ASCE 7-05, Section 12.12.2 and IBC 2009, Table 1604.3)
Allowable Deflection at Eave = 1.6 in (controlling deflection criterion)
Actual Calculated Deflection = 1.46 in (see DAFI outputs)
Story Drift from Elastic Analysis, δ1e = n/a in (seismic does not control the strength or serviceability design)
Deflection Amplification Factor, Cd = 4.5
Calculated Stor y Dr ift at Eave , δ1 = n/a in
Story drift requirements are satisfied - calculated story drift is less than controlling allowable story drift
Contr olling L oad Combinations
Wall Posts D+0.75(S+W) Post Foundation (Lateral Loading) D+W and 0.6D+W
Roof Diaphragm D+W and 0.6D+W Post Foundation (Uplift) 0.6D+W
Endwall Shearwalls D+W and 0.6D+W Wall Girts D+W and 0.6D+W
Roof Truss D+S Purlins 0.6D+W or D+S
DI APHRAGM DESI GN
k = p/Δ
Eave L oad
f new= 0.42
Pi = 1378 lbs P i = s[ h r (q wr - q lr ) + h w f new (q ww - q lw )]
Summar y of DAFI I nputs
Shear Load in Endwall 1 = 9486 lbf DAFI Output: Load Resisted by Frame 1
Shear Load in Endwall 2 = 8938 lbf DAFI Output: Load Resisted by Frame 16; Wall with 20' Door
Horizontal Diaphragm Shear = 8796 lbf DAFI Output: Largest Diaphragm Shear Load
Shear Load in Endwall 1, V max, 1 = 9486 lbf DAFI Output: Load Resisted by Frame 1
Shear Load in Endwall 2, V max, 2 = 8938 lbf DAFI Output: Load Resisted by Frame 16; Wall with 24' Door
Allowable Shear Strength, va = 110 lbf/ft (with NO.2 DFL girts, Specific Gravity = 0.50)
vmax ≤va <ok> (actual shear in endwalls is less than allowable shear)
Sidewall Shear Str ength Check
Wind Parallel To Ridge
vsidewall ≤va <ok> (actual shear in sidewall is less than allowable shear)
Ch, roof = ch,1 roof + ch2, roof = 19972.8 lbf/in (horizontal stiffness provided by roof sheathing)
Ch, ceiling = 19710 lbf/in (horizontal stiffness provided by ceiling sheathing)
M ax
Total M ax L oad in Shear L oad in
Hor izontal Horizontal
Roof Hor izontal L oad Plane of Plane of Allowable Shear
Stiffness of L oad on θ
Component Stiffness of Ratio Component, Component, L oad, va
Component Component,
Diaphr agm V max, in-plane va
V max, hor izontal
(lbf/in) (lbf/in) (lbs) (deg) (lbs) (lb/ft) (lb/ft)
Roof Sheathing 19973 39683 0.503 4427 16.26 4612 58 110
Ceiling
19710 39683 0.497 4369 0 4369 61 110
Sheathing
vmax ≤va <ok> (actual shear in diaphragm is less than allowable shear)
Roof Diaphr agm Chor d For ces
Load Ratio to Each Diaphragm , p = ch,x/Ch (individual diaphragm stiffness / total diaphragm stiffness)
Load on Roof Diaphragm, w = 172.2 lbf/ft (eave load, Pi , divided by column spacing, s)
2
End Moment, M ex = wxL x /12 (controls the design)
2
Midspan Moment, M mx = wxL x /24
Tension/ Compression Force, Tx = M ex/bx (controlling moment divided by depth of individual diaphragm)
