EAST GATE

NURGES - A
STRUCTURAL DRAWING
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

STRUCTURAL DRAWING LIST

ST-000

NTS
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

E - STRUCTRURAL CONCRETE NOTES :


E1- CONSTRUCTION JOINTS :

E2-CURING AND SEALING

GENERAL NOTES SHEET (1)

ST-001

E4- EMBEDDED /ATTACHED INSERTS FOR OTHER TRADES :

NTS
NURGES - A
F - FORMWORKS : H- ABBERVIATIONS : K- SYMBOLS :

1- GENERAL :
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

GENERAL NOTES SHEET (2)

ST-002

NTS
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
-
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
- STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
- SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

-
- - -

- STANDARD DETAIL SHEET (1)

- -

-
ST-003

NTS
NURGES - A

-
WALLS OR DROP BEAMS
1 / 5 OF SPAN

1. ALL DIMENSIONS ARE IN MILLIMETERS AND


LEVELS ARE IN METERS UNLESS OTHERWISE

1 / 5 OF SPAN
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
T16 AT 200 O.C.

WALLS OR DROP BEAMS


ADDITIONAL
TOP BARS
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.

T16 AT 200 O.C.


-
-
3. THIS DRAWING SHALL BE READ IN
ADDITIONAL
BOTTOM BARS
CONJUCTION WITH ALL RELEVANT
-
DOCUMENTS & PROJECT SPECIFICATION.
TYPICAL ADDITIONAL SLAB REINFORCEMENT AT CORNER
4. THE CONTRACTOR HAVE TO SUBMIT SHOP
DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

STANDARD DETAIL SHEET (2)

ST-004

NTS
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

-
4. THE CONTRACTOR HAVE TO SUBMIT SHOP
DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

- - 7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

- -

- -

- -

STANDARD DETAIL SHEET (3)

ST-005

NTS
-
NURGES - A
-

-
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

GROUND FLOOR COLUMN AND AXIS

ST-101

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

FIRST FLOOR COLUMN AND AXIS

ST-102

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

ROOF FLOOR COLUMN AND AXIS

ST-103

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

FOUNDATION LAYOUT PLAN

ST-201

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

GROUND FLOOR FRAMING PLAN

ST-301

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

R3
7. TOP & BOTTOM LONGITUDINAL FLEXURAL
REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.
R1
R4

CR
R3 R3
R1
R7

R7
R6 R6 R6

FIRST FLOOR FRAMING PLAN

ST-302

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

R1

R4 R3

CR
R3
R1

R5
R7
R2 R2 R2

CR

ROOF FLOOR FRAMING PLAN

ST-303

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

UPPER ROOF FLOOR FRAMING PLAN

ST-304

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
500 600 500 SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING

200

200

200
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


500 500 600 500
IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

200

200

200

200
6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY
IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

500 200 500 600 600

200

200

200
500 500 600 600 400 400
200

200

200

200

200

200
COLUMN & FOOTING AND DETAILS
GRADE BEAM SCHEDULE

ST-401

NTS
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

BEAM SCHEDULE AND DETAILS

ST-402

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

DETAILS

ST-403

1:100
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

FENCE DETAILS

ST-404

1:25
NURGES - A
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
LEVELS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
2. THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS & SITE CONDITIONS AFFECTING
THE WORK AT SITE.
3. THIS DRAWING SHALL BE READ IN
CONJUCTION WITH ALL RELEVANT
DOCUMENTS & PROJECT SPECIFICATION.

4. THE CONTRACTOR HAVE TO SUBMIT SHOP


DRAWINGS, DETAILS & MATERIALS TO THE
SUPERVISION ENGINEER OR OWNER BEFORE
STARTING ANY WORKS.

5. INCREASE THE BEAM WIDTH TO 100 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 152.4mm(6 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

6. INCREASE THE BEAM WIDTH TO 50 mm LOCALLY


IN ADDITION TO THE WIDTH SHOWN IN THE
SCHEDULE, TO ACCOMMODATE 101.6mm(4 Inches)
SLEEVES IN THE BEAMS AT THE TOILET AREAS.

7. TOP & BOTTOM LONGITUDINAL FLEXURAL


REINFORCEMENT SHALL BE BENT IN 1 TO 12
AS PER ACI DETAILING STANDARDS.

PARAPET DETAILS AND TOILET


SLEEVE 6'' GENERAL DETAILS

ST-405

1:20
NURGES - A