You are on page 1of 4

REVAMPS

Vacuum Unit Revamps


Following vacuum unit revamps, it is not uncommon to have operating problems. Case studies
show how the root cause can be identified using differential pressure measurements.

Daryl W. Hanson
Process Consulting Services Inc., Houston, Texas

Norm P. Lieberman
Process Improvement Engineering, Metairie, LA

T
roubleshooting refinery vacuum unit Column internals generate pressure drop mmHg absolute, most digital gauges read a
revamps(Photo 1) begins with accu- if they are functioning properly, but so will few mmHg low. Special high precision
rate differential pressure measure- liquid level. Because pressure drop gener- gauges are required if accurate pressure
ments. Specific pressure measurement ele- ated by packed column internals is very readings are required. When measuring
vations and detail drawings of the column low, two gauges must be used with the pressure drops, this is not a problem.
internals are essential to properly interpret readings taken simultaneously. To ensure
the data. Without complete information there is no offset between the two instru- Rules of Thumb
wrong conclusions can be drawn from the ments, they should both be connected to Column internals generate pressure drop
differential pressure measurements. Three the same process point and each should and so does liquid head. Properly func-
case studies will show how accurate field have the same reading. By measuring dif- tioning stripping section trays will generate
measured differential pressure can be ferential pressure simultaneously the read- between 3.5-5 mmHg per tray. Liquid level
interpreted incorrectly. These cases present ings are not affected by normal pressure also produces P, therefore 10” of 0.75
only a few of the ways to misinterpret data. variations. specific gravity liquid generates approxi-
When measuring pressures less than 10 mately 13-14 mmHg. Since packing gener-
Measuring Low Pressure
Being able to accurately measure pressures
under deep vacuum requires proper equip-
ment. Acceptable measuring devices are
absolute pressure mercury manometers or
absolute pressure electronic devices.
Moreover, tubing from the instrument to
the process connection must not leak or
measured pressure will be higher than true
process pressure. To test for leaks the pro-
cess isolation valve should be first opened
so that the measuring device reads the
process pressure, then the valve must be
blocked in. If the measured pressure grad-
ually increases then the tubing is leaking, if
it remains constant there is no leak.
If the pressure does not fall to a steady
value within a few seconds, then the con-
nection is partially plugged. The steady
state reading will then read high because a
very minor air leak cannot be completely
off-set by a relatively larger opening into
the connection. Photo 1. Vacuum unit

Reprinted from PTQ Revamps & Operations®, Autumn 2003


REVAMPS

Case 1: sures and the locations. Measured P


Black HVGO Product – across the slop wax (dirty gas oil or over-
“Low” Wash Section flash) collector tray and five feet of wash
Pressure Drop section packing was only 3 mmHg.
Cat feed hydrotreater (CFHT) Interpreting pressure drop correctly
run lengths were being dramati- requires complete knowledge of column
cally reduced by rapid metals internals and how they influence pressure.
Measured deposition on the catalyst. Pressures were taken above the wash bed
20 during survey
Recent refinery configuration and at the same location as the flash zone
Structured changes allowed heavy Mexican pressure instrument. Detailed review of
Packing heavily
packing
coked in middle and Venezuelan crudes contain- vendor drawings showed a vapor horn had
Grid of bed
ing very high vanadium to be been installed; yet it did not appear on the
Slop wax tray
processed. While the vacuum vessel elevation drawing. The flash zone
unit had a history of coking after pressure measurement was taken inside
a 3 year run, switching to heavy the vapor horn.
Actual flash crude caused downstream unit Pressure should never be measured
zone pressure
31 + 8mmHg higher contamination problems in only inside vapor horns because vapor and liq-
Flash zone than inside horn 18 months. CFHT catalyst had uid velocities are very high. Kinetic energy
Transfer Vapor 23 Measured reached end-of-run and an can make the pressure reading lower or
line horn during survey unscheduled outage was momentum from liquid impinging on the
planned. A decision needed to be pressure point can produce readings high-
made to go into the vacuum col- er than the flash zone pressure. Pressure in
umn and replace the packing or the flash zone was 8 mmHg higher than
Absolute pressure, mmHgA continue running. inside the horn. Therefore, the kinetic
A pressure survey was con- energy component of system pressure was
Figure 1. Measured pressures and locations ducted because coke reduces very high causing the measured pressure
packing open area and generates to be lower than the flash zone. Because
ates only 0.375 mm Hg pressure drop per higher P as the coke builds up in the the true pressure drop across the packing
foot of packing, pressure must be mea- packing. Once pressure drop reaches was very high, it confirmed the bed was
sured simultaneously to determine differ- approximately 1 mmHg per foot of pack- badly coked (Photo 2 and 3) and a shut-
ential pressure. Five feet of packing gener- ing, heavy vacuum gas oil (HVGO) prod- down was needed to replace the packing.
ates only 2 mmHg when operating proper- uct will begin to turn black due to vacuum Furthermore, high column pressure drop
ly and 5 mmHg when coke is being formed. tower bottoms (VTB) entrainment. reduced HVGO product yield.
Small variations in operating pressure can Pressures were measured simultaneously Conversely, pressures outside the vapor
materially change the conclusions about in the flash zone and above the wash sec- horn and below the overflash pan can be 3
the condition of a packed bed when a sin- tion because of convenient platform to 6 mmHg lower than the measurement
gle gauge survey is performed. access. Figure 1 shows the measured pres- inside the horn due to liquid impingement