HTP37z Simpson Strap = 1600 lbs (allowable tension capacity as specified by the manufacturer)
MSTA21 Simpson Strap = 1505 lbs (allowable tension capacity as specified by the manufacturer)
Px ≤Pa <ok> (actual tension load is less than allowable tension load)
CONNECTI ONS
ENDWALL CEILING LEDGER TO POSTS CONNECTION
Number of Posts = 10
Number of 16d Nails per Post = 4
M aximum Shear , V max, hor izontal = 4369 lbs (V max, horizontal from Ceiling Diaphragm Shear Strength Check Section)
Allowable Shear Capacity = 9830 lbs
Number of Posts = 10
Number of 16d Nails per Post = 4
M aximum Shear , V max, exter ior = 4551 lbs (V max from Endwall Shear Strength Check Section)
M aximum Shear , V max, inter ior = 4551 lbs (V max from Endwall Shear Strength Check Section)
Allowable Shear Capacity, V a = 6881 lbs
M aximum Tension For ce, T max = 1425 lbs (T x from Roof Diaphragm Chord Forces Section)
Allowable Tension Capacity, T a = 1505 lbs (at splice)
Allowable Tension Capacity, T a = 1474 lbs (at corner post)
REACTI ON Ceiling L edger to Endwall Posts Connection - Shear Tr ansfer fr om Ceiling Diaphr agm to Endwall
Bottom Gir t to Endwall Posts Connection - Shear Tr ansfer fr om I nter ior L iner to Endwall Posts
REACTI ON
Tension Load in Diaphragm Chord (lbs) Tmax 1368 ← Tension force from Roof Diaphragm Chord Forces Section
HTP37Z Simpson Str ap
Number of straps/brackets/hangers 1
Specific Gravity G 0.55
Duration Factor CD 1 C D is included by the manufacturer
Wet Service Factor CM 1
Design Value per strap/bracket/hanger 1850
Total Allowable Capacity (lbs) 1850
Ceiling Joist to Ceiling Joist Connection at Splice, Diaphr agm Tension Chor d
REACTI ON
Tension Load in Diaphragm Chord (lbs) Tmax 1425 ← Tension force from Roof Diaphragm Chord Forces Section
M STA21 Simpson Str ap
AL L OWABL E CAPACI TY
Number of straps/brackets/hangers 1
Specific Gravity G 0.55
Duration Factor CD 1 C D is included by the manufacturer
Wet Service Factor CM 1
Design Value per strap/bracket/hanger 1505
Total Allowable Capacity (lbs) 1505
Tension Load in Diaphragm Chord (lbs) Tmax 1368 ← Tension force from Roof Diaphragm Chord Forces Section
NAI L S - WOOD TO WOOD - SHEAR - NDS 2005, ASD
Nail Size 16d Intermediate Calculations
Number of nails # 5 KD 2.2
Nail Diameter (in) D 0.162 F yb (psi) 90000
Nail Length (in) L 3.5 2+R e = 3.0
Width of Side Member (in) w 1.5 1+2R e = 3.0
AL L OWABL E CAPACI TY
p k2 = 1.02
Specific Gravity of Main Member G 0.55 F em = 5526
Specific Gravity of Side Member 0.55 F es = 5526
Duration Factor CD 1.6 (NDS 2005, Table 2.3.2) Re = 1.0
Wet Service Factor CM 1 p= 2.50
Temperature Factor Ct 1 1+R e = 2.0
Toe Nail Factor Ctn 1 Is 1508