Photo 2. Coked grid Photo 3. Coked structured packing

Reprinted from PTQ Revamps & Operations®, Autumn 2003


REVAMPS

Flash 25 Measured
760
zone
Measured
16 during survey

Structured Packing clean when


packing Five (5)
inspected during sieve Initial P 20 mmHg
Grid turnaround trays
10" Actual P 0 mmHg
liquid With steam 755
No steam 757
Measured 18 18 No liquid head Stripping steam
P across 31 Measured 15" liquid
collector 21 during survey Quench
Slop wax tray LC 45 With steam
(in liquid level) flow 680 LC 45 No steam
25 Reduced
FI liquid level
21 Actual flash zone
15,000 With steam
Transfer line Flash zone pressure + 10mm Hg
lower than at 15,000 No steam
slop wax tray
Pressure, mmHgA

Absolute pressure, mmHgA Temperature, °F


BPD

Figure 2. Pressure measurement at the upper-level tap on the slop Figure 3. Measured pressures above and below the stripping
wax collector, below the wash bed and in the vapor section
space above
on the pressure tap. Using this reading and a short bed, black HVGO product normal operation measured at 60% of
alone, will lead the troubleshooter to a pointed to coke. level. Vapor flowing through the risers
conclusion that the wash zone packing In addition, the pressure survey mea- entrained slop wax that contained vacuum
and overflash tray have high pressure sured 15 mmHg across the wash bed. High tower bottoms from flash zone entrain-
drop, but this is often not so when the P indicated that coke was likely causing ment. Also when tray level was lowered,
refiner opens the tower. The lesson is clear: the black HVGO. Figure 2 shows pressure HVGO product color became a translucent
a pressure tap immediately below the wash was measured at the upper level tap on the dark green. The packed bed was not coked
zone packing should be used to measure slop wax collector, below the wash bed and (Photo 4)!
critical wash zone differential pressure. in the vapor space above. Furthermore,
slop wax tray level measured 60% which Case #3:
Case #2: indicated the upper instrument tap was in Low HVGO Product Yield-
Black HVGO Product –“High” the vapor space. But, slop wax collector “Normal” Stripping Section
Wash Section Pressure Drop trays have no level glass to confirm the Pressure Drop
Black HVGO product contained 1.6 wt % instrument reading is a true level and these HVGO product yield had dropped by
microcarbon residue that increased FCC instruments often do not work. Therefore, 4,000 bpd following start-up even though
catalyst consumption by more that 4 pressure was measured in the flash zone as the same crude rates and blends were
tons/day. Black HVGO is a symptom of a check of slop wax tray liquid level. being processed. Problems with column
wash bed coking, yet the refiner had no Measured flash zone pressure was only boot level instrumentation were common
history of coking. Moreover, flash zone 21 mmHg versus the 31 mmHg measured during start-up and throughout normal
temperature was only 730°F and the wash on the slop wax tray. Level on the tray was operation. High liquid level is the most
bed packing depth was only 4 feet. reduced until the instrument reading was common cause of stripping section tray
Experience shows it is nearly impossible to 15%, at the same time the measured pres- damage. Yet in the most recent turnaround
form coke in short crude vacuum column sure decreased from 31 to 18 mmHg. Thus, no tray damage was found. Until the refin-
(versus visbreaker or hydrocracker) wash the initial pressure reading on the tray er switched to heavier crude, very little
zones. Because entrainment from the flash included 10 inches of liquid, which emphasis was placed on stripping section
zone and wash liquid from the top keep the increased the pressure by 13 mmHg. performance. But as crudes get heavier,
packing sufficiently wetted to avoid “dry- Further review showed that the top of the stripping section performance plays an
out” in short packed beds and operating collector tray risers were 10 inches higher increasing important role in meeting
temperature was only 730°F, coking was than the instrument top tap. Consequently, HVGO product yield targets. Properly
not likely. Yet in spite of low temperature slop wax was overflowing the riser during functioning stripping trays generate 3-5