End Grain Factor Ceg 1 (NDS 2005, 11.5.2) III m 374
Depth Penetration Factor Cd 1 (Cd=p/10D) III s 513
Lateral Design Value (lbs) Z 178 (controlling yield value) IV 178
Total Allowable Lateral Capacity (lbs) Z' 284 ← Z'=(# of Nails) x Z x C D x C d x C eg x C tn x C M x C t
Tension Load in Diaphragm Chord (lbs) Tmax 1368 ← Tension force from Roof Diaphragm Chord Forces Section
WOOD SCREWS - WI THDRAWAL - NDS 2005, ASD
Screw Size # 8
Number of screws # 4 (# of effective screws not total)
Screw Diameter (in) D 0.164 Note: if a certain adjustment factor is not shown, its
Screw Length (in) L 3 value is assumed to be 1.0
AL L OWABL E CAPACI TY
1368.48 ÷ 1357 = 1.0082126 The rest can be assumed to be taken by 60d R.S. nail
Ceiling Joist to Cor ner Post Connection, Diaphr agm Tension Chor d
REACTI ON
Tension Load in Diaphragm Chord (lbs) Tmax 1425 ← Tension force from Roof Diaphragm Chord Forces Section
NAI L S - WOOD TO WOOD - SHEAR - NDS 2005, ASD
Nail Size 16d Intermediate Calculations
Number of nails # 6 KD 2.2
Nail Diameter (in) D 0.162 F yb (psi) 90000
Nail Length (in) L 3.5 2+R e = 3.0
Width of Side Member (in) w 1.5 1+2R e = 3.0
AL L OWABL E CAPACI TY
A 0 0 0 0 0 0
B 0 0 0 0 0 0
C 0 0 0 0
D 1.6 0 0 1.6
E 0 0 0 0
A 0 0 0 0 0 0
B 0 0 0 0 0 0
C 0 0 0 0
D 2.4 0 0 2.4
E 0 0 0 0
1 2 3 4 5 6 1E 2E 3E 4E
0 0.4 -0.69 -0.37 -0.29 -0.45 -0.45 0.61 -1.07 -0.53 -0.43
5 0.4 -0.69 -0.37 -0.29 -0.45 -0.45 0.61 -1.07 -0.53 -0.43
16.26 0.498 -0.69 -0.45 -0.4 -0.45 -0.45 0.753 -1.07 -0.65 -0.59
20 0.53 -0.69 -0.48 -0.43 -0.45 -0.45 0.8 -1.07 -0.69 -0.64
0 0 0 0 0 0 0 0 0 0 0
30 0.56 0.21 -0.43 -0.37 -0.45 -0.45 0.69 0.27 -0.53 -0.48
0 0 0 0 0 0 0 0 0 0 0
45 0.56 0.21 -0.43 -0.37 -0.45 -0.45 0.69 0.27 -0.53 -0.48
0 0 0 0 0 0 0 0 0 0 0
90 0.56 0.56 -0.37 -0.37 -0.54 -0.45 0.69 0.69 -0.48 -0.48
2
Wall Component Tributary Area: 21.33 ft
2
Roof Component Tributary Area: 21.33 ft
Roof Slope 16.26 degrees
a= 12 a= 4.8
a= 7.2 a= 2.88
a= 8.5 a= 3
a= 7.2 a= 4.8
a= 7.2
WALL GCp
Zone 4: 0 -1.04 0 -1.04
Zone 5: 0 -1.29 0 -1.29
ROOF GCp
Zone 1 0 -0.97 0 0
θ≤7 Zone 2 0 -1.57 0 0
Zone 3 0 -2.23 0 0
Zone 1 0 -0.86 0 -0.86
7<θ≤27 Zone 2 0 -1.54 0 -1.54
Zone 3 0 -2.4 0 -2.4
Zone 1 0 -0.94 0 0
27<θ≤45 Zone 2 0 -1.14 0 0
Zone 3 0 -1.14 0 0
Zone 1 n/a n/a n/a -0.86
Final
Results
Zone 2 n/a n/a n/a -1.54
Zone 3 n/a n/a n/a -2.4
.
My Range Envelope
1 Enclosed B
2 Partially En
3 Open Build
Wind Speed 90
Building Category II
1 0
Importance Factor 1
2
Wall Component Tributary Area: 21.33 ft
2
Roof Component Tributary Area: 21.33 ft
Roof Slope 16.26 degrees
a= 12 a= 4.8
a= 7.2 a= 2.88
a= 8.5 a= 3
a= 7.2 a= 4.8
a= 7.2
Length = 120 ft
h= 10.5
Clear Obstructed
0 0 0
0 0 0
>2h -0.3 -0.6