Reprinted from PTQ Revamps & Operations®, Autumn 2003


REVAMPS

When troubleshooting vacuum column


strippers, the quench flow rate should also
be monitored. If stripping trays are work-
ing properly there will be temperature
drop. Thus when steam is blocked in, the
temperature of the liquid leaving the strip-
ping trays increases, hence quench flow
rate must increase to maintain constant
temperature in the boot or the columns
bottom temperature will increase. When
stripping trays are not working, there is lit-
tle or no change in quench flow rate or bot-
toms temperature when steam is blocked
in.
High liquid level also results in loss of
vacuum due to liquid phase cracking. If
lowering the pool level restores vacuum,
liquid phase cracking is occurring.

Photo 4. Grid without coke THE AUTHORS

Daryl W. Hanson is a chemical


mmHg pressure drop per tray. Because pressure is generated by strip- engineer with Process Consulting
Figure 3 shows measured pressures ping steam and stripped hydrocarbon Services in Houston, TX. His respon-
sibilities include process and equip-
above and below the stripping section. flowing through the sieve holes and liquid ment design. He specializes in all
phases of refinery distillation from
Measured differential pressure was 20 level on the trays, if steam is blocked in, process simulation through field
mmHg or approximately 4 mmHg per tray then the measured pressure drop will nor- inspection. Previously he was lead
process specialist for Koch-Glitsch
so the stripping section appeared to be mally decrease to about 10% or less of nor- Inc. where he was involved with more
working. Stripping trays work by reducing mal values. However, when the steam was than 100 column revamps including
heavy oils and light-ends recovery towers. Hanson has
oil partial pressure, which vaporizes a por- blocked in there was no change in the authored more than 20 technical papers on revamping
and distillation. He holds a BS degree in Chemical
tion of the liquid. Heat for vaporization measured pressure drop. This indicated Engineering from Texas A&M University.
comes from the liquid stream; therefore, that measured pressure included liquid
liquid temperature drops as light material level. By decreasing column bottom level Norman P. Lieberman is an independent refinery
troubleshooter for his company Process Improvement
is stripped. Yet temperature measurements the measured pressure drop decreased to Engineering in Metairie, Louisiana. He specializes in
revamping distillation equipment and correcting process
between the flash zone and the bottom of zero. When stripping steam was put back operating problems. He has authored several books and
the stripping section showed no tempera- in service, measured pressure drop was numerous articles.
ture drop. Further testing was needed to still zero. Hence the trays had been dis-
clarify the inconsistent data. lodged by high liquid level (Photo 5).

Process Consulting Services, Inc.


3400 Bissonnet
Suite 130
Houston, Texas 77005
U.S.A.
Phone: [1]-(713)-665-7046
Fax: [1]-(713)-665-7246
E-mail: info@revamps.com
Website: www.revamps.com

Photo 5. Stripping tray damage

Reprinted from PTQ Revamps & Operations®, Autumn 2003

You might also like